Yaskawa FP605 Drive Fault Codes & Diagnostic Guide

Comprehensive fault code directory, trip alarm causes, and step-by-step diagnostic procedures for the Yaskawa FP605 industrial fan and pump AC drive series. Search or filter through the complete fault code database below.

Industrial Fan & Pump AC Drive Power: 2.2 to 450 kW (3 to 600 HP) Embedded Safe Torque Off (STO SIL3 / PLe)
Power Range 2.2 – 450 kW (3 – 600 HP)
Supply Voltage 200–240V / 380–480V (3-Phase)
Control Modes V/f Control, Vector (OLV), PM EZ Vector
Operator Interface 32-Char LCD Keypad with Status Ring (USB-OTG)

Complete Yaskawa FP605 Drive Fault Code Directory

Use the search box in the table below to quickly find your fault or alarm code (e.g., type oC, ov, GF, or Overcurrent).

Fault Code and MeaningCause and Remedy
AUXFB
PI Aux Feedback Level Loss

Cause: The analog input from the terminal set for PI Auxiliary Control Feedback Level [H3-xx = 27] is more than 21 mA or less than 3 mA for longer than 1 s.



Remedy:

  • Repair transducer or wiring.

  • Do a Fault Reset to clear the fault.


bAT
Keypad Battery Low Voltage

Cause: The keypad battery voltage is low.



Remedy:

  • Replace the keypad battery.

  • Note: Use o4-24 [bAT Detection Selection] to enable/disable bAT detection.


bCE
Bluetooth Communication Fault

Cause:

  • The smartphone or tablet with DriveWizard Mobile or DriveWizard installed is too far from the keypad.

  • Radio waves from a different device are causing interference.




Remedy:

  • Use the smartphone or tablet 10 m (32.8 ft) or nearer to the keypad.

  • Make sure that no device around the keypad uses the same radio bandwidth (2400 MHz to 2480 MHz).

  • Do a Fault Reset to clear the fault.


bUS
Option Communication Error

Cause:

  • The drive did not receive a signal from the controller.

  • Communications cable wiring is incorrect, disconnected, or short-circuited.

  • Electrical interference caused a communication data error.

  • The option is incorrectly installed or damaged.




Remedy:

  • Correct wiring errors and repair short circuits.

  • Replace defective cables.

  • Examine control/main circuit lines and ground wiring to decrease interference.

  • Install a noise filter on the input side.

  • Correctly install the option to the drive.

  • If fault continues, replace the option.


CE
Modbus Communication Error

Cause:

  • Communications cable wiring is incorrect, short-circuited, or not connected.

  • Electrical interference caused a communication data error.




Remedy:

  • Correct wiring errors and repair short circuits.

  • Replace defective communications cables.

  • Check magnetic contactors for interference; use Surge Protective Device if necessary.

  • Use recommended shielded lines and ground the shield properly.

  • Separate communication wiring from drive power lines.


CoF
Current Offset Fault

Cause:

  • The drive starts operation while the induced voltage stays in the motor (during coasting to a stop or after fast deceleration).

  • A drive hardware problem occurred.




Remedy:

  • Make a sequence that does not restart operation when induced voltage stays in the motor.

  • Set b3-01 = 1 [Speed Search at Start Selection = Enabled].

  • Do a Fault Reset to clear the fault or de-energize the drive.

  • If the fault stays, replace the drive.


CPF00
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF01
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF02
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF03
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF06
Control Circuit Error (EEPROM memory Data Error)

Cause:

  • The drive power supply was de-energized while a communication option entered a parameter Write command.

  • An EEPROM peripheral circuit error occurred.




Remedy:

  • Set A1-03 = 2220, 3330 to initialize the drive.

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF07
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF08
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF11
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF12
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF13
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF14
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF16
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF17
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF18
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF19
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF20
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF21
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF22
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF23
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF24
Control Circuit Error (Drive Unit Signal Fault)

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF26
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF27
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF28
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF29
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF30
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF31
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF32
Control Circuit Error

Cause: A drive hardware problem occurred.



Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF33
Control Circuit Error

Cause: A drive hardware problem occurred.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.


CPF34
Control Circuit Error

Cause: A drive hardware problem occurred.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF35
Control Circuit Error

Cause: A drive hardware problem occurred.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF36
Control Circuit Error

Cause: A drive hardware problem occurred.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF37
Control Circuit Error

Cause: A drive hardware problem occurred.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF38
Control Circuit Error

Cause: A drive hardware problem occurred.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


CPF39
Control Circuit Error

Cause: A drive hardware problem occurred.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.


dEv
Speed Deviation

Cause:
The load is too heavy; Acceleration/deceleration times are set too short; The dEv detection level settings are incorrect; The load is locked up; The holding brake is stopping the motor.


Remedy:

  • Decrease the load.

  • Increase the values set in C1-01 to C1-04 [Acceleration/Deceleration Time].

  • Adjust F1-10 [Speed Deviation Detection Level] and F1-11 [Speed Deviation Detect Delay Time].

  • Examine the machine.

  • Release the holding brake.


DIFF
Differential Feedback Exceeded

Cause:
The difference between the PID Feedback and Differential Level Source is more than the level set in Y4-18 for the time set in Y4-19.


Remedy:

  • Replace the feedback transducer or transducers.

  • Make sure that the settings of Y4-18 [Differential Level] to Y4-20 [Differential Level Detection Sel] are correct.


dv7
Polarity Judge Timeout

Cause:
There is a disconnection in the motor coil winding; The screws on the drive output terminals are loose.


Remedy:

  • Measure the motor line-to-line resistance and replace the motor if a coil is disconnected.

  • Tighten the terminal screws to the correct tightening torque.


EF0
Option Card External Fault

Cause:
The communication option received an external fault from the controller; A programming error occurred on the controller side.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input from the controller.

  • Examine the operation of the controller program.


EF1
External Fault (Terminal S1)

Cause:
MFDI terminal S1 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S1.

  • Correctly set the MFDI (H1-01).


EF2
External Fault (Terminal S2)

Cause:
MFDI terminal S2 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S2.

  • Correctly set the MFDI (H1-02).


EF3
External Fault (Terminal S3)

Cause:
MFDI terminal S3 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S3.

  • Correctly set the MFDI (H1-03).


EF4
External Fault (Terminal S4)

Cause:
MFDI terminal S4 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S4.

  • Correctly set the MFDI (H1-04).


EF5
External Fault (Terminal S5)

Cause:
MFDI terminal S5 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S5.

  • Correctly set the MFDI (H1-05).


EF6
External Fault (Terminal S6)

Cause:
MFDI terminal S6 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S6.

  • Correctly set the MFDI (H1-06).


EF7
External Fault (Terminal S7)

Cause:
MFDI terminal S7 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S7.

  • Correctly set the MFDI (H1-07).


EF8
External Fault (Terminal S8)

Cause:
MFDI terminal S8 caused an external fault through an external device; The wiring is incorrect; External Fault parameters set incorrectly.


Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input in the MFDI.

  • Correctly connect the signal line to MFDI terminal S8.

  • Correctly set the MFDI (H1-08).


Err
EEPROM Write Error

Cause:
There was a problem with the EEPROM hardware; Electrical interference corrupted the data while it was writing to the EEPROM.


Remedy:

  • Re-energize the drive.

  • If the fault stays, replace the control board or the drive.

  • Push ENTER Key.

  • Set the parameters again.


FAn1
Drive Cooling Fan Fault

Cause:
The cooling fan stopped operating correctly; The circulation fan is damaged.


Remedy:

  • Examine cooling fan operation.

  • Re-energize the drive.

  • Examine U4-03 and U4-04. If performance life expired or fan damaged, replace fan.

  • Examine circulation fan operation.


FDBKL
WIRE Break

Cause:
The analog input from the terminal set for PID Feedback is more than 21mA or less than 3mA for longer than 1s.


Remedy:

  • Make sure that you install the PID feedback source and it operates correctly.


GF
Ground Fault

Cause:
Overheating caused damage to the motor/insulation; Main circuit cable contacting ground; Increase in stray capacitance; Problem with drive hardware.


Remedy:

  • Measure motor insulation resistance and replace motor if necessary.

  • Examine motor main circuit cable for damage and repair.

  • If wiring length > 100m, decrease carrier frequency.

  • Decrease stray capacitance.

  • Replace the control board or the drive.


HFB
High Feedback Sensed

Cause:
The feedback level is more than the level set in Y1-11 for the time set in Y1-12.


Remedy:

  • Decrease the feedback level less than Y1-11.

  • Set Y1-11 and Y1-12 correctly.


HIAUX
High PI Aux Feedback Level

Cause:
PI Auxiliary Feedback is more than the level set in YF-12 for the time set in YF-13.


