Fault 3385 in the ABB ACH180 drive indicates that the automated rotor autophasing identification routine has failed to determine magnetic pole alignment. The drive trips to prevent uncontrolled motor runaway, violent torque ripples, and dangerous overcurrent surges.
Synchronous reluctance and permanent magnet synchronous motors (PMSM) require microsecond-accurate stator flux positioning relative to rotor magnetic poles. During commissioning or start sequences, the ACH180 applies targeted DC test current vectors through output terminals T1/U, T2/V, T3/W to detect the precise rotor electrical angle. If the motor rotor moves due to external fan windmilling, if motor parameters in group 99 are incorrect, or if the initial motor ID run did not complete successfully, the autophasing calculations diverge and trip fault 3385.
What Causes 3385 in ABB ACH180?
- Rotor rotation or mechanical backdraft caused by air currents through fan ducting while autophasing executes.
- Incorrect motor type configured in parameter
99.03 Motor type(such as asynchronous induction selected instead of PM/SynRM). - Unsuccessful or incomplete motor identification procedure in parameter
99.13 ID run requested. - Mismatched motor nameplate ratings entered for parameters
99.06 Motor nominal currentor99.07 Motor nominal voltage. - High motor cable capacitance, open output wiring, or uneven stator winding impedance.
Step-by-Step Troubleshooting and Solutions
- Confirm that the motor shaft is completely stationary and mechanically prevented from rotating before starting the drive routine.
- Verify that parameter
99.03 Motor typecorrectly matches the connected motor technology (Permanent Magnet or SynRM). - Execute a complete motor identification run using parameter
99.13 ID run requested, choosingNormalorReducedbased on mechanical coupling. - Cross-check every entry in parameter group
99 Motor dataagainst the physical motor nameplate data stamped on the motor frame. - Measure winding resistance balance across motor terminals with a calibrated micro-ohmmeter to detect internal stator coil faults.
Preventative Maintenance to Avoid 3385 Faults
Install mechanical backdraft dampers on air handling systems to prevent windmilling during idle periods, inspect motor lead shield grounding terminations for solid 360-degree contact, and store commissioned motor parameter files using the drive assistant control panel.
Frequently Asked Questions (FAQs)
What is the meaning of 3385 fault in ABB ACH180 drive?
The 3385 fault indicates that the ACH180 drive was unable to establish the magnetic pole position of a synchronous motor during the autophasing alignment procedure.
What are the primary causes of 3385 fault?
This fault occurs when the motor rotates during testing, motor parameters in group 99 are misconfigured, or the identification run has failed to complete successfully.
How do I troubleshoot and correct 3385 fault?
Ensure the motor is completely still, verify parameter 99.03 motor type matches the connected machine, check all nameplate entries, and repeat the motor ID run.