3381 Output Phase Loss Fault in ABB ACH180 Drive

Home/ABB/ABB ACH180 drive/3381 Output Phase Loss Fault in ABB ACH180 Drive

Fault 3381 in the ABB ACH180 drive denotes an output phase loss condition where current flow through one of the motor output phases is absent or severely unbalanced. The drive trips immediately to prevent single-phasing, stator overheating, and severe mechanical vibration.

During normal inverter operation, pulse-width modulated (PWM) voltage is synthesized across output terminals T1/U, T2/V, T3/W to produce balanced three-phase motor current. Internal current transformers continuously monitor instantaneous phase currents. If a conductor opens, a local isolator opens during operation, or winding continuity breaks, current drops to zero on that leg. In scalar control mode, the drive asserts this protection once output frequency exceeds 10% of nominal motor frequency and current imbalance persists.

What Causes 3381 in ABB ACH180?

  1. Loose, broken, or disconnected motor cable conductor between drive terminals T1/U, T2/V, T3/W and the motor junction box.
  2. Open local motor safety disconnect switch or corroded knife blades between the drive output and motor.
  3. Open-circuit condition within motor stator windings or an internal burned wire inside the motor connection box.
  4. Testing with a low-power motor whose rated full-load current is less than 1/6 of the nominal drive output rating in scalar mode.
  5. Defective internal current transducer or damaged IGBT gate driver on one output phase.

Step-by-Step Troubleshooting and Solutions

  1. Inspect all power terminations at drive output terminals T1/U, T2/V, T3/W and motor terminals U1, V1, W1, retorquing to specified values.
  2. Verify that local motor disconnect switches and contactors are fully engaged and measure negligible resistance across all three poles.
  3. Disconnect motor leads from the drive and perform winding phase-to-phase resistance tests and a 1000 V DC insulation megger test to ground.
  4. If operating a fractional test motor in scalar mode (motor current under 1/6 drive rating), set parameter 31.19 Motor phase loss to No action.
  5. Run the drive in low-speed manual jog while measuring each output phase with a calibrated clamp-on meter to verify current balance.

Preventative Maintenance to Avoid 3381 Faults

Perform annual torque checks on all motor circuit terminals, inspect auxiliary contacts on local safety disconnects, and utilize continuous-flex shielded symmetrical motor cabling to prevent internal conductor fatigue from machine vibration.

Frequently Asked Questions (FAQs)

What is the meaning of 3381 fault in ABB ACH180 drive?

The 3381 fault indicates that the ACH180 drive detected a missing or disconnected output phase between the drive output terminals and the motor windings.

What are the primary causes of 3381 fault?

Common causes include open motor cables, disengaged local disconnect switches, burned stator coils, and small test motors drawing insufficient current.

How do I troubleshoot and correct 3381 fault?

Check all output wiring connections, test motor winding resistance with an ohmmeter, inspect local isolators, and adjust parameter 31.19 if testing small motors.