Remedy:

  • Decrease the PI Auxiliary Feedback level less than YF-12.

  • Set YF-12 and YF-13 correctly.


HLCE
High Level Communication Errors

Cause:
Communication data error occurred between the option and the master drive when using Gateway function.


Remedy:

  • Examine the wiring between the option and the master drive and remove the cause of the fault.


HWL
High Water Level

Cause:
The digital input terminal set to High Water Level is activated, deactivated, or defective (depending on setting).


Remedy:

  • Decrease the water level.

  • Adjust the terminal set to H1-xx = BC or 1BC.


LF
Output Phase Loss

Cause:
Motor main circuit cable disconnected; Disconnection in motor coil; Loose output terminal screws; Drive capacity mismatch; Using single-phase motor; Output transistor damaged.


Remedy:

  • Connect motor main circuit cable wiring. Correct wiring errors.

  • Measure motor Line-to-Line Resistance and replace motor if coil is disconnected.

  • Tighten terminal screws to correct torque.

  • Examine drive capacity vs motor output.

  • (Drive cannot operate single-phase motor).

  • Re-energize drive. If fault stays, replace control board or drive.


LF2
Output Current Imbalance

Cause:
Phase loss in wiring on output side; Loose terminal screws; Imbalance between three phases of PM motor impedance; Drive output circuit broken.


Remedy:

  • Examine for wiring errors or disconnected wires and repair.

  • Tighten terminal screws to correct torque.

  • Measure Line-to-Line Resistance and replace motor if necessary.

  • Re-energize drive. If fault stays, replace control board or drive.


LFB
Low Feedback Sensed

Cause:
The feedback level is less than the level set in Y1-08 for the time set in Y1-09.


Remedy:

  • Increase the feedback level to more than Y1-08.

  • Set Y1-08 and Y1-09 correctly.


LOAUX
Low PI Aux Feedback Level

Cause:
PI Auxiliary Feedback is less than the level set in YF-09 for the time set in YF-10.


Remedy:

  • Increase the PI Auxiliary Feedback level to be more than YF-09.

  • Set YF-09 and YF-10 correctly.


LOP
Loss of Prime

Cause: The drive used the Y1-18 [Prime Loss Detection Method] setting and measured a pump load that is less than the level set in Y1-19 for the time set in Y1-20, and the output frequency is Y1-21 or more.



Remedy:

  • Examine for a dry well, air in the system, or no water in the system. Use preferred priming method suggested by the pump manufacturer to restart the pump.

  • When there is resistance in the pump, let the system pump water again.

  • Set Y1-18 to Y1-21 correctly.

  • Note: Do a Fault Reset to clear the fault.


LWL
Low Water Level

Cause: The digital input terminal set to H1-xx = BB [Low Water Level] is activated/defective, or the terminal set to H1-xx = 1BB [!Low Water Level] is deactivated/defective.



Remedy:

  • Increase the water level.

  • Adjust the terminal set to H1-xx = BB or 1BB.


NMS
Setpoint Not Met

Cause: The feedback deviates from the setpoint at a level more than Y1-15 [Maximum Setpoint Difference] for the time set in Y1-16.



Remedy:

  • Examine for a blocked impeller, over cycling, or broken pipe.

  • Set Y1-15 and Y1-16 correctly.


nSE
Node Setup Error

Cause: The drive received a Run command while the Node Setup function was active.



Remedy:
Stop the drive when the Node Setup function is in use.
oC
Overcurrent

Cause:

  • The load is too large.

  • Overheating caused damage to the motor or motor insulation is not satisfactory.

  • Short circuit or ground fault on the output side (cables or motor).

  • Acceleration time is too short.

  • The drive is operating a specialized motor or a motor larger than the drive's rating.

  • A magnetic contactor was switched at the output.




Remedy:

  • Measure current flowing into the motor. Replace drive with larger capacity if necessary.

  • Measure motor insulation resistance; replace motor if insulation is unserviceable.

  • Check motor main circuit cable for short circuits or ground faults. Repair or replace cable.

  • Increase Acceleration Times (C1-01/C1-03) or S-Curve Characteristics (C2-01 to C2-04).

  • Ensure motor nameplate rating does not exceed drive rating.

  • Set operation sequence to not switch the magnetic contactor while the drive is outputting voltage.


OD
Output Disconnect

Cause: The output circuit between the drive and the motor is open, and the drive output current is less than 5% of E2-01.



Remedy:
Close the disconnected output circuit between the drive and the motor.
oFA00
Option Not Compatible with Port

Cause: The option connected to connector CN5-A is not compatible. This may occur if DIP switches on JOHB-SMP3 are not set to a valid protocol.



Remedy:

  • Connect the option to the correct connector.

  • Remove power, wait for charge light to go off, then set DIP switches on the JOHB-SMP3 to the desired protocol.


oFA01
Option Fault/Connection Error

Cause: The option card connected to connector CN5-A is not compatible.



Remedy:

  • De-energize the drive.

  • Refer to the option card manual and correctly connect the option card to the connector on the drive.


oFA02
Duplicate Options

Cause: The same option cards or the same type of option cards are connected to connectors CN5-A and B.



Remedy:
Connect the option card to the correct connector.
oFA03
Diagnostic Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA04
Flash Write Mode

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA05
Option A/D Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA06
Option Communication Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA10
Option RAM Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA11
Option Ope Mode Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA12
Drive Receive CRC Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA13
Drive Receive Frame Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA14
Drive Receive Abort Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA15
Option Receive CRC Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA16
Option Receive Frame Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA17
Option Receive Abort Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA30
COM ID Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA31
Type Code Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA32
SUM Check Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA33
Option Receive Time Over

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA34
Memobus Time Over

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA35
Drive Receive Time Over 1

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA36
CI Check Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA37
Drive Receive Time Over 2

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA38
Control Reference Error

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA39
Drive Receive Time Over 3

Cause: A fault occurred in the option card.



Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


oFA40

CtrlResSel 1Err

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFA41

Drive Receive Time Over 4

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFA42

CtrlResSel 2Err

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFA43

Drive Receive Time Over 5

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb00

Option Not Compatible with Port

Cause:
The option connected to connector CN5-B is not compatible.


Remedy:

  • Connect the option to the correct connector.


Note: The communication options cannot connect to connector CN5-B.

Do a Fault Reset to clear the fault.

oFb01

Option Fault/Connection Error

Cause:
The option card connected to connector CN5-B was changed during operation.


Remedy:

  • De-energize the drive.

  • Refer to the option card manual and correctly connect the option card to the connector on the drive.


Note: Do a Fault Reset to clear the fault.
oFb02

Duplicate Options

Cause:
The same option cards or the same type of option cards are connected to connectors CN5-A and B.


Remedy:

  • Connect the option card to the correct connector.


Note: Do a Fault Reset to clear the fault.
oFb03

Diagnostic Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb04

Flash Write Mode

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb05

Option A/D Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb06

Option Communication Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb10

Option RAM Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb11

Option Ope Mode Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb12

Drive Receive CRC Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb13

Drive Receive Frame Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb14

Drive Receive Abort Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb15

Option Receive CRC Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb16

Option Receive Frame Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oFb17

Option Receive Abort Error

Cause:
A fault occurred in the option card.


Remedy:

  • De-energize the drive.

  • Make sure that the option card is correctly connected to the connector.

  • If the problem continues, replace the option card.


Note: Do a Fault Reset to clear the fault.
oH

Heatsink Overheat

Cause:
The ambient temperature is high and the heatsink temperature of the drive is more than the value set in L8-02 [Overheat Alarm Level].


Remedy:

  • Measure the ambient temperature.

  • Increase the airflow in the control panel.

  • Install a cooling device (cooling fan or air conditioner) to lower the ambient temperature.

  • Remove objects near the drive that are producing too much heat.




Cause:
The load is too heavy.


Remedy:

  • Measure the output current.

  • Decrease the load.

  • Decrease the value set in C6-02 [Carrier Frequency Selection].




Cause:
The internal cooling fan of the drive stopped.


Remedy:

  • Use the procedures in this manual to replace the cooling fan.

  • Set o4-03 = 0 [Fan Operation Time Setting = 0 h].


oH1

Heatsink Overheat

Cause:
The ambient temperature is high and the heatsink temperature of the drive is more than the oH1 detection level.


Remedy:

  • Measure the ambient temperature.

  • Increase the airflow in the control panel.

  • Install a cooling device (cooling fan or air conditioner) to lower the ambient temperature.

  • Remove objects near the drive that are producing too much heat.




Cause:
The load is too heavy.


Remedy:

  • Measure the output current.

  • Decrease the load.

  • Decrease the value set in C6-02 [Carrier Frequency Selection].


oH3

Motor Overheat (PTC Input)

Cause:
The thermistor wiring that detects motor temperature is defective.


