WEG CFW900 drive

Home / WEG / WEG CFW900 drive

WEG CFW900 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW900 high-performance variable speed drive series. Search or filter through the complete fault code directory below.

Next-Gen High Performance VFD Power: 1.1 to 630 kW (1.5 to 900 HP) IoT Ready, Dual Ethernet & STO/SS1
Power Range 1.1 – 630 kW (1.5 – 900 HP)
Supply Voltage 200–240V / 380–480V / 500–690V AC
Control Modes V/f, VVW, Vector Induction & PM Motor
Operator Interface Graphic HMI with Bluetooth® & WPS Mobile

Complete WEG CFW900 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F006, F021, or Overcurrent).

Fault / Alarm and MeaningCause and Remedy
F006

Grid Unbal./Phase Loss

Unbalance or phase loss in the power supply.

Cause:



  • Phase loss at the inverter input.

  • Input voltage unbalance > 5%.

  • Loss of one phase in the power supply.




Note: In case the motor has no load on the shaft or the load is low, this fault may not occur. Actuation time is set to C7.1.1. When C7.1.1=0, the fault is disabled.



Remedy:


Check input grid voltage balance and secure connections on mains lines. Verify there are no open circuit fuses. If required, disable this check by setting parameter C7.1.1 = 0.
A010

Rectifier Overtemp.

Alarm of high temperature measured in the temperature sensors (NTC) of the rectifier modules.

Cause:



  • High ambient temperature around the inverter (> 50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.




Note: It can be disabled by changing the IGBT Overtemp. setting to fault only in parameter C7.5.1.



Remedy:


Clean any dust from heatsink fins. Verify fan operation and clear any blockages. Improve surrounding cabinet ventilation. Check settings in parameter C7.5.1.
F011

Rectifier Overtemp.

Fault of overtemperature measured in the temperature sensors (NTC) of the rectifier modules.

Cause:



  • High ambient temperature around the inverter (> 50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.





Remedy:


Verify fan operation and clean heatsink fins. Improve room/enclosure ventilation as needed to reduce surrounding ambient temperature.
A018

Low Battery Voltage

Low battery voltage alarm.

Cause:



  • The real-time clock internal battery voltage is low.





Remedy:


Perform maintenance to replace the internal battery.
A019

24Vdc Power Supply Overvoltage

24Vdc power supply overvoltage fault.

Cause:



  • Voltage of the 24 Vdc power supply that feeds the control is above the maximum permitted value of 27.4 V cc.





Remedy:


Check the external 24 Vdc supply to ensure it is configured within specifications and is not outputting voltage above 27.4 V.
A020

24Vdc Power Supply Undervoltage

24 Vdc power supply undervoltage fault.

Cause:



  • Voltage of the 24 Vdc power supply that feeds the control is below the minimum permitted value of 22.8 Vdc.





Remedy:


Check the incoming 24 Vdc supply wiring and voltage levels. Ensure the external power source is rated correctly.
F021

DC Link Undervoltage

DC link undervoltage fault.

Cause:


Supply voltage is too low, producing voltage on the DC link (S2.7.1) below the minimum value:

  • Ud < 203 V: Supply voltage 200 V.

  • Ud < 210 V: Supply voltage 208-240 V.

  • Ud < 385 V: Supply voltage 380 V.

  • Ud < 405 V: Supply voltage 400-415 V.

  • Ud < 446 V: Supply voltage 440-460 V.

  • Ud < 487 V: Supply voltage 480 V.

  • Ud < 507 V: Supply voltage 500-525 V.

  • Ud < 557 V: Supply voltage 550-600 V.

  • Ud < 669 V: Supply voltage 660-690 V.

  • Phase loss at the input.

  • Fault on the pre-charge circuit.

  • Parameter C1.1.2 is configured with a value above the rated line voltage.





Remedy:


Verify incoming mains supply. Check input terminals and check for missing phases. Check the pre-charge circuit. Verify the configuration value of parameter C1.1.2.
F022

DC Link Overvoltage

DC link overvoltage fault.

Cause:


Supply voltage is too high, producing voltage on the DC link (S2.7.1) above the maximum permitted value:

  • Ud > 400 V: Models 200-240 V.

  • Ud > 800 V: Models 380-480 V.

  • Ud > 1000 V: Models 500-600 V.

  • Ud > 1200 V: Models 660-690 V.

  • Driven load inertia too high or deceleration ramp set too fast.

  • Parameter C3.5.2.1, C3.5.3.2, or C3.6.1 setting is too high.





Remedy:


Check the incoming mains supply voltage. Increase deceleration ramp time, adjust load inertia, or reduce parameters C3.5.2.1, C3.5.3.2, or C3.6.1.
F025

Pulse Feedback Error

Failure to compare the PWM pulses generated by the control and the output voltages measured by the inverter.

Cause:



  • Motor is disconnected or motor is small in relation to the rated current of the inverter connected to the output.

  • Possible defect on the inverter internal circuits.

  • Problems in the circuit of the STO safety inputs (XC2).




Note: Reset the inverter and try again.



Remedy:


Check output motor cabling connections. Verify STO safety inputs circuit at terminal block XC2. Reset the drive.
F030

IGBT U Desat

Fault of desaturation on the IGBTs of arm U.

Cause:



  • Short circuit between the motor phases U and V or U and W.





Remedy:


Inspect output motor cables and motor terminal box for short circuits between phase U-V or U-W. If motor connections are correct, verify IGBT state.
F034

IGBT V Desat

Fault of desaturation on the IGBTs of arm V.

Cause:



  • Short circuit between the motor phases V and U or V and W.





Remedy:


Inspect output motor cables and motor terminal box for short circuits between phase V-U or V-W. If motor connections are correct, verify IGBT state.
F038

IGBT W Desat

Fault of desaturation on the IGBTs of arm W.

Cause:



  • Short circuit between the motor phases W and U or W and V.





