The A981 alarm indicates that an external auxiliary device or process sensor assigned to External Event 1 has signaled an abnormal state to the ABB ACH180. The drive logs an active warning while keeping the inverter modulating to maintain critical process airflow or pumping.
The ACH180 supports programmable external event monitoring to notify operators of non-critical field conditions without shutting down essential HVAC systems. Parameter 31.01 (External event 1 source) assigns the monitoring terminal—typically digital input DI1 or a fieldbus control bit—while parameter 31.02 (External event 1 type) is configured to generate a warning rather than a fault trip. When an external interlock activates (such as a dirty filter sensor or damper position alert), the drive maintains PWM output to terminals U2, V2, W2, keeping the motor running while signaling the warning flag to supervisory BMS controllers.
What Causes A981 in ABB ACH180?
- Tripped external auxiliary contact, such as a dirty filter differential pressure switch or damper position switch.
- Loose, broken, or high-resistance control wiring connected to assigned digital input terminals (e.g.,
DI1). - Fluctuation or momentary drop of the
24V DCwetting voltage across external field sensor contacts. - Parameter
31.01(External event 1 source) mapped to an active or floating digital terminal. - Inverted contact logic selected in parameter
31.02, causing a warning under normal operational contact states.
Step-by-Step Troubleshooting and Solutions
- Identify Monitored Field Input: Check parameter
31.01(External event 1 source) to determine which digital input terminal or communication word triggers Event 1. - Inspect the Connected External Device: Examine the physical field sensor (e.g., air filter differential pressure switch) to determine if service or media replacement is required.
- Measure Terminal Voltage: Place multimeter probes across the assigned digital input and
DGND; confirm whether24V DCis present when the field contact is closed. - Review Event Action Configuration: Inspect parameter
31.02(External event 1 type) to verify whether the system expects normally open or normally closed contact behavior. - Perform Insulation Megger Test: If long external wiring raceways are used, disconnect leads and run a
500V DCinsulation test to ground to rule out intermittent cable degradation.
Preventative Maintenance to Avoid A981 Alarms
Service HVAC filter media on scheduled maintenance cycles, verify terminal screw torque on digital control blocks annually, and inspect outdoor damper end-switches for weatherproofing integrity.
Frequently Asked Questions (FAQs)
What is the meaning of A981 alarm in ABB ACH180 drive?
The A981 alarm indicates that an external auxiliary sensor assigned to External Event 1 has activated, generating an alert while allowing the motor to continue running.
What are the primary causes of A981 alarm?
Primary root causes include dirty air filter differential switches, damper limit switch warnings, loose digital input wiring, loss of 24V DC wetting voltage, and contact logic mismatches.
How do I troubleshoot and correct A981 alarm?
Identify the input source in parameter 31.01, inspect the physical field sensor, measure for 24V DC across the assigned terminal, and reset the external device.