Remedy:

  • Correct wiring errors.




Cause:
A fault occurred on the machine. Example: The machine is locked.


Remedy:

  • Examine the machine and remove the cause of the fault.





Cause:
The motor has overheated.


Remedy:

  • Check the load level, acceleration/deceleration time, and motor start/stop frequency (cycle time).

  • Decrease the load.

  • Increase the values set in C1-01 to C1-04.

  • Set E2-01 [Motor Rated Current (FLA)] correctly.

  • Make sure that the motor cooling system is operating correctly, and repair or replace it if it is damaged.

  • Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2, adjust E3-04 to E3-10. Decrease values in E1-08 and E1-10.


oH4

Motor Overheat Fault (PTC Input)

Cause:
The motor has overheated.


Remedy:

  • Check the load level, acceleration/deceleration time, and motor start/stop frequency (cycle time).

  • Decrease the load.

  • Increase the values set in C1-01 to C1-04.

  • Set E2-01 [Motor Rated Current (FLA)] correctly.

  • Make sure that the motor cooling system is operating correctly.

  • Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2, adjust E3-04 to E3-10.


Note: If E1-08 and E1-10 are set too low, the overload tolerance will decrease at low speeds.
oL1

Motor Overload

Cause:
The load is too heavy.


Remedy:

  • Decrease the load.

  • Reset oL1 when U4-16 < 100.




Cause:
The acceleration/deceleration times or cycle times are too short.


Remedy:

  • Examine the acceleration/deceleration times and the motor start/stop frequencies.

  • Increase the values set in C1-01 to C1-04.




Cause:
Overload occurred while running at low speed.


Remedy:

  • Decrease the load when running at low speed.

  • Increase the motor speed.

  • If the motor is run frequently at low speeds, replace the motor with a larger motor or use a drive-dedicated motor.




Cause:
L1-01 [Motor Overload (oL1) Protection] is set incorrectly.


Remedy:

  • Set L1-01 in as specified by the motor qualities for a drive-dedicated motor.




Cause:
The V/f pattern does not fit the motor qualities.


Remedy:

  • Examine the ratios between the V/f pattern frequency and voltage. Decrease the voltage if it is too high compared to the frequency.

  • Adjust E1-04 to E1-10. For motor 2, adjust E3-04 to E3-10. Decrease values in E1-08 and E1-10.




Cause:
E1-06 [Base Frequency] is set incorrectly.


Remedy:

  • Set E1-06 to the rated frequency shown on the motor nameplate.




Cause:
One drive is operating more than one motor.


Remedy:

  • Set L1-01 = 0 [Disabled], connect thermal overload relay to each motor to prevent damage to the motor.





Cause:
The electronic thermal protector qualities and the motor overload properties do not align.


Remedy:

  • Examine the motor qualities and set L1-01 correctly.

  • Connect a thermal overload relay to the motor.




Cause:
The electronic thermal protector is operating at an incorrect level.


Remedy:

  • Set E2-01 [Motor Rated Current (FLA)] correctly to the value specified by the motor nameplate.




Cause:
There is increased motor loss from overexcitation operation.


Remedy:

  • Lower the value set in n3-13 [OverexcitationBraking (OEB) Gain].

  • Set L3-04 ≠ 4.

  • Set n3-23 = 0.




Cause:
The speed search-related parameters are set incorrectly.


Remedy:

  • Examine the settings for all speed search related parameters.

  • Adjust b3-03.

  • Set b3-24 = 1 after Auto-Tuning.




Cause:
Phase loss in the input power supply is causing the output current to change.


Remedy:

  • Make sure that there is no phase loss, and repair problems.




Cause:
Overload occurred during overexcitation deceleration.


Remedy:

  • Decrease the value set in n3-13.

  • Decrease the value set in n3-21.


oL2

Drive Overload

Cause:
The load is too large.


Remedy:

  • Decrease the load.




Cause:
The acceleration/deceleration times or cycle times are too short.


Remedy:

  • Examine the acceleration/deceleration times and the motor start/stop frequencies.

  • Increase the values set in C1-01 to C1-04.




Cause:
The V/f pattern does not fit the motor qualities.


Remedy:

  • Examine the ratios between the V/f pattern frequency and voltage. Decrease the voltage if it is too high compared to the frequency.

  • Adjust E1-04 to E1-10. Decrease values in E1-08 and E1-10. For motor 2, adjust E3-04 to E3-10.




Cause:
The drive capacity is too small.


Remedy:

  • Replace the drive with a larger capacity model.




Cause:
Overload occurred while running at low speed.


Remedy:

  • Decrease the load when running at low speed.

  • Replace the drive with a larger capacity model.

  • Decrease the value set in C6-02 [Carrier Frequency Selection].




Cause:
The torque compensation gain is too large.


Remedy:

  • Decrease the value set in C4-01 [Torque Compensation Gain] to make sure that the motor does not stall.




Cause:
The speed search-related parameters are set incorrectly.


Remedy:

  • Examine the settings for all speed search-related parameters.

  • Adjust b3-03.

  • Set b3-24 = 1 after Auto-Tuning.




Cause:
Phase loss in the input power supply is causing the output current to change.


Remedy:

  • Correct errors with the wiring for main circuit drive input power.

  • Make sure that there is no phase loss, and repair problems.




Cause:
Overload occurred during overexcitation deceleration.


Remedy:

  • Decrease the value set in n3-13.

  • Decrease the value set in n3-21.


oL3
Overtorque Detection 1

Cause: A fault occurred on the machine (e.g., machine is locked) OR parameters are incorrect for the load.



Remedy:

  • Examine the machine and remove the cause of the fault.

  • Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque Detection Time 1] settings.


oL4
Overtorque Detection 2

Cause: A fault occurred on the machine (e.g., machine is locked) OR parameters are incorrect for the load.



Remedy:

  • Examine the machine and remove the cause of the fault.

  • Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque Detection Time 2] settings.


oL7
High Slip Braking Overload

Cause: Load inertia too large, external force rotated motor, or HSB Overload Time (n3-04) is too small.



Remedy:

  • Decrease deceleration times in C1-02 and C1-04 for applications not using High Slip Braking.

  • Increase the value set in n3-04.

  • Connect a thermal overload relay to the motor and set n3-04 = 1200 s.


oPr
Keypad Connection Fault

Cause: Keypad not securely connected or connection cable is disconnected.



Remedy:

  • Examine the connection between the keypad and the drive.

  • Remove the keypad and connect it again.

  • If the cable is damaged, replace it.


oS
Overspeed

Cause: There is overshoot.



Remedy:

  • Decrease C5-01 [ASR Proportional Gain 1] and increase C5-02 [ASR Integral Time 1].


ov
Overvoltage

Cause: Deceleration time too short (regenerative energy flowing to drive).



Remedy:

  • Set L3-04 = 1 [Stall Prevention during Decel = General Purpose].

  • Increase C1-02 or C1-04 [Deceleration Times].

  • Perform Deceleration Rate Auto-Tuning.




Cause: Acceleration time too short.



Remedy:

  • Increase C1-01 or C1-03 [Acceleration Times].

  • Increase C2-02 [S-Curve Time @ End of Accel].

  • Set L3-11 = 1 [Overvoltage Suppression Select = Enabled].




Cause: Output cable/motor shorted to ground (charging main circuit capacitor).



Remedy:

  • Examine motor main circuit cable, terminals, and terminal box; remove ground faults.

  • Re-energize the drive.




Cause: Speed search parameters incorrect (during speed search, power loss recovery, or premium efficiency motor usage).



Remedy:

  • Set b3-19 ≠ 0 [Speed Search Restart Attempts].

  • Adjust b3-03 [Speed Search Deceleration Time].

  • Do Stationary Auto-Tuning for Line-to-Line Resistance, then set b3-24 = 1.

  • Increase L2-04 [Powerloss V/f Recovery Ramp Time].




Cause: Power supply voltage too high.



Remedy:

  • Decrease power supply voltage to align with drive rated voltage.




Cause: Electrical interference.



Remedy:

  • Examine control/main circuit lines and ground wiring.

  • Ensure magnetic contactor is not the source of interference; use Surge Protective Device.




Cause: Load inertia set incorrectly or Motor hunting.



Remedy:

  • Adjust L3-25 [Load Inertia Ratio].

  • Adjust n1-02 [Hunting Prevention Gain] and n8-45/n8-47.


ov2
DC Bus Overvoltage 2

Cause: Wiring is too long and DC bus voltage is too large.



Remedy:

  • Shorten the shielded motor cable.

  • Decrease the carrier frequency.

  • Switch on internal EMC filter (if power supply has neutral ground).