Remedy:


Inspect output motor cables and motor terminal box for short circuits between phase W-U or W-V. If motor connections are correct, verify IGBT state.
F042

Brake IGBT Desat

Fault of desaturation on the dynamic braking IGBT.

Cause:



  • Short circuit on the connecting cables of the dynamic braking.





Remedy:


Check connection cables of the braking resistor for insulation wear or short circuits. Verify the resistance of the dynamic braking resistor.
A046

High Load on the Motor

Motor overload alarm.

Cause:



  • Parameters C7.4.3, C7.4.4, and C7.4.5 settings are configured too low for the used motor.

  • Excessive load at the motor shaft.




Note: This alarm can be disabled by setting parameter C7.4.1 = 0 or 2.



Remedy:


Adjust motor overload protection parameters C7.4.3, C7.4.4, and C7.4.5 to match motor load specifications. Check for mechanical blocks on the motor shaft.
A047

High Load on the IGBTs

IGBT overload alarm.

Cause:



  • High current load at the inverter output.





Remedy:


Check drive load status to lower active current peaks. Ensure motor sizing matches application limits.
F048

Overload on the IGBTs

IGBT overload fault.

Cause:



  • Current at the inverter output is too high.





Remedy:


Reduce motor load or duty cycle to prevent high output current. Verify inverter dimensioning.
A050

IGBT1 U Overtemp.

Alarm of high temperature measured in the temperature sensors (NTC) of the IGBTs.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.




Note: It can be disabled by setting parameter C7.5.1.



Remedy:


Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits.
A051

IGBT1 V Overtemp.

Alarm of high temperature measured in the temperature sensors (NTC) of the IGBTs.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.




Note: It can be disabled by setting parameter C7.5.1.



Remedy:


Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits.
A052

IGBT1 W Overtemp.

Alarm of high temperature measured in the temperature sensors (NTC) of the IGBTs.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.




Note: It can be disabled by setting parameter C7.5.1.



Remedy:


Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits.
F053

IGBT1 U Overtemp.

Fault of overtemperature measured in the temperature sensors (NTC) of the IGBTs.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.





Remedy:


Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature.
F054

IGBT1 V Overtemp.

Fault of overtemperature measured in the temperature sensors (NTC) of the IGBTs.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.





Remedy:


Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature.
F055

IGBT1 W Overtemp.

Fault of overtemperature measured in the temperature sensors (NTC) of the IGBTs.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.





Remedy:


Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature.
A060

IGBT/DRL Junction Overtemp.

High temperature at the junction of the IGBTs or diodes alarm.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.





Remedy:


Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits.
F061

IGBT/DRL Junction Overtemp.

Overtemperature at the junction of the IGBTs or diodes fault.

Cause:



  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Blocked or defective cooling fan.

  • Inverter heatsink is too dirty, preventing proper cooling airflow.





Remedy:


Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature.
F062

Thermal Imbalance

Power module temperature unbalance fault.

Cause:



  • The temperature difference between IGBT modules of the same phase (U, V, W) is above 15 °C.

  • The temperature difference between IGBT modules of different phases (U and V, U and W, V and W) is above 20 °C.

  • The temperature difference between rectifier modules of different phases (R and S, R and T, S and T) is above 20 °C.





Remedy:


Verify balanced operational conditions of the IGBT modular blocks. Ensure fans are running correctly on all power books.
F070

DC Link Short Circuit

Fault of short circuit at the output, DC link, or braking resistor.

Cause:



  • Short circuit between two motor phases.

  • Short circuit on the connecting cables of the dynamic braking.

  • IGBT modules are short-circuited.





Remedy:


Check output motor cabling for phase-to-phase short-circuits. Check dynamic braking connection leads. Verify IGBT module conditions.
F071

Overcur. at the Output

Output overcurrent fault.

Cause:



  • Load inertia too high or deceleration ramp set too fast.

  • Setting parameter C3.4.1 or C3.3.5.1.1 is too high.





Remedy:


Increase deceleration ramp time or reduce load inertia. Check values in parameters C3.4.1 or C3.3.5.1.1.
F072

Motor Overload

Motor overload fault.

Cause:



  • Parameters C7.4.3, C7.4.4, and C7.4.5 settings are configured too low for the used motor.

  • Load on the motor shaft is too high.




Note: This fault can be disabled by setting parameter C7.4.1 = 0 or 3.



Remedy:


Verify motor nominal currents. Check settings of parameters C7.4.3, C7.4.4, and C7.4.5. Check for mechanical load blocks on the motor shaft.
F074

Ground Fault

Overcurrent to ground fault.

Cause:



  • Short circuit to ground in one or more output phases.

  • Motor cable capacitance is too large, resulting in current peaks at the output.




Note: This fault can be disabled by setting parameter C7.2.1 = 0 or 3.



Remedy:


Verify insulation of motor cables and motor winding. If cable capacitance is high, reduce cable length or add an output reactor.
F078

Motor Overtemp.

Cause:


Fault related to the PTC temperature sensor installed on the motor.

  • Load on the motor shaft is too high.

  • Load cycle is too short (high number of starts and stops per minute).

  • High ambient temperature around the motor.

  • Poor contact or short circuit (resistance < 100 Ω) on the wiring connected to the motor thermistor.

  • Motor thermistor not installed.

  • Motor shaft locked.




Note: The fault can be disabled by setting C7.5.2 = 2 or 3. It is necessary to program Slot X analog input and output for PTC function.



Remedy:


Check mechanical load on the motor shaft and optimize start/stop duty cycles. Ensure proper motor cooling. Measure thermistor wire resistance to verify it is > 100 Ω. Confirm correct installation and parameters on Slot X and parameter C7.5.2.
F080

CPU Fault (Watchdog)

Cause:


Inverter control watchdog fault.

  • Electrical noise.





Remedy:


Optimize grounding lines and shield pathways. Ensure control cables are physically separated from high-current power cables.
F084

Self-Diagnostics. Error

Cause:


Self-Diagnostics Fault.

