ABB ACH180 alarm A6E6 signals an internal configuration error within parameter group 37 User load curve. The drive raises this warning when envelope coordinates violate geometric rules, temporarily disabling ULC supervision to prevent false load tripping.
The User Load Curve establishes a multi-point envelope of torque versus speed or frequency to detect broken belts or mechanical overloads. The internal algorithm requires that speed and frequency coordinates ascend monotonically ($Point_1 < Point_2 < Point_3 < Point_4 < Point_5$) and that every overload limit remains strictly above its corresponding underload limit. Inverted or equal coordinate points break table interpolation, forcing the drive to suspend curve monitoring while continuing basic motor modulation.
What Causes A6E6 in ABB ACH180?
- Auxiliary code
0000: Speed points in parameters37.11... 37.15are not strictly monotonically increasing. - Auxiliary code
0001: Frequency points in parameters37.16... 37.20are not strictly monotonically increasing. - Auxiliary code
0002: Underload torque points (parameters37.21... 37.25) are programmed above overload torque points. - Auxiliary code
0003: Overload torque points (parameters37.31... 37.35) are programmed below underload torque points. - Inadvertent manual entry of identical speed or frequency values across adjacent curve coordinates.
Step-by-Step Troubleshooting and Solutions
- Open the drive event log on the control panel to identify the specific auxiliary code (
0000,0001,0002, or0003). - If aux code
0000or0001appears, audit parameters37.11... 37.15(speed) or37.16... 37.20(frequency); ensure each subsequent point is strictly greater than the preceding value. - If aux code
0002or0003appears, compare underload parameters37.21... 37.25directly against overload parameters37.31... 37.35at each speed point. - Adjust overload torque points so they maintain at least a
10% to 15%positive margin above the corresponding underload threshold. - Save parameter modifications and verify that alarm code
A6E6clears from the active alarm screen immediately.
Preventative Maintenance to Avoid A6E6 Faults
Plot custom User Load Curve envelopes on paper or in a spreadsheet before entering values into the drive keypad, verify motor torque curves during commissioning, and utilize Drive Composer for graphical envelope verification.
Frequently Asked Questions (FAQs)
What is the meaning of A6E6 alarm in ABB ACH180 drive?
Alarm A6E6 indicates an invalid User Load Curve configuration where speed points do not increase sequentially or overload points fall below underload limits.
What are the primary causes of A6E6 alarm?
This alarm is caused by non-sequential speed or frequency points in group 37, or inverted overload and underload torque envelope coordinates.
How do I troubleshoot and correct A6E6 alarm?
Inspect the event auxiliary code, verify that speed points 37.11... 37.15 ascend sequentially, and ensure overload limits exceed underload limits at every point.