PE1
PLC Fault 1

Cause: The communication option detected a fault.



Remedy:

  • Refer to the manual for the communication option card.


PE2
PLC Fault 2

Cause: The communication option detected a fault.



Remedy:

  • Refer to the manual for the communication option card.


PF
Input Phase Loss

Cause: Input phase loss, loose wiring, or voltage changing too much.



Remedy:

  • Correct errors with wiring for main circuit drive input power.

  • Tighten terminal screws to correct torque.

  • Examine input power stability and magnetic contactor.

  • Set L8-05 = 0 [Input Phase Loss Protection Sel = Disabled] (if balance unsatisfactory).




Cause: Main circuit capacitors unserviceable.



Remedy:

  • Examine capacitor maintenance time (U4-05). If >90%, replace control board or drive.

  • If input power is correct but fault stays, replace control board or drive.


PSE
JOHB-SMP3 Protocol Set Error

Cause: DIP switches on JOHB-SMP3 card are at factory default or invalid.



Remedy:

  • Remove power, wait for charge light to go out, then set DIP switches to desired protocol.


SC
Short Circuit/IGBT Failure

Cause: Overheating damaged motor/insulation, motor main circuit cable grounding, or output short circuit.



Remedy:

  • Measure motor insulation resistance; replace motor if unserviceable.

  • Examine motor main circuit cable for damage/repair short circuits.

  • Check for short circuits in terminals +1, U/T1, V/T2, W/T3.

  • If short circuit exists, contact Yaskawa or sales representative.

  • When A1-02=5 (OLV/PM), set L8-27 correctly.


SCF
Safety Circuit Fault

Cause: The safety circuit is broken.



Remedy:

  • Make sure you ground the drive correctly and re-energize.

  • If fault stays, replace control board or drive.


SEr
Speed Search Retries Exceeded

Cause: Speed search-related parameters incorrect OR motor coasting in opposite direction.



Remedy:

  • Decrease b3-10 [Speed Estimation Detection Gain].

  • Increase b3-17 and b3-18 (Retry Current/Time).

  • Do Auto-Tuning again.

  • Set b3-14 = 1 [Bi-directional Speed Search = Enabled].


SPCNR
Single Phase Converter Not Ready

Cause: Digital input for Single Phase Converter deactivated (faulted or not ready).



Remedy:

  • Examine wiring between drive and converter.

  • Examine error code on converter.


STPo
Motor Step-Out Detected

Cause: Incorrect motor code, load too large/inertia too large, or acceleration/deceleration times too short.



Remedy:

  • Set E5-01 correctly.

  • Increase n8-55 [Motor to Load Inertia Ratio].

  • Increase n8-51 [Pull-in Current] (or adjust n8-79 if during decel).

  • Increase C1-01 to C1-04 times or C2-01 S-Curve.

  • Replace drive/motor with larger capacity.


TiM
Keypad Time Not Set

Cause: Battery is in keypad, but date and time are not set.



Remedy:

  • Use the keypad to set the date and time.


UL3
Undertorque Detection 1

Cause: Fault on machine (e.g., broken belt) or incorrect parameters.



Remedy:

  • Examine machine and remove cause.

  • Adjust L6-02 and L6-03 settings.


UL4
Undertorque Detection 2

Cause: Fault on machine (e.g., broken belt) or incorrect parameters.



Remedy:

  • Examine machine and remove cause.

  • Adjust L6-05 and L6-06 settings.


UL6
Underload or Belt Break Detected

Cause: Output current decreased less than motor underload curve (L6-14) for longer than L6-03.



Remedy:

  • Adjust L6-14 setting to set output current to stay above underload curve during normal operation.


Uv1
DC Bus Undervoltage

Cause: Phase loss, loose wiring, unstable input power, or magnetic contactor issue.



Remedy:

  • Correct wiring errors and tighten terminals.

  • Examine input power stability and magnetic contactor on main circuit side.




Cause: Loss of power or Capacitors unserviceable.



Remedy:

  • Use better power supply.

  • Examine U4-05 [Capacitor Maintenance]; replace board/drive if >90%.




Cause: Soft-charge bypass relay damaged.



Remedy:

  • Check U4-06; replace board or drive if >90%.


Uv2
Control Power Undervoltage

Cause: L2-02 [Power Loss Ride Through] increased but momentary power loss unit not connected OR hardware problem.



Remedy:

  • Connect the momentary power loss recovery unit to the drive.

  • Re-energize the drive.

  • If fault stays, replace control board or drive.


Uv3
Soft Charge Answerback Fault

Cause: Relay/contactor on soft-charge bypass is damaged OR air inside drive is too hot.



Remedy:

  • Re-energize the drive.

  • Check monitor U4-06; if >90%, replace board/drive.

  • Check the ambient temperature of the drive.


VLTS
Thermostat Fault

Cause: Digital input set for Thermostat Fault (H1-xx = 88) is active.



Remedy:

  • Examine the wiring or wait for the motor to cool.


AEr
Station Address Setting Error

Cause:

The node address for the communication option is not in the permitted setting range.



Remedy:

For CANopen communication, set F6-35 [CANopen Node ID Selection] correctly.
AUXFB
PI Aux Feedback Level Loss

Cause:

The analog input from the terminal set to H3-xx = 27 [MFAI Function Selection = PI Auxiliary Control Feedback Level] is more than 21 mA or less than 3 mA for longer than 1 s.



Remedy:

Repair transducer or wiring.
bAT
Keypad Battery Low Voltage

Cause:

The keypad battery voltage is low.



Remedy:

Replace the keypad battery.
bb
Baseblock

Cause:

An external baseblock command was entered through one of the MFDI terminals Sx, and the drive output stopped as shown by an external baseblock command.



Remedy:

Examine the external sequence and timing of the baseblock command input.
bCE
Bluetooth Communication Error

Cause:


  • The smartphone or tablet with DriveWizard Mobile or DriveWizard is too far from the keypad.

  • Radio waves from a different device are causing interference.




Remedy:

  • Move to 10 m (32.8 ft) or less from the keypad.

  • Make sure that no device around the keypad uses the same radio bandwidth (2400 MHz to 2480 MHz).


BuDif
Main Fdbk Lost, Using Diff Fdbk

Cause:

The drive detected a wire-break on the analog input terminal set for PID Feedback (or Main PID Feedback Transducer is broken).



Remedy:

  • Examine the connection of the Main PID Feedback Transducer.

  • Replace Main PID Feedback Transducer.


Bu-Fb
Main Fdbk Lost Using Backup Fdbk

Cause:

The drive detected wire-break on the analog input terminal set to H3-xx = B [PID Feedback] (or Transducer is broken).



Remedy:

  • Examine the connection of the Main PID Feedback Transducer.

  • Replace Main PID Feedback Transducer.


BuFbl
Backup Fdbk Lost Chk/Repl Xducer

Cause:

The drive detected wire-break on the analog input terminal set for PID Feedback Backup [H3-xx = 24].



Remedy:

  • Examine the connection of the Differential PID Feedback transducer.

  • Replace Backup PID Feedback Transducer.


bUS
Option Communication Error

Cause:


  • Communication cable wiring is incorrect or disconnected.

  • Short-circuit in communications cable.

  • Electrical interference.

  • Option card is incorrectly installed or damaged.




Remedy:

  • Correct wiring errors and repair short circuits.

  • Examine control/main circuit lines and ground wiring to decrease interference.

  • Use a Surge Protective Device on magnetic contactors if necessary.

  • Use shielded lines and separate communication wiring from drive power lines.

  • Correctly install or replace the option card.


bUSy
Busy

Cause:


  • You set the drive to use MEMOBUS/Modbus communications to change parameters, but you used the keypad.

  • You tried to change a parameter while the drive was changing setting.




Remedy:

  • Use MEMOBUS/Modbus communications to enter the command, then use the keypad.

  • Wait until the process is complete.


CALL
Serial Comm Transmission Error

Cause:


  • Communications cable wiring is incorrect, disconnected, or shorted.

  • Programming error on the controller side.

  • Damage to communications circuitry.

  • Termination resistor setting incorrect.




Remedy:

  • Correct wiring errors and replace defective cables.

  • Examine communications at start-up and correct programming errors.

  • Do a self-diagnostics check; replace control board if needed.

  • On the last drive in network, set DIP switch S2 to ON.


CE
Modbus Communication Error

Cause:


  • Communications cable wiring is incorrect, shorted, or disconnected.

  • Electrical interference.

  • Communication protocol is not compatible.

  • H5-09 [CE Detection Time] is too small.

  • Controller software/hardware issue.




Remedy:

  • Correct wiring errors and use shielded lines.

  • Examine controller settings and correct communication conditions (H5-xx).