  • Defect on the inverter internal circuits.





Remedy:


Power down the inverter and check internal circuitry. Contact technical support for card evaluation if fault is persistent.
A090

External Alarm

Cause:


External alarm via digital input.

  • DI input wiring programmed to generate external alarms is open.




Note: Necessary to set the DI in parameter C7.10.1.



Remedy:


Check digital input terminal loops and secure connections to prevent open circuit alarms.
F091

External Protection

Cause:


External fault via digital input.

  • DI input wiring programmed to generate external faults is open.




Note: Necessary to set the DI in parameter C7.10.2.



Remedy:


Check digital input terminal loops and ensure external switches are not triggering open circuits.
F099

Invalid Curr. Offset

Cause:


Current measurement circuit has a value out of the standards for zero current.

  • Defect on the inverter internal circuits.





Remedy:


Check the internal current sensors. Board replacement or factory repairs may be necessary.
F104

A/D Converter Error

Cause:


Fault reading the A/D converter that measures the inverter currents and voltages.

  • Defect on the inverter internal circuits.

  • Electromagnetic interference above the level the inverter withstands.





Remedy:


Inspect control module circuits. Verify that general installation grounding, cable shielding, and panel layouts are properly set up to mitigate EMI.
A110

High Motor Temperature

Cause:


Alarm related to the PTC temperature sensor installed on the motor.

  • Load on the motor shaft is too high.

  • Load cycle is too short (high number of starts and stops per minute).

  • High ambient temperature around the motor.

  • Poor contact or short circuit (resistance < 100 Ω) on the wiring connected to the motor thermistor.

  • Motor thermistor not installed.

  • Motor shaft locked.




Note: The alarm can be disabled by setting C7.5.2. It is necessary to program Slot X analog input and output for PTC function.



Remedy:


Check mechanical load, motor bearings, and temperature. Secure thermistor wire terminal screws and verify resistance is not < 100 Ω.
A128

Serial Communication Timeout

Cause:


It indicates that the CFW900 stopped receiving telegrams on the serial interface for a period longer than the setting programmed in C9.3.5.

  • Check network installation, broken cable or fault/poor contact on the connections with the network, and grounding.




Note: Make sure the master always sends telegrams to the equipment within a period shorter than the setting in C9.3.5. It can be disabled by setting C9.3.5=0.0 s.



Remedy:


Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying C9.3.5.
A133

No Power Supply on the CAN Interface

Cause:


It actuates when the CAN interface is powered and lack of power supply to the interface is detected.

  • CAN interface without power supply between pins 1 and 5 of the connector.

  • Power cables switched or reversed.

  • Poor contact on the CAN interface cable or connector.




Note: Measure if there is voltage within the allowed range between pins 1 and 5 of the CAN interface connector.



Remedy:


Check external 24 Vdc supply is active and connected correctly to pins 1 and 5. Verify cable polarity.
A134

Bus Off

Cause:


Bus off error detected on the CAN interface.

  • Verify if there is any short-circuit between the CAN circuit transmission cables.

  • Verify if the cables have not been changed or inverted.

  • Verify if all the network devices use the same baud rate.

  • Verify if termination resistors with the correct values were installed only at the extremes of the main bus.

  • Verify if the CAN network was properly installed.





Remedy:


Verify CAN cabling polarity and check for line shorts. Match network node baud rates. Check termination resistor locations. Cycle power to reestablish communications.
A135

CANopen Off-line

Cause:


It occurs if the state of the CANopen node changes from operational to pre-operational.

  • The master is not sending the guarding/heartbeat telegrams at the programmed time.

  • Communication problems caused by lost telegrams or transmission delays.




Note: Check the operation of the error control mechanisms (Heartbeat/Node Guarding).



Remedy:


Check master configuration times and correct. Address network communication lag or noise.
A136

Master in Idle

Cause:


It actuates when communicating with the DeviceNet network master in Run mode, and transition to Idle mode is detected.

  • The master operation switch or run-bit is in the IDLE state in the host software (refer to master device documentation).





Remedy:


Set the master operation control switch to Run or verify the configuration word bits on the master controller.
A137

DeviceNet connection timeout

Cause:


It indicates that one or more DeviceNet I/O connections has expired. It occurs when, for some reason, after the cyclical communication between the master and the product has started, this communication is interrupted.

  • Check the status of the network master.

  • Check network installation, broken cable or fault/poor contact on the connections with the network.





Remedy:


Check DeviceNet master state. Inspect physical network cables for breaks or loose connections.
A145

SNTP Connection Timeout

Cause:


It indicates that the inverter tried to connect to the NTP server and got no response. It occurs when, for some reason, after starting connection with the NTP server, the server did not return the response requested by the inverter.

  • Incorrect configuration and IP address.

  • Targeted NTP server is no longer active.





Remedy:


Check configuration and IP address. Verify that the NTP server is still active and reachable over the network.
A149

Timeout Modbus TCP

Cause:


It indicates that the device stopped receiving valid telegrams for a period longer than the setting in C9.6.3. The time counting starts as soon as it receives the first valid telegram.

  • Check network installation, broken cable or fault/poor contact on the connections with the network, grounding.

  • The Modbus TCP client is not actively sending telegrams to the equipment in a time shorter than the setting in parameter C9.6.3.




Note: This function can be disabled in parameter C9.6.3.



Remedy:


Check connections, cables, and grounding. Ensure the master/client is sending telegrams faster than the timeout configured in parameter C9.6.3, or adjust C9.6.3 to disable the timeout.
F150

Motor Overspeed

Cause:


Overspeed fault.

  • Incorrect setting of C3.3.2.1.2 and/or C3.3.2.1.3.

  • Crane-type load trips.




Note: Activated when the actual speed exceeds the value of C4.3.1.1.2 x (100 % + C7.7.1) for more than 20 ms.



