AFE2 Emergency stop (off1 or off3) alarm in ABB ACH180 drive

Home/ABB/ABB ACH180 drive/AFE2 Emergency stop (off1 or off3) alarm in ABB ACH180 drive

ABB ACH180 alarm AFE2 signifies that the drive has initiated a controlled emergency deceleration stop under mode Off1 or Off3. The drive modulates the motor down to zero speed along a rapid deceleration ramp before cutting power stage gating.

Emergency Stop Off1 and Off3 correspond to controlled stops under IEC 60204-1 Stop Category 1. Off1 decelerates the motor along standard ramp parameter 23.13 Deceleration time 1, whereas Off3 utilizes the rapid emergency deceleration time set in parameter 23.23 Emergency stop time. During an Off3 ramp, high regenerative kinetic energy is pumped back into the intermediate DC bus. Once motor shaft rotation reaches zero, PWM switching ceases, locking out operation under alarm AFE2 until reset.

What Causes AFE2 in ABB ACH180?

  1. Activation of an emergency stop input assigned to Off1 or Off3 in parameter 21.04 Emergency stop mode.
  2. Opening of external safety relay contacts wired to the input defined in parameter 21.05 Emergency stop source.
  3. Building automation system issuing an emergency stop ramp command over BACnet or Modbus communications.
  4. Loose wire or terminal corrosion causing an intermittent open circuit on the emergency stop digital input.
  5. Inadvertent manual selection of Off1/Off3 stop modes during safety circuit commissioning.

Step-by-Step Troubleshooting and Solutions

  1. Confirm that the driven equipment has come to a safe, complete standstill and that plant operating conditions permit restarting.
  2. Inspect all physical emergency stop buttons and restore them to their normal, closed operational positions.
  3. Check parameter 21.04 Emergency stop mode to verify whether the drive is set to Off1 (standard ramp) or Off3 (emergency ramp).
  4. Review parameter 23.23 Emergency stop time; confirm that the emergency ramp is not set too fast to prevent intermediate DC link overvoltage trips during braking.
  5. Measure voltage at the digital input terminal assigned in parameter 21.05 to verify a stable 24V DC signal, then cycle the run command to clear AFE2.

Preventative Maintenance to Avoid AFE2 Faults

Regularly test dynamic braking choppers and resistors if fitted to ensure rapid Off3 emergency stops do not overload the DC bus, and inspect e-stop push-button contacts for oxidation in humid air-handler rooms.

Frequently Asked Questions (FAQs)

What is the meaning of AFE2 alarm in ABB ACH180 drive?

Alarm AFE2 indicates that the drive has received an Emergency Stop Off1 or Off3 command and has executed a controlled deceleration ramp to zero speed.

What are the primary causes of AFE2 alarm?

This alarm is caused by activated emergency stop push buttons, safety relay trips, building automation interlocks, or open wiring on the input assigned in 21.05.

How do I troubleshoot and correct AFE2 alarm?

Verify system safety, return emergency stop push buttons to their normal positions, verify 24V DC at the digital input, and cycle the run enable command.