ABB ACH180 alarm A6B1 indicates that a new security pass code was typed into parameter 96.100 but has not been confirmed in parameter 96.101. The drive triggers this warning to prevent accidental lockouts caused by unverified security credentials.
To avoid lockout scenarios where typographical errors leave a drive inaccessible, the ACH180 requires a two-step confirmation process when establishing pass codes. Entering an unconfirmed code leaves non-volatile memory in a pending verification state. The drive continues normal motor modulation and speed control, but keeps alarm A6B1 active until the technician either confirms the new password or cancels the operation.
What Causes A6B1 in ABB ACH180?
- New security pass code entered into parameter
96.100 Change user pass codewithout completing96.101 Confirm user pass code. - Typographical mismatch between the strings entered into parameters
96.100and96.101. - Exiting the keypad navigation menu or disconnecting PC tools mid-way through a security pass code update.
- Control panel communication timeout while writing new credentials to non-volatile memory.
- Interrupted security macro execution during automated commissioning routines.
Step-by-Step Troubleshooting and Solutions
- Access the parameters menu and navigate directly to parameter group
96 System. - Check parameter
96.100 Change user pass codeto review the pending pass code change. - Enter the identical numeric code into parameter
96.101 Confirm user pass codeto validate and store the new pass code in non-volatile flash. - If you wish to cancel the pass code change, navigate to parameter
96.02 Pass codeand enter an invalid value to close the lock without updating. - Verify that warning
A6B1clears automatically once the pass code is confirmed or the lock session is terminated.
Preventative Maintenance to Avoid A6B1 Faults
Record master pass codes in secure plant documentation before entering them into the drive, complete two-step confirmation entries without leaving keypad menus idle, and avoid changing security codes in noisy electrical environments.
Frequently Asked Questions (FAQs)
What is the meaning of A6B1 alarm in ABB ACH180 drive?
Alarm A6B1 signifies that a new pass code has been entered into parameter 96.100 but has not yet been matched in confirmation parameter 96.101.
What are the primary causes of A6B1 alarm?
This alarm is caused by exiting parameter group 96 without entering the confirmation code, mismatched confirmation numbers, or interrupted keypad sessions.
How do I troubleshoot and correct A6B1 alarm?
Type the identical pass code into parameter 96.101 Confirm user pass code to confirm, or exit by entering an invalid code into 96.02 to cancel.