Remedy:


Verify parameter configurations for C3.3.2.1.2 and C3.3.2.1.3. For hoisting/crane applications, ensure proper load control and braking logic.
A152

Pow.Int. Air Overtemp.

Cause:


High internal air temperature alarm.

  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Defective internal cooling fan (when applicable).




Note: The alarm can be disabled by setting C7.5.1.



Remedy:


Improve enclosure ventilation. Replace any defective internal cooling fans. Set parameter C7.5.1 to adjust alarm behavior if desired.
F153

Pow.Int. Air Overtemp.

Cause:


Internal air overtemperature fault.

  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Defective internal cooling fan (when applicable).





Remedy:


Check local cooling conditions, clear air blockages, and ensure cabinet fans are running correctly.
A154

Cont.Int.Air Overtemp.

Cause:


Control circuit high temperature alarm.

  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Locked or defective fan.

  • Inverter heat sink too dirty.




Note: The alarm can be disabled by setting C7.5.1.



Remedy:


Check cooling fan status, clean heatsink, and improve room airflow. Use C7.5.1 to adjust alarm behavior if desired.
F155

Cont.Int.Air Overtemp.

Cause:


Control circuit overtemperature fault.

  • High ambient temperature around the inverter (>50 °C) and high output current.

  • Locked or defective fan.

  • Inverter heat sink too dirty.





Remedy:


Check cooling fan, clean heatsink, and reduce ambient/room temperatures if too high.
A156

IGBT undertemperature

Cause:


Alarm of undertemperature measured by the sensors in the IGBTs, rectifier, power and/or control below -30 °C.

  • Ambient temperature around the inverter ≤ -30 °C.




Note: The alarm can be disabled by setting C7.5.1.



Remedy:


Verify ambient working temperature. Provide workspace heating if operating in extreme cold. Use parameter C7.5.1 to bypass if desired.
F157

IGBT undertemperature

Cause:


Fault of undertemperature measured by the sensors in the IGBTs, rectifier, power and/or control below -30 °C.

  • Ambient temperature around the inverter ≤ -30 °C.





Remedy:


Check the installation environment. Provide heating element control inside the cabinet for operation in cold environments.
F158

Corrupted settings

Cause:


Inverter settings are invalid.

  • Parameter settings file cannot be restored correctly.




Note: Restore the settings from a backup.



Remedy:


Restore the parameter settings from a validated backup file.
F160

STO90 Fault

Cause:


It indicates to the user that STO90 is in a fault state.

  • Incorrect installation of the safety inputs circuit (STO1 and STO2).

  • Actuation time between the safety inputs (STO1 and STO2) greater than 1 s.

  • Incorrect setting of the safety input type (dry contact or OSSD) on DIP switches S1.

  • DIP switches S2 activated in a state other than the STO state.

  • Incorrect programming of the safety function or programming timeout (2 min).

  • Damage in the electronic circuit of STO90.





Remedy:


Verify safety input circuits. Confirm STO1 and STO2 terminals are balanced and synchronized. Check DIP switches S1/S2 positions. Replace module if defective.
F161

STO90 Off-line

Cause:


It indicates to the user that CFW900 central control has lost communication with STO90.

  • Poor contact between STO90 and CFW900 central control.

  • Damage in the electronic circuit of STO90 or CFW900 central control.





Remedy:


Check terminal contacts and board fitment. Verify central control unit circuit.
F171

Pow. Fan 1 Speed

Cause:


Heat sink fan 1 speed fault.

  • Dirt on the fan blades and rolling bearings.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.
F172

Pow. Fan 2 Speed

Cause:


Heat sink fan 2 speed fault.

  • Dirt on the fan blades and rolling bearings.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.
F173

Pow. Fan 3 Speed

Cause:


Heat sink fan 3 speed fault.

  • Dirt on the fan blades and rolling bearings.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.
F174

Pow. Fan 4 Speed

Cause:


Heat sink fan 4 speed fault.

  • Dirt on the fan blades and rolling bearings.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.
F175

Int. Fan 1 Speed

Cause:


Internal fan 1 speed fault.

  • Dirt on the fan blades and rolling bearings.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Clean fan blades and secure connections. Replace if mechanically failed.
F176

Int. Fan 2 Speed

Cause:


Internal fan 2 speed fault.

  • Dirt on the fan blades and rolling bearings.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Clean fan blades and secure connections. Replace if mechanically failed.
A181

Clock with invalid value

Cause:


Clock with wrong time.

  • Battery low, defective, or not installed.




Note: Set the date and time in C11.1.2.



Remedy:


Configure date and time parameter C11.1.2. Replace the internal battery if discharged or missing.
F185

Pre-charge Protection

Cause:


It indicates pre-charge contactor fault.

  • Defective pre-charge contactor.

  • Command fuse open.

  • Phase loss at input L1/R or L2/S.





Remedy:


Check pre-charge contactor and loop fuses. Verify incoming input phases.
A186

Pow. Fan 1 Speed

Cause:


Heat sink fan low speed alarm.

  • Dirt on the fan blades and rolling bearings.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Clean fan blades and ensure bearing path is clear. Check connections.
A187 / A188 / A189

Pow. Fan 2, 3, 4 Speed

Heatsink fan low speed alarm.

Cause:



  • Dirt on the fan blades and rolling bearings.

  • Defective fan hardware.

  • Defective fan power supply line connection.





Remedy:


Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.
A190 / A191

Int. Fan 1, 2 Speed

Internal fan low speed alarm.

Cause:



  • Dirt on the fan blades and rolling bearings.

  • Defective fan hardware.

  • Defective fan power supply line connection.





Remedy:


Check internal fan blades and clear dirt. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.
F228

Serial Communication Timeout

Cause:


It indicates that the CFW900 stopped receiving telegrams on the serial interface for a period longer than the setting programmed in C9.3.5.

  • Check network installation, broken cable or fault/poor contact on the connections with the network, and grounding.