  • Increase the value set in H5-09.

  • Examine the controller and remove the cause of the problem.


CE
Run at H5-34 (CE Go-To-Freq)

Cause:

(Same as standard CE Error)

Wiring incorrect, interference, protocol incompatibility, or timeout.



Remedy:

  • Repair short circuits and connect cables.

  • Examine control circuit lines and decrease electrical interference.

  • Check H5-xx settings and increase H5-09.

  • Examine the controller.


CrST
Cannot Reset

Cause:

The drive received a fault reset command when a Run command was active.



Remedy:

Turn off the Run command then de-energize and re-energize the drive.
CyPo
Cycle Power to Accept Changes

Cause:

Although F6-15 = 1 [Reload Now], the drive does not update the communication option parameters.



Remedy:

Re-energize the drive to update the communication option parameters.
dEv
Speed Deviation

Cause:


  • The load is too heavy.

  • Acceleration and deceleration times are set too short.

  • dEv detection level settings (F1-10, F1-11) are incorrect.

  • The load is locked up or holding brake is stopping motor.




Remedy:

  • Decrease the load.

  • Increase values in C1-01 to C1-04.

  • Adjust F1-10 and F1-11.

  • Examine machine and release holding brake.


DIFF
Differential Feedback Exceeded

Cause:

The difference between the PID Feedback and Differential Level Source [H3-xx = 2D] is more than the level set in Y4-18.



Remedy:

  • Replace the feedback transducer or transducers.

  • Set Y4-18 and Y4-19 correctly.


dnE
Drive Disabled

Cause:

A terminal set for H1-xx = 6A [MFDI Function Selection = Drive Enable] deactivated.



Remedy:

Examine the operation sequence.
DS
De-Scale/De-Rag Active

Cause:

The terminal is set to H2-xx = C5 or 1C5 and the set length of run time elapsed.



Remedy:

  • If you do not want to De-Scale, set Y8-01 = 0.

  • Adjust the Y8-08 [Run Time before De-Scale] setting.


EF
FWD/REV Run Command Input Error

Cause:

The drive received a forward command and a reverse command at the same time for longer than 0.5 s.



Remedy:

Examine the forward and reverse command sequence and correct the problem.
EF0
Option Card External Fault

Cause:

The communication option card received an external fault from the controller, or programming error occurred.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Clear the external fault input from the controller.

  • Examine the operation of the controller program.


EF1
External Fault (Terminal S1)

Cause:

MFDI terminal S1 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S1.

  • Correctly set the MFDI parameters.


EF2
External Fault (Terminal S2)

Cause:

MFDI terminal S2 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S2.

  • Correctly set the MFDI parameters.


EF3
External Fault (Terminal S3)

Cause:

MFDI terminal S3 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S3.

  • Correctly set the MFDI parameters.


EF4
External Fault (Terminal S4)

Cause:

MFDI terminal S4 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S4.

  • Correctly set the MFDI parameters.


EF5
External Fault (Terminal S5)

Cause:

MFDI terminal S5 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S5.

  • Correctly set the MFDI parameters.


EF6
External Fault (Terminal S6)

Cause:

MFDI terminal S6 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S6.

  • Correctly set the MFDI parameters.


EF7
External Fault (Terminal S7)

Cause:

MFDI terminal S7 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S7.

  • Correctly set the MFDI parameters.


EF8
External Fault (Terminal S8)

Cause:

MFDI terminal S8 caused an external fault through an external device, or wiring is incorrect.



Remedy:

  • Find the device that caused the external fault and remove the cause.

  • Correctly connect the signal line to MFDI terminal S8.

  • Correctly set the MFDI parameters.


EOF

Emergency Override FWD

Cause: The digital input terminal set to H1-xx = AF [Emergency Override FWD] activated.


Remedy:


When the emergency condition is gone, deactivate the digital input set to Emergency Override FWD.
EOR

Emergency Override REV

Cause: The digital input terminal set to H1-xx = B0 [Emergency Override REV] activated.


Remedy:


When the emergency condition is gone, deactivate the digital input set to Emergency Override REV.
EP24v

External Power 24V Supply

Cause: The voltage of the main circuit power supply decreased, and the 24 V power supply is supplying power to the drive.


Remedy:



  • Examine the main circuit power supply.

  • Turn ON the main circuit power supply to run the drive.


FDBKL

Feedback Loss Wire Break

Cause: PID Feedback analog input is > 21 mA or < 3 mA for longer than 1s (Signal selection 4-20mA).


Remedy:


Make sure that you install the PID feedback source and it operates correctly.
FLGT

Feedback Loss, Go To Freq b5-83

Cause: PID Feedback analog input is > 21 mA or < 3 mA for longer than 1s (Signal selection 4-20mA).


Remedy:


Make sure that you install the PID feedback source and it operates correctly.
FR
Freq Ref < Minimum Speed (Y1-06)

Cause: The drive frequency reference setting is less than the value set in Y1-06 [Minimum Speed].


Remedy:


Increase the frequency reference to a value more than Y1-06.
FR
Cause: The drive frequency reference setting is less than the value set in Y4-12 [Thrust Frequency].


Remedy:


Increase the frequency reference to a value more than Y4-12.
HCA

High Current Alarm

Cause:

  • The load is too heavy.

  • The acceleration time is too short.

  • The drive is trying to operate a specialized motor or a motor larger than the drive rating.




Remedy:



  • Decrease the load for applications with repetitive starts/stops or replace with larger drive.

  • Calculate necessary torque, increase acceleration times (C1-01/03), or adjust S-Curves (C2-01 to C2-04).

  • Examine motor nameplate and ensure drive rating matches motor rating.


HIAUX

High PI Aux Feedback Level

Cause: PI Auxiliary Feedback is more than the level set in YF-12 for the time set in YF-13.


Remedy:



  • Decrease the PI Auxiliary Feedback level to less than YF-12.

  • Set YF-12 and YF-13 correctly.


HIFB

High Feedback Sensed

Cause: The feedback level is more than the level set in Y1-11 [High Feedback Level].


Remedy:



  • Decrease the feedback level to less than Y1-11 - Y1-14.

  • Set Y1-11 and Y1-12 correctly.


L24v

Loss of External Power 24 Supply

Cause: The voltage of the backup 24 V power supply has decreased.


Remedy:



  • Examine the external 24 V power supply for disconnected wires/wiring errors.

  • Examine the external 24 V power supply for problems.


LCP

Low City Pressure

Cause: Insufficient pressure is present on the inlet to the pump.


Remedy:



  • Examine the pressure switch contact and control wiring.

  • Make sure suction pressure is present.

  • Set Y4-22 and Y4-23 correctly.

  • Deactivate the digital input set to Low City Pressure.


LOAUX

Low PI Aux Feedback Level

Cause: PI Auxiliary Feedback is less than the level set in YF-09 for the time set in YF-10.


Remedy:



  • Increase the PI Auxiliary Feedback level more than YF-09.

  • Set YF-09 and YF-10 correctly.


LOFB

Low Feedback Sensed

Cause: The feedback level is less than the level set in Y1-08 for the time set in Y1-09.


Remedy:



  • Increase the feedback level to more than Y1-08 + Y1-14.

  • Set Y1-08 and Y1-09 correctly.


LoG

Com Error / Abnormal SD Card

Cause:

  • Drive connected to USB.

  • Too many log files (>1000) or no memory space.

  • Communication error between keypad and drive.

  • Keypad does not support short-term data logs.




Remedy:



  • Put a micro SD card in the keypad.

  • Set o5-01 = 0 [Log Start/Stop Selection = OFF].

  • Connect a keypad that supports short-term data logs (REV: H or later).


LOP

Loss of Prime

Cause: Pump load is less than the level set in Y1-19 for the time set in Y1-20.


Remedy:



  • Examine a dry well, air in the system, or no water. Use priming method.

  • Allow system to pump water again if there is resistance.

  • Set Y1-18 to Y1-21 correctly.


LSP

Low Suction Pressure

Cause: An external input (Low Suction Pressure) has indicated insufficient suction pressure.


Remedy:



  • Examine pressure switch and wiring.

  • Make sure suction pressure is present.

  • Increase system pressure.

  • Set Y4-22 and Y4-23 correctly.


LT-1

Cooling Fan Maintenance Time

Cause: The cooling fan is at 90% of its performance life estimate.


Remedy:



  • Replace the cooling fan.

  • Set o4-03 = 0 to reset the cooling fan operation time.


LT-2

Capacitor Maintenance Time

Cause: The capacitors for the main circuit and control circuit are at 90% of their performance life estimate.


Remedy:


Replace the control board or the drive. Contact Yaskawa or sales representative.
LT-3

SoftChargeBypassRelay MainteTime

Cause: The soft charge bypass relay is at 90% of its performance life estimate.


