AFFE Override active alarm in ABB ACH180 drive

Home/ABB/ABB ACH180 drive/AFFE Override active alarm in ABB ACH180 drive

Warning AFFE Override active in the ABB ACH180 drive indicates that the drive has entered HVAC Override Mode (such as Fireman’s Override or smoke purge control). The drive operates under prioritized life-safety instructions, bypassing non-critical protective faults to maintain essential emergency ventilation.

In commercial building safety systems, the ACH180 is programmed to act as a mission-critical smoke evacuation or stairwell pressurization asset. When the dedicated digital input mapped in parameter group 70 Override energizes, the drive locks into Override Mode. The operating system suppresses standard process interlocks, external warnings, and non-fatal motor overload trips, forcing the inverter to modulate the motor at a programmed constant speed or direction across terminals U2, V2, W2. The drive will continue to run the motor up to its ultimate physical thermal limits—even risking hardware destruction—to preserve human life and clear smoke paths during building fire emergencies.

What Causes AFFE in ABB ACH180?

  1. Activation of a dedicated fire alarm panel relay or smoke control switch connected to the Override digital input.
  2. Manual testing of emergency fire ventilation sequences by building commissioning personnel.
  3. A short circuit, false 24V DC signal, or wiring bridge on the digital input assigned in parameter 70.02 Override enable.
  4. Supervisory building automation commands asserting override control words over fieldbus communications.
  5. Incorrectly configured polarity (active-high versus active-low) in parameter 70.02 Override enable.

Step-by-Step Troubleshooting and Solutions

  1. Check parameter group 70 Override, specifically parameter 70.02 Override enable, to identify the assigned digital trigger input.
  2. Inspect parameter 70.03 Override speed reference and 70.04 Override frequency reference to verify the programmed emergency running setpoint.
  3. Verify the physical state of the building fire alarm panel, smoke damper end-switches, and firefighter control station keyswitches.
  4. Measure DC voltage at the assigned override digital input terminal using a multimeter; confirm 0V DC when emergency override is inactive.
  5. Check parameter 70.06 Override direction and test motor cable insulation with a 500V megger to ensure emergency high-speed runs do not trigger short circuits.

Preventative Maintenance to Avoid AFFE Faults

Conduct scheduled semi-annual functional testing of the smoke control system to confirm that override signals activate and disengage cleanly. Inspect emergency control wiring for insulation chafing and verify that building automation fire alarm relays release completely without contact sticking.

Frequently Asked Questions (FAQs)

What is the meaning of AFFE fault in ABB ACH180 drive?

The AFFE warning is an informative notice indicating that the ABB ACH180 drive has entered emergency Override Mode to maintain critical smoke extraction or ventilation.

What are the primary causes of AFFE fault?

This warning is caused by fire alarm panel contact closure, manual testing of smoke purge systems, fieldbus override commands, or a 24V DC signal on the override terminal.

How do I troubleshoot and correct AFFE fault?

Verify building fire alarm relays, inspect digital input voltages, check parameter 70.02 configuration, and reset external emergency keyswitches.