Note: Make sure the master always sends telegrams to the equipment within a period shorter than the setting in C9.3.5. It can be disabled by setting C9.3.5=0.0 s.



Remedy:


Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying C9.3.5.
F233

No Power Supply on the CAN Interface

Cause:


It actuates when the CAN interface is powered and lack of power supply to the interface is detected.

  • CAN interface without power supply between pins 1 and 5 of the connector.

  • Power cables switched or reversed.

  • Poor contact on the CAN interface cable or connector.




Note: Measure if there is voltage within the allowed range between pins 1 and 5 of the CAN interface connector.



Remedy:


Check external 24 Vdc supply is active and connected correctly to pins 1 and 5. Verify cable polarity.
F234

Bus Off

Cause:


Bus off error detected on the CAN interface.

  • Verify if there is any short-circuit between the CAN circuit transmission cables.

  • Verify if the cables have not been changed or inverted.

  • Verify if all the network devices use the same baud rate.

  • Verify if termination resistors with the correct values were installed only at the extremes of the main bus.

  • Verify if the CAN network was properly installed.





Remedy:


Check CAN high and low wires for short circuits or inverted signals. Match node baud rates across the network. Check termination resistor values and placement.
F235

CANopen Off-line

Cause:


It occurs if the state of the CANopen node changes from operational to pre-operational.

  • The master is not sending the guarding/heartbeat telegrams at the programmed time.

  • Communication problems caused by lost telegrams or transmission delays.




Note: Check the operation of the error control mechanisms (Heartbeat/Node Guarding).



Remedy:


Check master configuration times and correct. Address network communication lag or noise.
F236

Master in Idle

Cause:


It actuates when communicating with the DeviceNet network master in Run mode, and transition to Idle mode is detected.

  • Set the switch that controls the master operation of the master to Run or the corresponding bit on the configuration word of the master software.





Remedy:


Set the master operation control switch to Run or verify the configuration word bits on the master controller (refer to master device documentation).
F237

DeviceNet connection timeout

Cause:


It indicates that one or more DeviceNet I/O connections has expired. It occurs when, for some reason, after the cyclical communication between the master and the product has started, this communication is interrupted.

  • Check the status of the network master.

  • Check network installation, broken cable or fault/poor contact on the connections with the network.





Remedy:


Check DeviceNet master state. Inspect physical network cables for breaks or loose connections.
F249

Modbus TCP Timeout

Cause:


It indicates that the device stopped receiving valid telegrams for a period longer than the setting in C9.6.3.

  • Check network installation, broken cable or fault/poor contact on the connections with the network, grounding.

  • Ensure the Modbus TCP client always sends telegrams to the equipment in a time shorter than the setting in C9.6.3.




Note: This function can be disabled in parameter C9.6.3.



Remedy:


Check connections, cables, and grounding. Ensure the master/client is sending telegrams faster than the timeout configured in parameter C9.6.3, or adjust C9.6.3 to disable the timeout.
A345 / F346 / A348 / F349 / A351 / F352

IGBT P.U/P.V/P.W B1 High Load & Overload

Cause:


Alarm / Fault of overload on IGBT 1 of phase U, V, or W.

  • High current at the inverter output.





Remedy:


Reduce motor load or adjust acceleration parameters to lower active output current levels. Check drive sizing if current remains continuously high.
A354 / F355 / A357 / F358 / A360 / F361

IGBT P.U/P.V/P.W B2 High Load & Overload

Cause:


Alarm / Fault of overload on IGBT 2 of phase U, V, or W.

  • High current at the inverter output.





Remedy:


Reduce motor load or adjust acceleration parameters to lower active output current levels. Check drive sizing if current remains continuously high.
F600

Pulse Update Error

Cause:


Fault related to updating the PWM pulses.

  • Defect on the inverter internal circuits.





Remedy:


Check the physical state of the control board. If the pulse updates are failing, the internal circuitry may be defective.
F606

Power Monitor Comm Lost

Cause:


Communication fault between AUI and PMON.

  • Defect on the inverter internal circuits.

  • Electromagnetic interference above the level the inverter withstands.

  • Power board turned off.





Remedy:


Verify internal power board status. Ensure proper connection cables are secure and grounding pathways are clear of noise interference.
F607

SMM Comm Lost

Cause:


Communication fault between PWC and SMM.

  • Defect on the inverter internal circuits.

  • Electromagnetic interference above the level the inverter withstands.

  • Safety interface board turned off.





Remedy:


Verify safety interface board is powered and seated correctly. Protect connection ports from electromagnetic noise.
F608

Code Flow Failure

Cause:


Internal fault during inverter operation.



Remedy:


Reset the inverter. Load the factory default parameters. If the problem persists, contact WEG assistance.
F609

Model Version Incompatible

Cause:


Inverter model data version is incompatible with the actual firmware.



Remedy:


Contact technical support to arrange the model update.
A700 / F701

HMI Disconnected

Cause:


Alarm / Fault related to the HMI disconnection.

  • Commands configured via HMI, and HMI is not connected to the inverter.





Remedy:


Ensure remote HMI is plugged in and check keypad serial connections.
A702

Inverter Disabled

Cause:


Alarm indicates that the General Enable command is Inactive.

  • Run/Stop command of the SoftPLC application equal to Run, or the movement block was enabled with the inverter in general disable.





Remedy:


Ensure the drive General Enable command is active. Check SoftPLC application logic parameters.
A706

SPLC Refer. Not Progr.

Cause:


Reference not programmed for SoftPLC.

  • It occurs when a movement block is enabled and the speed reference is not set for SoftPLC (check C4.3.1.2).





Remedy:


Ensure local and remote speed reference setups are configured correctly for SoftPLC in parameter C4.3.1.2.
A708 / F709

SoftPLC Not Running

Cause:


SoftPLC application is not running.

  • Check the SoftPLC status in S6.1.1 and the action configuration for application not running in C10.1.3.





