AFF3 Run permissive forced warning alarm in ABB ACH180 drive

Home/ABB/ABB ACH180 drive/AFF3 Run permissive forced warning alarm in ABB ACH180 drive

The AFF3 warning indicates that one or more digital inputs configured as sources for Start Interlocks 1 through 4 are actively forced in software. The ABB ACH180 warns operators that equipment start permissives are running under software simulation.

The start interlock suite (parameters 20.41...20.44) ensures that mechanical isolation dampers, fire dampers, and safety gates are proven before motor rotation begins. When an input assigned to any of these interlocks is overridden via parameter 10.03 (DI force selection), the drive evaluates interlock logic using simulated bits rather than physical voltage at the control terminals. The ACH180 issues warning AFF3 to notify technicians that while PWM gating commands to terminals U2, V2, W2 may be permitted, the drive is operating in a bypass state that overrides external hardware safeties.

What Causes AFF3 in ABB ACH180?

  1. One or more bits corresponding to digital inputs in parameter 10.03 (DI force selection) are set to 1 while mapped to parameters 20.41...20.44.
  2. Commissioning engineers forcing digital inputs to test drive rotation without field sensors physically wired.
  3. Diagnostic scripts in Drive Composer leaving forced bits enabled following routine maintenance.
  4. Unintended parameter changes over Modbus communication altering the digital input force register.
  5. Loading a parameter macro template that included pre-configured digital input simulation bits.

Step-by-Step Troubleshooting and Solutions

  1. Review Start Interlock Sources: Check parameters 20.41 (Start interlock 1), 20.42 (Start interlock 2), 20.43 (Start interlock 3), and 20.44 (Start interlock 4) to identify all assigned digital inputs.
  2. Inspect Force Selection Register: Check parameter 10.03 (DI force selection) to identify which specific digital input bits (e.g., bit 0 for DI1, bit 1 for DI2) are set to 1.
  3. Clear Forced Input Bits: Reset the active bits in parameter 10.03 back to 0, or set the entire word to 0000 0000 to return control to physical wiring.
  4. Measure Physical Input Signals: Measure voltage between each assigned digital input terminal and DGND to ensure 24V DC is present when external safety devices are closed.
  5. Verify Warning Removal: Confirm that warning AFF3 disappears from the active alarm list once physical digital signals govern all start interlocks.

Preventative Maintenance to Avoid AFF3 Faults

Always audit parameter 10.03 before handing over HVAC air handling units to operational staff, document all forced testing in maintenance logs, and password-protect commissioning menus.

Frequently Asked Questions (FAQs)

What is the meaning of AFF3 alarm in ABB ACH180 drive?

The AFF3 alarm indicates that one or more digital inputs assigned to Start Interlocks 1 through 4 are actively forced in software rather than responding to field wiring.

What are the primary causes of AFF3 alarm?

Primary root causes include active force bits in parameter 10.03 DI force selection, incomplete testing procedures during commissioning, and loading parameter templates with simulated inputs.

How do I troubleshoot and correct AFF3 alarm?

Check interlock parameters 20.41...20.44, clear all force bits in parameter 10.03 to zero, and verify that physical field sensors supply genuine 24V DC to the terminals.