Remedy:


Replace the control board or the drive.
LT-4

IGBT Maintenance Time (50%)

Cause: The IGBT is at 50% of its performance life estimate.


Remedy:


Check the load, carrier frequency, and output frequency.
LWT

Low Water In Tank

Cause: An external input has indicated that the water level in the tank is too low.


Remedy:



  • Examine pressure switch and wiring.

  • Make sure suction pressure is present.

  • Increase the water level.

  • Set Y4-22 and Y4-23 correctly.


NMS

Setpoint Not Met

Cause: The feedback deviates from the setpoint at a level more than Y1-15 for the time set in Y1-16.


Remedy:



  • Examine for a blocked impeller, over cycling, or broken pipe.

  • Set Y1-15 and Y1-16 correctly.


OD

Output Disconnect

Cause: The output circuit between the drive and motor is open (current < 5% of FLA).


Remedy:



  • Close the disconnected output circuit between the drive and the motor.

  • If you do not use a motor disconnect, set Y4-42 = 0 [Disabled].


oH

Heatsink Overheat

Cause:

  • High ambient temperature.

  • Not sufficient airflow around the drive / Dust clogging fan.

  • Internal cooling fan stopped.




Remedy:



  • Measure ambient temperature, increase airflow, install cooling device.

  • Check installation space and circulation.

  • Clean dust/debris.

  • Replace cooling fan and reset o4-03.


oH2

External Overheat (H1-XX=B)

Cause: An external device sent an oH2 alarm.


Remedy:



  • Find the external device that output the overheat alarm.

  • Remove the cause of the problem.

  • Clear the Overheat Alarm (oH2) by MFDI terminal.


oH3

Motor Overheat (PTC Input)

Cause:

  • Defective thermistor wiring.

  • Machine locked/Fault on machine.

  • Motor overheated (Load, Accel time, E2-01 setting, V/f pattern).




Remedy:



  • Correct wiring errors.

  • Examine machine and remove fault.

  • Decrease load, Increase C1-01 to C1-04, Check E2-01.

  • Check cooling system. Adjust V/f pattern (E1-04 to E1-10).


oL3

Overtorque 1

Cause:

  • A fault occurred on the machine (e.g., locked).

  • Parameters are incorrect for the load.




Remedy:



  • Examine the machine and remove the cause of the fault.

  • Adjust L6-02 and L6-03 settings.


oL4

Overtorque 2

Cause:

  • A fault occurred on the machine (e.g., locked).

  • Parameters are incorrect for the load.




Remedy:



  • Examine the machine and remove the cause of the fault.

  • Adjust L6-05 and L6-06 settings.


oS

Overspeed

Cause: There is overshoot.


Remedy:


Decrease C5-01 [ASR Proportional Gain 1] and increase C5-02 [ASR Integral Time 1].
ov

DC Bus Overvoltage

Cause:

  • Drive output cable/motor shorted to ground.

  • Power supply voltage too high.

  • Electrical interference (noise).




Remedy:



  • Examine motor main circuit cable, terminals, and motor box for ground faults.

  • Decrease power supply voltage to align with drive rated voltage.

  • Examine control/main circuit lines, grounding, and install Surge Protective Device if necessary.


ovEr

Too Many Parameters Changed

Cause: You tried to change more than 150 parameters.



Remedy:

  • Make sure that parameters that do not have an effect on drive operation are at their default settings.



Note:

• You can change 150 parameters maximum.

• If you change parameters that have dependencies, the drive can detect ovEr when the number of changed parameters is fewer than 150.

PASS

Modbus Communication Test

Cause: The MEMOBUS/Modbus communications test is complete.



Remedy:

  • The PASS display will turn off after communications test mode is cleared.


PF

Input Phase Loss

Cause:

  • There is a phase loss in the drive input power.

  • Loose wiring in the input power terminals.

  • The drive input power voltage is changing too much.

  • Unsatisfactory balance between voltage phases.

  • The main circuit capacitors are unserviceable.




Remedy:

  • Correct errors with the wiring for main circuit drive input power.

  • Tighten the terminal screws to the correct tightening torque.

  • Examine the input power for problems and make the drive input power stable.

  • If the input power supply is good, examine the magnetic contactor on the main circuit side for problems.

  • Examine the capacitor maintenance time in monitor U4-05 [CapacitorMaintenance]. If U4-05 is more than 90%, replace the capacitor.

  • Re-energize the drive. If the alarm stays, replace the circuit board or the drive.



Note: The drive detects this error if the DC bus voltage changes irregularly without regeneration. Use L8-05 to enable/disable detection.

R-DNE

Remote Drive Disable

Cause:

  • The digital input set to H1-xx = BD [Remote Drive Disable] activated.

  • The digital input set to H1-xx = 1BD [!Remote Drive Disable] deactivated.




Remedy:

  • Examine the statuses of the digital input terminals set to H1-xx = BD or 1BD.


rUn

Motor Switch during Run

Cause: The drive received a Motor 2 Selection [H1-xx = 16] during run.



Remedy:

  • Make sure that the drive receives the Motor 2 Selection while the drive is stopped.


SE

Modbus Test Mode Error

Cause: MEMOBUS/Modbus communications self-diagnostics [H1-xx = 67] was done while the drive was running.



Remedy:

  • Stop the drive and do MEMOBUS/Modbus communications self-diagnostics.


SPCNR

Single Phase Converter Not Ready

Cause: When YC-14 = 1, the digital input set to H1-xx = BE [Single Phase Converter Ready NC] deactivated to show that the attached converter is faulted or not ready.



Remedy:

  • Examine the wiring between the drive and converter.

  • Examine the error code on converter.


STo

Safe Torque OFF

Cause:

  • Safe Disable inputs H1-HC and H2-HC are open.

  • There is internal damage to the two Safe Disable channels.




Remedy:

  • Make sure that the Safe Disable signal is input from an external source to terminal H1-HC and H2-HC.

  • When the Safe Disable function is not in use, use a jumper to connect terminals H1-HC and H2-HC.

  • Replace the board or the drive (Contact Yaskawa).


SToF

Safe Torque OFF Hardware

Cause:

  • One of the two terminals H1-HC or H2-HC received the Safe Disable input signal.

  • The Safe Disable input signal is wired incorrectly.

  • There is internal damage to one Safe Disable channel.




Remedy:

  • Make sure that the Safe Disable signal is input from an external source to terminals H1-HC or H2-HC.

  • When the Safe Disable function is not in use, use a jumper to connect terminals H1-HC and H2-HC.

  • Replace the board or the drive.


TiM

Keypad Time Not Set

Cause: There is a battery in the keypad, but you have not set the date and time.



Remedy:

  • Use the keypad to set the date and time.



Note: Parameter o4-24 [bAT Detection selection] enables and disables TiM detection.

TrPC

IGBT Maintenance Time (90%)

Cause: The IGBT is at 90% of its performance life estimate.



Remedy:

  • Replace the IGBT or the drive. For more information, contact Yaskawa or your nearest sales representative.


UL3

Undertorque Detection 1

Cause:

  • A fault occurred on the machine. Example: There is a broken pulley belt.

  • The parameters are incorrect for the load.




Remedy:

  • Examine the machine and remove the cause of the fault.

  • Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque Detection Time 1] settings.


UL4

Undertorque Detection 2

Cause:

  • A fault occurred on the machine. Example: There is a broken pulley belt.

  • The parameters are incorrect for the load.




Remedy:

  • Examine the machine and remove the cause of the fault.

  • Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque Detection Time 2] settings.


UL6

Underload or Belt Break Detected

Cause:

  • The output current decreased less than the motor underload curve set in L6-14 for longer than the time set in L6-03.

  • The belt has broken disconnecting the motor from the load.




Remedy:

  • Examine parameters L6-13 [Motor Underload Curve Select] and L6-14.


Uv

Undervoltage

Cause:

  • The drive input power voltage is changing too much.

  • There is a phase loss in the drive input power.

  • There is loose wiring in the drive input power terminals.

  • There was a loss of power.

  • The main circuit capacitors have become unserviceable.

  • The drive input power transformer is too small and voltage drops when the power is switched on.

  • Air inside the drive is too hot.

  • The Charge LED is broken.




Remedy:

  • Examine the input power for problems and make stable.

  • Correct errors with the wiring for main circuit drive input power.

  • Tighten the terminal screws to the correct tightening torque.

  • Use a better power supply.

  • Examine capacitor maintenance time (U4-05). If > 90%, replace control board/drive.

  • Check for alarm when MCCB/ELCB/Magnetic Contactor is ON.

  • Check the capacity of the drive power supply transformer.