Remedy:


Configure and run the SoftPLC application. Check parameters in S6.1.1 and C10.1.3.
F1000

Accessory firmware update error

Cause:


Error during accessory firmware update.

  • Old inverter firmware version.





Remedy:


Update the inverter base firmware to compatible levels.
A1012 / F1013

Default Slot AI1 cable disconnection

Cause:


Analogue input signal set to actual mode is out of the range 4 to 20 mA.

  • AI cable broken (the read value was less than 2 mA for 5 seconds).

  • Poor contact on the signal connection at the terminals.





Remedy:


Inspect AI1 loop cabling for breaks. Tighten screw terminal contacts.
A1014 / F1015

Default Slot AI2 cable disconnection

Cause:


Analogue input signal set to actual mode is out of the range 4 to 20 mA.

  • AI cable broken (the read value was less than 2 mA for 5 seconds).

  • Poor contact on the signal connection at the terminals.





Remedy:


Inspect AI2 loop cabling for breaks. Tighten screw terminal contacts.
F1100

Slot A incompatible accessory

Cause:


Error during accessory firmware update.

  • Old inverter firmware version.





Remedy:


Update the inverter base firmware to support the accessory update.
F1101

Slot A Initialization Error

Cause:


It was not possible to initialize a resource required for the accessory to work.

  • Resource already in use by another accessory.

  • In the case of communication network accessories, only one accessory of each type of network can be connected to the inverter at a time.





Remedy:


Ensure no resource overlapping is present on Slot A. Connect only one network communication accessory at a time.
F1103

Slot A accessory connection

Cause:


Loss of communication with the accessory.

  • Above-supported electromagnetic noise.

  • Vibration above supported limits causing connector problems.

  • Corrupted accessory firmware.





Remedy:


Reduce local electromagnetic noise and structural vibrations. Inspect physical terminals and check accessory board firmware state.
A1104 / F1105

Slot A Temperature Warning / Fault

Temperature or overtemperature inside the Slot A accessory is high.

Cause:



  • Temperature around the inverter is close to or above 60 ºC.





Remedy:


Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits.
A1106 / F1107

Slot A enc. A cable disconnection

Encoder channel A signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1108 / F1109

Slot A enc. B cable disconnection

Encoder channel B signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1110 / F1111

Slot A enc. Z cable disconnection

Encoder channel Z signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.





Remedy:


Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1112 to F1117

Slot A AI1, AI2, AI3 Cable Disconnection

Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
A1118 / F1119

Slot A AI4 Cable Disconnection

Analog input signal AI4 set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
F1125

Slot A temp. sensor wrong hw config

Cause:



  • The sensor type selected by the accessory DIP switches does not match the sensor type configured by parameters.

  • DIP switch configured incorrectly. Check the CFW900-TEMP-01 accessory guide.

  • "Sensor Type" parameter is incorrectly configured (refer to C5.2.6.1).





Remedy:


Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1.
A1126 / F1127

Slot A temperature sensor 1 error

Cause:



  • Sensor 1 cable is broken.

  • Sensor 1 is short-circuited.

  • Sensor 1 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1128 / F1129

Slot A sensor 1 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1130 / F1131

Slot A temperature sensor 2 error

Cause:



  • Sensor 2 cable is broken.

  • Sensor 2 is short-circuited.

  • Sensor 2 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1132 / F1133

Slot A sensor 2 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1134 / F1135

Slot A temperature sensor 3 error

Cause:



  • Sensor 3 cable is broken.

  • Sensor 3 is short-circuited.

  • Sensor 3 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1136 / F1137

Slot A sensor 3 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1138 / F1139

Slot A temperature sensor 4 error

Cause:



  • Sensor 4 cable is broken.

  • Sensor 4 is short-circuited.

  • Sensor 4 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1140 / F1141

Slot A sensor 4 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1142 / F1143

Slot A temperature sensor 5 error

Cause:



  • Sensor 5 cable is broken.

  • Sensor 5 is short-circuited.

  • Sensor 5 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1144 / F1145

Slot A sensor 5 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1146 / F1147

Slot A temperature sensor 6 error

Cause:



  • Sensor 6 cable is broken.

  • Sensor 6 is short-circuited.

  • Sensor 6 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1148 / F1149

Slot A sensor 6 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
F1200

Slot B incompatible accessory

Cause:



  • Error during accessory firmware update.

  • Inverter base firmware is too old.





Remedy:


Update the inverter base software to a compatible version.
F1201

Slot B Initialization Error

Cause:



  • The required operational resource is already occupied/allocated by another accessory.

  • For communication accessories, only one node/accessory of each network type can be active on the inverter at a time.





Remedy:


Review Slot B accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time.
F1203

Slot B accessory connection

Cause:



  • High electromagnetic interference/noise levels.

  • Vibration levels exceed structural limits causing physical connector faults.

  • Accessory card firmware corruption.





Remedy:


Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted.
A1204 / F1205

Slot B Temperature Warning / Fault

Temperature or overtemperature inside the Slot B accessory is high.

Cause:



  • Temperature around the inverter is close to or above 60 ºC.





Remedy:


Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits.
A1206 / F1207

Slot B enc. A cable disconnection

Encoder channel A signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1208 / F1209

Slot B enc. B cable disconnection

Encoder channel B signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1210 / F1211

Slot B enc. Z cable disconnection

Encoder channel Z signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.





Remedy:


Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1212 to F1217

Slot B AI1, AI2, AI3 Cable Disconnection

Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
A1218 / F1219

Slot B AI4 Cable Disconnection

Analog input signal AI4 set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
F1225

Slot B temp. sensor wrong hw config

Cause:



  • The sensor type selected by the accessory DIP switches does not match the sensor type configured by parameters.

  • DIP switch configured incorrectly. Check the CFW900-TEMP-01 accessory guide.

  • "Sensor Type" parameter is incorrectly configured (refer to C5.2.6.1).





