B688 Auto stop command alarm in ABB ACH180 drive

Home/ABB/ABB ACH180 drive/B688 Auto stop command alarm in ABB ACH180 drive

ABB ACH180 event B688 is an informative event logged when an active start signal is removed while the drive is operating in Auto mode. The drive initiates its configured stopping profile, bringing the motor to rest and cutting inverter modulation.

During normal automated operation, removing the run enable signal or transitioning the digital start input to logic 0 prompts the drive to execute the stopping sequence configured in parameter 21.03 Stop mode. Depending on user selection, the drive either decelerates the motor along parameter 23.13 Deceleration time 1 or terminates IGBT switching pulses immediately to allow coasting. Event B688 records the exact timestamp of this command, verifying that motor shutdown resulted from standard remote automation logic.

What Causes B688 in ABB ACH180?

  1. Opening of an external BMS automation run contact wired to digital input terminal DI1.
  2. Building management controller transmitting a Stop bit over BACnet MS/TP or Modbus RTU serial links.
  3. Expiration of an internal run timer or time-of-day HVAC occupancy schedule.
  4. Process PID controller transitioning into sleep mode due to low process flow demand.
  5. Intermittent open circuit or loose terminal connection in the external two-wire start circuit.

Step-by-Step Troubleshooting and Solutions

  1. Verify whether the motor shutdown corresponds with planned building management occupancy or setback schedules.
  2. Check parameter 20.01 Ext1 commands to identify the assigned external stop command input source.
  3. Measure voltage across the designated start digital input terminal; confirm whether input voltage drops below 5V DC, signaling an open stop state.
  4. Review parameter 21.03 Stop mode to verify whether the drive is set to Ramp or Coast stopping behavior.
  5. If nuisance stoppages occur, inspect field wiring for loose terminal screws, corroded interposing relay contacts, or fieldbus communication drops.

Preventative Maintenance to Avoid B688 Faults

Routinely inspect external control relay contacts for pitting or oxidation, maintain firmware parameter backups, and monitor fieldbus communication error counters to ensure stop commands are clean and uncorrupted.

Frequently Asked Questions (FAQs)

What is the meaning of B688 alarm in ABB ACH180 drive?

Event B688 is an informational status entry confirming that the drive received a valid stop command while operating under Auto mode control.

What are the primary causes of B688 alarm?

This event is triggered by opening remote BMS start contacts, serial fieldbus stop commands, time-clock schedule expirations, or PID sleep mode entry.

How do I troubleshoot and correct B688 alarm?

No action is needed for normal scheduled stops; if stops occur unexpectedly, check external 24V DC control circuits and review BMS schedules.