  • Check the ambient temperature of the drive.

  • Replace the control board or the entire drive.



Note: The drive detects this error if one of these conditions is correct when the Run command has not been input (while the drive is stopped):

- The DC bus voltage < L2-05

- The Contactor that prevents inrush current in the drive was opened.

- There is low voltage in the control drive input power.


oPE01


Drive Capacity Setting Error

Cause:

The value set in o2-04 [Drive Model (KVA) Selection] does not agree with the drive model.



Remedy:

  • Set o2-04 to the correct value.



oPE02


Parameter Range Setting Error

Cause:

Parameter settings are not in the applicable setting range, or relationships between parameters are incorrect (e.g., Motor Rated Current E2-01 ≤ No-Load Current E2-03).



Remedy:

  • Push the enter key to show U1-18 [oPE Fault Parameter] to find the specific parameter causing the error.

  • Make sure E2-01 > E2-03.

  • Check Logical conflicts between L8-12 and L8-35 (Installation method vs Temperature).

  • Ensure PI2 Control limits are correct (S3-09 > S3-10 and S3-13 < S3-15).

  • Correct parameter settings as indicated by U1-18.



oPE03


Multi-Function Input Setting Err

Cause:

The settings for these parameters do not agree or overlap:

  • F3-10 to F3-25 [Terminal D1 to DF Function Selection]

  • H1-01 to H1-08 [Terminals S1 to S8 Function Selection]

  • H7-01 to H7-04 [Virtual Multi-Function Inputs]

  • MFDI pairs set incorrectly (e.g., Up/Down command set simultaneously).





Remedy:

  • Set the parameters correctly to prevent MFDI function overlap.

  • If using Up/Down or Run/FWD wire sequences, ensure pairs are set correctly.

  • Remove function settings that are not in use.



oPE05


Run Cmd/Freq Ref Source Sel Err

Cause:

The setting to assign the Run command or frequency reference to an option card or the pulse train input is incorrect.

  • Option PCB selected (b1-01=3 or b1-02=3) but no card connected.

  • Pulse Train Input selected (b1-01=4) but H6-01 is not 0.

  • Digital Input Data Length conflicts (F3-01 vs F3-03).





Remedy:

  • Connect an option card to the drive if Option PCB is selected.

  • Set H6-01 = 0 if using Pulse Train Input.

  • Set F3-03 = 2 [16-bit] if required.

  • Correct the parameter settings.



oPE07


Analog Input Selection Error

Cause:

The settings for H3-02, H3-06, H3-10 [MFAI Function Selection] and H7-30 [Virtual Analog Input Selection] overlap or conflict with PID settings.



Remedy:

  • Set H3-02, H3-06, H3-10, and H7-30 correctly to prevent overlap.

  • Set values to F or 1F [Not Used] for unused terminals.

  • If using Differential Level Source (H3-xx = 2D), ensure Y4-41 is set correctly for backup PID feedback.



oPE08


Parameter Selection Error

Cause:

You set a function that is not compatible with the control method set in A1-02.

  • V/f Control conflicts with Dynamic Noise Control (S1-01) or Output Disconnect (Y4-42).

  • PM Motor settings (E5-xx) incorrect for OLV/PM (A1-02=5).

  • Drive capacity/Motor mismatch for specific control modes.





Remedy:

  • Push the enter key to show U1-18 [oPE Fault Parameter].

  • Set S1-01 = 0 or Y4-42 = 0 if in V/f mode.

  • Set E5-01 correctly based on the motor nameplate.

  • Set E5-09 and E5-24 to 0 if required by the control mode.



oPE09


PID Control Selection Fault

Cause:

PID Control is enabled (b5-01=1) but conflicts with other parameters:

  • Frequency Reference Lower Limits (d2-02).

  • Sleep Level Type (Y2-01).

  • Thrust Frequency (Y4-12) or Minimum Speed (Y1-06).





Remedy:

  • Correct the parameter settings causing the conflict.

  • Verify b5-01 setting.



oPE10


V/f Data Setting Error

Cause:

The parameters that set the V/f pattern do not satisfy the required frequency conditions (Min ≤ Mid Point A ≤ Base ≤ Mid Point B ≤ Max).



Remedy:

  • Set parameters (E1-09 through E1-04 for Motor 1) correctly to satisfy the logical frequency order.



oPE11


Carrier Frequency Setting Error

Cause:

These parameters are set at the same time incorrectly:

  • C6-05 > 6 [Carrier Freq Proportional Gain].

  • C6-04 > C6-03 [Carrier Frequency Lower Limit > Upper Limit].





Remedy:

  • Set C6-02 to C6-05 correctly.



oPE16


Energy Saving Constants Error

Cause:

The Energy Saving parameters are not set in the applicable setting range, or Energy Saving Control overlaps with Dynamic Noise Control (S1-01=1).



Remedy:

  • Make sure E5-xx is set correctly as specified by motor nameplate data.

  • Disable Energy Saving Control or Dynamic Noise Control.



oPE33


Digital Output Selection Error

Cause:

Inverse output functions (H2-01 to H2-03 = 1xx) are selected while secondary functions (H2-60, H2-63, H2-66) are used.



Remedy:

  • Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.

  • Note: It is not possible to use inverse output when using output functions for logic operations.


End1
Excessive Rated Voltage Setting

Cause: The torque reference was more than 20% during Auto-Tuning or the no-load current that was measured after Auto-Tuning is more than 80%.



Remedy:

  • Make sure that the input motor nameplate data is correct.

  • Do Auto-Tuning again and correctly set the motor nameplate data.

  • If you can uncouple the motor and load, remove the motor from the machine and do Rotational Auto-Tuning again.

  • If you cannot uncouple the motor and load, use the results from Auto-Tuning.


End2
Iron Core Saturation Coefficient

Cause: The motor nameplate data entered during Auto-Tuning is incorrect.



Remedy:

  • Make sure that the input motor nameplate data is correct.

  • Do Auto-Tuning again and correctly set the motor nameplate data.


End3
Rated Current Setting Alarm

Cause: The rated current value is incorrect.



Remedy:

  • Do Auto-Tuning again and set the correct rated current shown on the motor nameplate.


End4
Adjusted Slip Calculation Error

Cause:

- The Auto-Tuning results were not in the applicable parameter setting range.

- The motor rated slip that was measured after Stationary Auto-Tuning was 0.2 Hz or lower.

- The secondary resistor measurement results were not in the applicable range.



Remedy:

  • Make sure the input motor nameplate data is correct.

  • Do Rotational Auto-Tuning again and correctly set the motor nameplate data.

  • If you cannot uncouple the motor and load, do Stationary Auto-Tuning 2.


End5
Resistance Tuning Error

Cause: The Auto-Tuning results of the Line-to-Line Resistance were not in the applicable range.



Remedy:

  • Make sure that the input motor nameplate data is correct.

  • Examine and repair damaged motor wiring.


End6
Leakage Inductance Alarm

Cause:

- The Auto-Tuning results were not in the applicable parameter setting range.

- A1-02 [Control Method Selection] setting is not applicable.



Remedy:

  • Make sure that the input motor nameplate data is correct, and do Auto-Tuning again.

  • Examine the value set in A1-02.


End7
No-Load Current Alarm

Cause:

- The Auto-Tuning results of the motor no-load current value were not in the applicable range.

- Auto-Tuning results were less than 5% of the motor rated current.



Remedy:

  • Examine and repair damaged motor wiring.

  • Make sure that the input motor nameplate data is correct, and do Auto-Tuning again.


End8
HFI Alarm

Cause:

- Inductance saliency ratio (E5-07/E5-06) is too small.

- The drive cannot find the n8-36 [HFI Frequency Level for L Tuning] value.



Remedy:

  • Set the correct value on the motor nameplate to E5-xx [PM Motor Settings] or do rotational/stationary Auto-Tuning.

  • When it is necessary to set n8-35 = 1, make sure that there is no unusual noise in the low speed range (10% or less) and that the motor does not rotate in reverse at start.


Note: If the drive detects End8, it will automatically set n8-35 = 0 [Pull-in]. Do not change the settings unless necessary.

End9
Initial Pole Detection Alarm

Cause: The drive cannot calculate the correct value for n8-84 [Polarity Detection Current] during High Frequency Injection Tuning.



Remedy:

  • When n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection], make sure that the motor does not rotate in reverse at start.


Note: If the drive detects End9, it will automatically set n8-35 = 0 [Pull-in]. Do not change the settings unless necessary.

Er-01
Motor Data Error

Cause:

- The motor nameplate data entered during Auto-Tuning is incorrect.

- The combination of the motor rated power and motor rated current do not match.