Remedy:


Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1.
A1226 / F1227

Slot B temperature sensor 1 error

Cause:



  • Sensor 1 cable is broken.

  • Sensor 1 is short-circuited.

  • Sensor 1 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1228 / F1229

Slot B sensor 1 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1230 / F1231

Slot B temperature sensor 2 error

Cause:



  • Sensor 2 cable is broken.

  • Sensor 2 is short-circuited.

  • Sensor 2 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1232 / F1233

Slot B sensor 2 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1234 / F1235

Slot B temperature sensor 3 error

Cause:



  • Sensor 3 cable is broken.

  • Sensor 3 is short-circuited.

  • Sensor 3 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1236 / F1237

Slot B sensor 3 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1238 / F1239

Slot B temperature sensor 4 error

Cause:



  • Sensor 4 cable is broken.

  • Sensor 4 is short-circuited.

  • Sensor 4 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1240 / F1241

Slot B sensor 4 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1242 / F1243

Slot B temperature sensor 5 error

Cause:



  • Sensor 5 cable is broken.

  • Sensor 5 is short-circuited.

  • Sensor 5 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1244 / F1245

Slot B sensor 5 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1246 / F1247

Slot B temperature sensor 6 error

Cause:



  • Sensor 6 cable is broken.

  • Sensor 6 is short-circuited.

  • Sensor 6 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1248 / F1249

Slot B sensor 6 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
F1300

Slot C incompatible accessory

Cause:



  • Error during accessory firmware update.

  • Inverter base firmware is too old.





Remedy:


Update the inverter base software to a compatible version.
F1301

Slot C Initialization Error

Cause:



  • The required operational resource is already occupied/allocated by another accessory.

  • For communication accessories, only one node/accessory of each network type can be active on the inverter at a time.





Remedy:


Review Slot C accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time.
F1303

Slot C accessory connection

Cause:



  • High electromagnetic interference/noise levels.

  • Vibration levels exceed structural limits causing physical connector faults.

  • Accessory card firmware corruption.





Remedy:


Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted.
A1304 / F1305

Slot C Temperature Warning / Fault

Temperature or overtemperature inside the Slot C accessory is high.

Cause:



  • Temperature around the inverter is close to or above 60 ºC.





Remedy:


Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits.
A1306 / F1307

Slot C enc. A cable disconnection

Encoder channel A signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1308 / F1309

Slot C enc. B cable disconnection

Encoder channel B signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1310 / F1311

Slot C enc. Z cable disconnection

Encoder channel Z signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.





Remedy:


Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1312 to F1317

Slot C AI1, AI2, AI3 Cable Disconnection

Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
A1318 / F1319

Slot C AI4 Cable Disconnection

Analog input signal AI4 set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
F1325

Slot C temp. sensor wrong hw config

Cause:



  • The sensor type selected by the accessory DIP switches does not match the sensor type configured by parameters.

  • DIP switch configured incorrectly. Check the CFW900-TEMP-01 accessory guide.

  • "Sensor Type" parameter is incorrectly configured (refer to C5.2.6.1).





Remedy:


Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1.
A1326 / F1327

Slot C temperature sensor 1 error

Cause:



  • Sensor 1 cable is broken.

  • Sensor 1 is short-circuited.

  • Sensor 1 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1328 / F1329

Slot C sensor 1 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1330 / F1331

Slot C temperature sensor 2 error

Cause:



  • Sensor 2 cable is broken.

  • Sensor 2 is short-circuited.

  • Sensor 2 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1332 / F1333

Slot C sensor 2 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1334 / F1335

Slot C temperature sensor 3 error

Cause:



  • Sensor 3 cable is broken.

  • Sensor 3 is short-circuited.

  • Sensor 3 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1336 / F1337

Slot C sensor 3 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1338 / F1339

Slot C temperature sensor 4 error

Cause:



  • Sensor 4 cable is broken.

  • Sensor 4 is short-circuited.

  • Sensor 4 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1340 / F1341

Slot C sensor 4 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1342 / F1343

Slot C temperature sensor 5 error

Cause:



  • Sensor 5 cable is broken.

  • Sensor 5 is short-circuited.

  • Sensor 5 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1344 / F1345

Slot C sensor 5 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1346 / F1347

Slot C temperature sensor 6 error

Cause:



  • Sensor 6 cable is broken.

  • Sensor 6 is short-circuited.

  • Sensor 6 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1348 / F1349

Slot C sensor 6 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
F1400

Slot D incompatible accessory

Cause:



  • Error during accessory firmware update.

  • Inverter base firmware is too old.





Remedy:


Update the inverter base software to a compatible version.
F1401

Slot D Initialization Error

Cause:



  • The required operational resource is already occupied/allocated by another accessory.

  • For communication accessories, only one node/accessory of each network type can be active on the inverter at a time.





Remedy:


Review Slot D accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time.
F1403

Slot D accessory connection

Cause:



  • High electromagnetic interference/noise levels.

  • Vibration levels exceed structural limits causing physical connector faults.

  • Accessory card firmware corruption.





Remedy:


Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted.
A1404 / F1405

Slot D Temperature Warning / Fault

Temperature or overtemperature inside the Slot D accessory is high.

Cause:



  • Temperature around the inverter is close to or above 60 ºC.





Remedy:


Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits.
A1406 / F1407

Slot D enc. A cable disconnection

Encoder channel A signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1408 / F1409

Slot D enc. B cable disconnection

Encoder channel B signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1410 / F1411

Slot D enc. Z cable disconnection

Encoder channel Z signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.





Remedy:


Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1412 to F1417

Slot D AI1, AI2, AI3 Cable Disconnection

Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
A1418 / F1419

Slot D AI4 Cable Disconnection

Analog input signal AI4 set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
F1425

Slot D temp. sensor wrong hw config

Cause:



  • The sensor type selected by the accessory DIP switches does not match the sensor type configured by parameters.

  • DIP switch configured incorrectly. Check the CFW900-TEMP-01 accessory guide.

