The AFF2 warning indicates that a digital input currently forced via software simulation is being used as the active source for parameter 20.40 Run permissive. The ABB ACH180 flags this condition to alert engineers that physical process interlocks are being bypassed in software.
During drive commissioning or diagnostic troubleshooting, technical personnel can manually override digital input hardware states using internal forcing registers. However, when parameter 20.40 (Run permissive) references a forced digital input, the drive operates without true physical verification from field devices such as chilled water flow switches or cooling fans. The ACH180 issues warning AFF2 while continuing motor modulation on terminals U2, V2, W2, reminding plant operators that automated machinery protection has been superseded by a software simulation bit.
What Causes AFF2 in ABB ACH180?
- The digital input channel assigned to parameter
20.40(Run permissive) is forced in parameter10.03(DI force selection). - Commissioning override bits left active following bench testing or control loop simulation.
- Technician forcing digital inputs via Drive Composer PC tool without unforcing before placing the unit in service.
- Restoring a diagnostic parameter backup file that had digital input force registers enabled.
- Accidental modification of parameter
10.03during automated fieldbus parameter downloads.
Step-by-Step Troubleshooting and Solutions
- Inspect Run Permissive Parameter: Check parameter
20.40(Run permissive) to identify which digital input terminal (e.g.,DI1,DI2) provides the run permissive signal. - Review DI Force Selection Register: Open parameter
10.03(DI force selection) and check if the bit corresponding to that digital input is set to1(Forced). - Unforce Digital Inputs: Set parameter
10.03to0000 0000to disable software forcing and return all digital inputs to real-world physical terminal tracking. - Verify Physical Field Wiring: Ensure the physical permissive contact wired between
+24Vand the assigned terminal is closed, and verify with a multimeter that24V DCis present. - Confirm Alarm Clearance: Check that warning
AFF2clears automatically once the forced bit is reset and the real terminal signal governs the run permissive circuit.
Preventative Maintenance to Avoid AFF2 Faults
Incorporate a mandatory verification step in commissioning sign-off checklists to ensure parameter 10.03 is cleared to zero, and restrict parameter write access using security PIN codes in parameter group 96.
Frequently Asked Questions (FAQs)
What is the meaning of AFF2 alarm in ABB ACH180 drive?
The AFF2 alarm indicates that the digital input assigned to parameter 20.40 Run permissive is actively forced in software rather than following physical terminal signals.
What are the primary causes of AFF2 alarm?
Primary root causes include active override bits in parameter 10.03 DI force selection, incomplete commissioning sign-offs, and parameter backup restores containing forced test data.
How do I troubleshoot and correct AFF2 alarm?
Check parameter 20.40, locate the forced input bit in parameter 10.03, reset the force selection to zero, and verify that the physical field circuit delivers valid 24V DC.