- The combination of the motor rated current that was entered and E2-03 [Motor No-Load Current] do not match.

- The combination of the setting values of Motor Base Frequency and Motor Base Speed do not match.



Remedy:

  • Make sure that the motor nameplate data is correct.

  • Do Auto-Tuning again and correctly set the motor nameplate data.

  • Examine the combination of drive capacity and motor output.

  • Examine the motor rated current and the no-load current.

  • Set E2-03 correctly.


Er-02
Drive in an Alarm State

Cause:

- The motor nameplate data entered during Auto-Tuning is incorrect.

- You did Auto-Tuning while the drive had a minor fault or alarm.

- There is a defective motor cable or cable connection.

- The load is too large.

- The drive detected a minor fault during Auto-Tuning.



Remedy:

  • Make sure that the motor nameplate data entered in Auto-Tuning is correct.

  • Clear the minor fault or alarm and do Auto-Tuning again.

  • Examine and repair motor wiring.

  • Decrease the load.

  • Examine the machine area to see if, for example, the motor shaft is locked.

  • Examine the minor fault code and remove the cause of the problem.


Er-03
STOP Button was Pressed

Cause: During Auto-Tuning, STOP was pushed.



Remedy:

  • Auto-Tuning did not complete correctly. Do Auto-Tuning again.


Er-04
Line-to-Line Resistance Error

Cause:

- The Auto-Tuning results were not in the applicable parameter setting range.

- Auto-Tuning did not complete in a pre-set length of time.

- There is a defective motor cable or cable connection.

- The motor nameplate data entered during Auto-Tuning is incorrect.



Remedy:

  • Examine and repair motor wiring.

  • Disconnect the machine from the motor and do Rotational Auto-Tuning again.

  • Make sure that the input motor nameplate data is correct.

  • Do Auto-Tuning again and correctly set the motor nameplate data.


Er-05
No-Load Current Error

Cause:

- The Auto-Tuning results were not in the applicable parameter setting range.

- Auto-Tuning did not complete in a pre-set length of time.

- The motor nameplate data entered during Auto-Tuning is incorrect.

- Rotational Auto-Tuning was done with a load that was more than 30% of the rating connected to the motor.



Remedy:

  • Examine and repair motor wiring.

  • Disconnect the machine from the motor and do Rotational Auto-Tuning again.

  • Make sure that the input motor nameplate data is correct.

  • If you cannot uncouple the motor and load, make sure that the load is less than 30% of the motor rating. If a mechanical brake is installed, release the brake during Rotational Auto-Tuning.


Er-08
Rated Slip Error

Cause:

- The motor nameplate data entered during Auto-Tuning is incorrect.

- Auto-Tuning did not complete in a pre-set length of time.

- The Auto-Tuning results were not in the applicable parameter setting range.

- Rotational Auto-Tuning was done with a load that was more than 30% of the rating connected to the motor.



Remedy:

  • Make sure that the input motor nameplate data is correct.

  • Examine and repair the motor wiring.

  • If the motor and machine are connected during Rotational Auto-Tuning, decouple the motor from the machinery.

  • Disconnect the machine from the motor and do Rotational Auto-Tuning again.

  • If you cannot uncouple the motor and load, make sure that the load is less than 30% of the motor rating and release any mechanical brake.


Er-09
Acceleration Error

Cause:

- The motor did not accelerate for the specified acceleration time.

- Rotational Auto-Tuning was done with a load that was more than 30% of the rating connected to the motor.



Remedy:

  • Increase the value set in C1-01 [Acceleration Time 1].

  • Disconnect the machine from the motor and do Rotational Auto-Tuning again.

  • If you cannot uncouple the motor and load, make sure that the load is less than 30% of the motor rating and release any mechanical brake.


Er-12
Current Detection Error

Cause:

- There is a phase loss in the drive input power (U/T1, V/T2, W/T3).

- The current exceeded the current rating of the drive.

- The output current is too low.

- You tried Auto-Tuning without a motor connected to the drive.

- There was a current detection signal error.



Remedy:

  • Examine and repair motor wiring.

  • Check the motor wiring for any short circuits between the wires.

  • Check and turn ON any magnetic contactors used between motors.

  • Replace the control board or the drive.

  • Connect the motor and do Auto-Tuning.


Er-13
Leakage Inductance Error

Cause:

- The motor rated current value is incorrect.

- The drive could not complete tuning for leakage inductance in fewer than 300 s.



Remedy:

  • Correctly set the rated current indicated on the motor nameplate and do Auto-Tuning again.

  • Examine and repair motor wiring.


Er-18
Back EMF Error

Cause: The result of the induced voltage tuning was not in the applicable range.



Remedy:

  • Make sure that the input motor nameplate data is correct.

  • Do Auto-Tuning again and correctly set the motor nameplate data.


Er-19
PM Inductance Error

Cause: The Auto-Tuning results of the PM motor inductance were not in the applicable range.



Remedy:

  • Make sure that the input motor nameplate data is correct.

  • Do Auto-Tuning again and correctly set the motor nameplate data.


Er-20
Stator Resistance Error

Cause: The Auto-Tuning results of the PM Motor Stator Resistance were not in the applicable range.



Remedy:

  • Make sure that the input motor nameplate data is correct.

  • Do Auto-Tuning again and correctly set the motor nameplate data.


Er-25
HighFreq Inject Param Tuning Err

Cause: The motor data is incorrect.



Remedy:

  • Do Stationary Auto-Tuning again.


Note: If the drive detects Er-25 after you do Stationary Auto-Tuning, it is possible that the motor cannot use high frequency injection. For more information, contact Yaskawa or your nearest sales representative.

CPEr

Control Mode Mismatch

Cause: The keypad setting and drive setting for A1-02 [Control Method Selection] do not agree.



Remedy:



  • Set A1-02 on the drive to the same value that is on the keypad.

  • Restore the parameters.


CPyE

Error Writing Data

Cause: Parameter restore did not end correctly.



Remedy:



  • Restore the parameters.


CSEr

Control Mode Mismatch

Cause: The keypad is broken.



Remedy:



  • Replace the keypad.


dFPS

Drive Model Mismatch

Cause: You tried to restore parameters to a different drive model than the one that you backed up.



Remedy:



  • Examine the drive model that you used to back up the parameters.

  • Restore the parameters.


iFEr

Keypad Communication Error

Cause: There was a communications error between the keypad and the drive.



Remedy:



  • Examine the connector or cable connection.


ndAT

Error Received Data

Cause: The parameter settings for model and specifications (power supply voltage and capacity) are different between the keypad and the drive.



Remedy:



  • Make sure that drive model and the value set in o2-04 [Drive Model (KVA) Selection] agree.

  • Restore the parameters.








Cause: The parameters are not stored in the keypad.



Remedy:



  • Connect a keypad that has the correct parameters.

  • Restore the parameters.


rdEr

Error Reading Data

Cause: You tried to back up the data when o3-02 = 0 [Copy Allowed Selection = Disabled].



Remedy:



  • Set o3-02 = 1 [Enabled] and back up again.


vAEr

Voltage Class, Capacity Mismatch

Cause: The power supply specifications or drive capacity parameter settings are different between the keypad and the drive.



Remedy:



  • Make sure that drive model and the value set in o2-04 [Drive Model (KVA) Selection] agree.

  • Restore the parameters.


vFyE

Parameters do not Match

Cause: The parameters that are backed up in the keypad and the parameters in the drive are not the same.



Remedy:



  • Restore or backup the parameter again.

  • Verify the parameters.


How to Clear & Reset Yaskawa FP605 Drive Faults

  1. Keypad Reset: Ensure any active Run or Start command is deactivated, then press the RESET button on the high-visibility LCD keypad.
  2. Digital Input Reset (Terminal S1–S8): Pulse the multi-function digital input terminal assigned to Fault Reset (configured via parameter H1-xx = 14).
  3. DriveWizard PC Tool / Mobile App: Connect your PC or mobile device via the built-in USB-OTG port (accessible even without main input power applied) or via Bluetooth with DriveWizard Mobile, and click “Fault Reset”.
  4. Fieldbus / Network Command: Write Bit 3 (Fault Reset) of Control Register 0001H to `1` using embedded RS-485 (Modbus RTU / BACnet MS/TP) or optional industrial communication card.
  5. Power Cycle: Disconnect input line power, wait until the high-visibility status ring and internal CHARGE LED turn off completely (approx. 5 minutes for bus capacitor discharge), then reconnect power.
⚠️ High-Voltage Electrical Safety Warning: Always verify that the internal CHARGE indicator lamp is completely extinguished, and test with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+1] (or [+]) and [-] before removing covers or inspecting motor output terminals U/T1, V/T2, and W/T3 on the Yaskawa FP605 drive.