2310 Overcurrent fault in ABB ACH180 drive

Home/ABB/ABB ACH180 drive/2310 Overcurrent fault in ABB ACH180 drive

Fault 2310 Overcurrent in the ABB ACH180 drive indicates that output current has exceeded the inverter internal hardware trip limit. The drive immediately commands an instantaneous gate pulse shutdown to protect the output IGBT modules from catastrophic thermal destruction.

The ACH180 continuously samples phase current waveforms through internal transducers. When motor stator current spikes beyond the design trip threshold—typically over 200% to 300% of nominal rating—comparator circuits trigger a hardware trip within microseconds. Extreme overcurrent transients destabilize intermediate DC circuit capacitors, generate severe dv/dt spikes, and risk irreversible punch-through on IGBT gate oxide layers. To prevent hardware burnout, the ACH180 halts modulation, stops the motor by coast, and latches fault 2310.

What Causes 2310 in ABB ACH180?

  1. Sudden mechanical jam, excessive starting inertia, or locked rotor condition on the driven load.
  2. Acceleration ramp time configured too aggressively in parameter group 23 Speed reference ramp or group 28 Frequency reference chain.
  3. Phase-to-phase short circuit or low insulation resistance earth fault in the motor windings or output cable.
  4. Incorrect motor nameplate data in parameter group 99 Motor data or mismatched scaling in parameters 46.01, 46.02, or 46.03.
  5. An output contactor opening or closing while the drive is modulating, or power factor capacitors installed on terminals U2, V2, W2.

Step-by-Step Troubleshooting and Solutions

  1. Inspect the mechanical load (pumps, HVAC blowers, gearboxes) for binding, bearing seizure, or debris preventing free shaft rotation.
  2. Increase acceleration times in parameter group 23 (parameter 23.12) or group 28 (parameter 28.72) to reduce current draw during speed transitions.
  3. Verify that motor nameplate ratings entered in parameter group 99 match the motor stamp exactly, and check scaling in 46.01 Speed scaling, 46.02 Frequency scaling, and 46.03 Torque scaling.
  4. Disconnect leads from terminals U2, V2, W2 and perform a 500V/1000V megger insulation test on cables and motor to detect phase-to-ground breakdowns.
  5. Ensure no contactors cycle downstream while running, and immediately remove any power factor correction capacitors or surge absorbers on the motor line.

Preventative Maintenance to Avoid 2310 Faults

Schedule regular insulation resistance megger tests on motor windings and verify electrical terminal torques on terminals U2, V2, W2. Ensure mechanical air filters and drive heatsink passages remain unobstructed to prevent ambient thermal de-rating from compounding high current stress on output power transistors.

Frequently Asked Questions (FAQs)

What is the meaning of 2310 fault in ABB ACH180 drive?

The 2310 fault indicates that output current exceeded the internal hardware trip limit of the ABB ACH180 drive, causing an immediate inverter safety shutdown.

What are the primary causes of 2310 fault?

Primary causes include mechanical overload, short acceleration times, ground faults in motor cabling, incorrect group 99 motor data, or downstream output contactor switching.

How do I troubleshoot and correct 2310 fault?

Check the motor load, lengthen acceleration ramps in parameter group 23 or 28, verify motor data, and test cable insulation resistance with a megger.