5681 PU communication fault in ABB ACH180 drive

Home/ABB/ABB ACH180 drive/5681 PU communication fault in ABB ACH180 drive

ABB ACH180 fault 5681 signals that cyclic data transmission between the drive control unit and the power unit (PU) has failed. The drive inhibits firing pulses immediately to protect power semiconductors from operating without real-time supervisory control.

The control unit computes motor control vector calculations and velocity loops, transmitting firing angles to the power unit while receiving real-time current, DC link voltage, and status feedback. Communication across this internal interface relies on strict synchronization. If packet frames drop or parity checksum errors exceed threshold limits, the drive triggers a safety shutdown to prevent unpredictable IGBT switching.

What Causes 5681 in ABB ACH180?

  1. Physical looseness, vibration damage, or poor contact on the internal multi-pin bridge connector joining the control and power boards.
  2. Excessive high-frequency common-mode noise generated by unshielded motor cables or inadequate drive ground bonding.
  3. Auxiliary switched-mode power supply (SMPS) voltage fluctuations powering the power unit logic circuit.
  4. Severe electrical fast transients (EFT) or lightning surges on incoming supply terminals L1, L2, L3.
  5. Damaged optical or differential transceiver circuitry on the internal communication bus.

Step-by-Step Troubleshooting and Solutions

  1. Disconnect line power, observe lockout/tagout safety protocols, and allow the DC bus capacitors to discharge below 5V DC before opening the enclosure.
  2. Inspect the mechanical seating of the control unit on the power unit; ensure fastening screws and internal ribbon/pin connectors are firmly seated.
  3. Check high-frequency grounding: confirm motor cable shields are clamped with 360-degree contact to the drive grounding plate.
  4. Verify incoming AC supply stability and check for balance across line phases to eliminate low-voltage brownouts affecting internal DC-DC logic power supplies.
  5. Power cycle the drive; if fault 5681 recurs immediately without external connections landed, service or replace the drive unit.

Preventative Maintenance to Avoid 5681 Faults

Ensure drive cabinets are isolated from intense machinery vibration using anti-vibration rubber mounts, maintain tight ground bonding from panel chassis to facility earth, and routinely check internal board mounting fasteners during service intervals.

Frequently Asked Questions (FAQs)

What is the meaning of 5681 fault in ABB ACH180 drive?

Fault 5681 indicates that communication between the drive control board and the internal power unit has dropped or experienced excessive data errors.

What are the primary causes of 5681 fault?

Common causes include loose internal board interconnects, mechanical vibration, severe electromagnetic noise, or auxiliary power supply dips.

How do I troubleshoot and correct 5681 fault?

Isolate power, inspect and reseat internal board connections, verify 360-degree motor cable shielding, and cycle power to clear bus errors.