  • "Sensor Type" parameter is incorrectly configured (refer to C5.2.6.1).





Remedy:


Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1.
A1426 / F1427

Slot D temperature sensor 1 error

Cause:



  • Sensor 1 cable is broken.

  • Sensor 1 is short-circuited.

  • Sensor 1 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1428 / F1429

Slot D sensor 1 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1430 / F1431

Slot D temperature sensor 2 error

Cause:



  • Sensor 2 cable is broken.

  • Sensor 2 is short-circuited.

  • Sensor 2 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1432 / F1433

Slot D sensor 2 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1434 / F1435

Slot D temperature sensor 3 error

Cause:



  • Sensor 3 cable is broken.

  • Sensor 3 is short-circuited.

  • Sensor 3 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1436 / F1437

Slot D sensor 3 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1438 / F1439

Slot D temperature sensor 4 error

Cause:



  • Sensor 4 cable is broken.

  • Sensor 4 is short-circuited.

  • Sensor 4 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1440 / F1441

Slot D sensor 4 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1442 / F1443

Slot D temperature sensor 5 error

Cause:



  • Sensor 5 cable is broken.

  • Sensor 5 is short-circuited.

  • Sensor 5 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1444 / F1445

Slot D sensor 5 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1446 / F1447

Slot D temperature sensor 6 error

Cause:



  • Sensor 6 cable is broken.

  • Sensor 6 is short-circuited.

  • Sensor 6 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1448 / F1449

Slot D sensor 6 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
F1500

Slot E incompatible accessory

Cause:



  • Error during accessory firmware update.

  • Inverter base firmware is too old.





Remedy:


Update the inverter base software to a compatible version.
F1501

Slot E Initialization Error

Cause:



  • The required operational resource is already occupied/allocated by another accessory.

  • For communication accessories, only one node/accessory of each network type can be active on the inverter at a time.





Remedy:


Review Slot E accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time.
F1503

Slot E accessory connection

Cause:



  • High electromagnetic interference/noise levels.

  • Vibration levels exceed structural limits causing physical connector faults.

  • Accessory card firmware corruption.





Remedy:


Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted.
A1504 / F1505

Slot E Temperature Warning / Fault

Temperature or overtemperature inside the Slot E accessory is high.

Cause:



  • Temperature around the inverter is close to or above 60 ºC.





Remedy:


Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits.
A1506 / F1507

Slot E enc. A cable disconnection

Encoder channel A signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1508 / F1509

Slot E enc. B cable disconnection

Encoder channel B signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.




Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed).



Remedy:


Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1510 / F1511

Slot E enc. Z cable disconnection

Encoder channel Z signal is not detected correctly.

Cause:



  • Broken or disconnected signal cable.

  • Encoder connection error.

  • Encoder has no power supply.





Remedy:


Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage.
A1512 to F1517

Slot E AI1, AI2, AI3 Cable Disconnection

Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
A1518 / F1519

Slot E AI4 Cable Disconnection

Analog input signal AI4 set to 4 to 20 mA mode is out of range.

Cause:



  • Analogue input loop cable is broken (the read value remained under 2 mA for longer than 5 seconds).

  • Poor contact at the signal connection terminal blocks.





Remedy:


Check loops for physical line breaks. Clean and secure terminal connections.
F1525

Slot E temp. sensor wrong hw config

Cause:



  • The sensor type selected by the accessory DIP switches does not match the sensor type configured by parameters.

  • DIP switch configured incorrectly. Check the CFW900-TEMP-01 accessory guide.

  • "Sensor Type" parameter is incorrectly configured (refer to C5.2.6.1).





Remedy:


Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1.
A1526 / F1527

Slot E temperature sensor 1 error

Cause:



  • Sensor 1 cable is broken.

  • Sensor 1 is short-circuited.

  • Sensor 1 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1528 / F1529

Slot E sensor 1 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1530 / F1531

Slot E temperature sensor 2 error

Cause:



  • Sensor 2 cable is broken.

  • Sensor 2 is short-circuited.

  • Sensor 2 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1532 / F1533

Slot E sensor 2 high temp / overtemperature

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.
A1534 / F1535

Slot E temperature sensor 3 error

Cause:



  • Sensor 3 cable is broken.

  • Sensor 3 is short-circuited.

  • Sensor 3 is located in an extremely low temperature environment.





Remedy:


Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters.
A1536

Slot E sensor 3 high temp

Cause:



  • The monitored equipment is operating at high temperature.

  • Fault actuation level configuration error.





Remedy:


Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds.

How to Clear & Reset WEG CFW900 Drive Faults

  1. Keypad Reset: Press the red “O / STOP / RESET” key on the front graphic HMI keypad. If the unit is configured in remote mode (REM), switch to local mode (LOC) before initiating a manual keypad reset.
  2. Digital Input Reset (DI): If assigned in configuration menu C9 (I/O Configuration) to the “Fault Reset” function, pulse the assigned 24V digital input terminal to clear trip status.
  3. WPS PC Software & WPS Mobile: Connect using the embedded dual Ethernet ports, standard USB-C port, or integrated Bluetooth via the WPS Mobile application, and issue a “Fault Reset” command from the diagnostics dashboard.
  4. Industrial Ethernet / Fieldbus: Assert Bit 7 (Fault Reset) in the Control Word (S1.6.3 / CIP Bit 2) via native EtherNet/IP, Modbus TCP, Profinet, or RS485 Modbus RTU communications.
  5. Power Cycle: Disconnect the three-phase AC mains supply, wait at least 10 minutes until the DC bus capacitors completely discharge and the HMI display extinguishes, then re-apply input power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect incoming power and wait a minimum of 10 minutes for intermediate DC bus link capacitors to fully discharge. Confirm with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+UD] and [-UD] (or dynamic braking terminal [BR]) before removing terminal covers or touching motor output connections U, V, and W on the WEG CFW900 drive.