ABB ACH180 fault 6681 occurs when the drive detects a complete communication break on its embedded fieldbus (EFB) interface over EIA-485. Depending on user parameter configuration, the drive trips immediately or executes a predefined fallback speed action.
The integrated EIA-485 port receives periodic supervisory control words and speed references from building management systems (BMS) utilizing BACnet MS/TP or Modbus RTU protocols. If cyclic polling halts and the timeout period set in parameter 58.16 Communication loss time expires, the drive executes the protective action assigned in parameter 58.14 Communication loss action. Disabling IGBT pulse-width modulation ensures fans and pumps do not run uncontrolled under lost automation feedback.
What Causes 6681 in ABB ACH180?
- BMS controller, PLC, or fieldbus master unit powered down, offline, or halted.
- Broken, loose, or reversed RS-485 communication conductors landed on terminals
25, 26, 27, 28. - Missing, damaged, or improperly configured
120 Ωend-of-line bus termination resistors. - Excessive common-mode voltage or ground loops caused by ungrounded or poorly grounded shield drains.
- Communication timeout threshold in parameter
58.16set too aggressively for network traffic.
Step-by-Step Troubleshooting and Solutions
- Verify the operating status of the fieldbus master controller and confirm active network polling across the automation segment.
- Inspect fieldbus wiring on control unit EIA-485 terminals: terminal
25 (B+), terminal26 (A-), terminal27 (DGND), and terminal28 (SHIELD)for secure seating. - Check line termination: ensure the
120 Ωtermination switch is enabled only on the physical first and last nodes of the RS-485 trunk. - Measure DC differential voltage across terminals
25and26with a multimeter; active communication should exhibit an oscillating voltage between2.0V DCand4.0V DC. - Review parameter
58.14 Communication loss actionand evaluate if adjusting communication loss delay parameter58.16accommodates network latency.
Preventative Maintenance to Avoid 6681 Faults
Always utilize shielded twisted-pair cables rated specifically for RS-485 serial communications, isolate communication conduit from power lines U, V, W, and verify consistent baud rates across all network drops.
Frequently Asked Questions (FAQs)
What is the meaning of 6681 fault in ABB ACH180 drive?
Fault 6681 signifies that cyclic communication between the drive embedded EIA-485 interface and the upstream fieldbus controller has been lost past the programmed timeout.
What are the primary causes of 6681 fault?
This trip occurs due to fieldbus master outages, disconnected wiring on EIA-485 terminals 25 to 28, improper bus termination, or mismatched communication baud rates.
How do I troubleshoot and correct 6681 fault?
Check master PLC status, tighten connections on terminals 25, 26, 27, 28, verify termination resistors, and adjust response parameter 58.14.