The A5013 alarm indicates that keypad start control is disabled because a drive start inhibit interlock or pending emergency stop condition remains active. The ACS150 hardware logic prevents local manual starting until all pre-run safety circuits and stop commands are fully cleared.
Before the ACS150 modulates intermediate DC bus voltage into alternating stator currents, safety and command state registers must satisfy the internal run permissive checklist. When an emergency stop is active via parameter 2109 (EMERG STOP SEL), or if a 3-wire stop circuit on terminals DI1/DI2 remains open, start inhibit activates. Pressing the Start button while this inhibit condition persists triggers A5013, maintaining IGBT gates in a de-energized, high-impedance state to prevent accidental machine movement during an uncleared emergency.
What Causes A5013 in ABB ACS150?
- Depressed or latched external emergency stop push-button tied to parameter
2109(EMERG STOP SEL). - Open stop circuit on digital inputs when 3-wire control macro is selected in parameter
1001. - Start command toggled on before drive run enable or safety interlocks are validated.
- Auxiliary safety relay open or disconnected wiring on terminal strip
DI1–DI5. - Supply voltage brownout or control board reset leaving the start state machine in locked inhibit status.
Step-by-Step Troubleshooting and Solutions
- Inspect all physical emergency stop buttons and pull-cords, reset any latched contacts, and verify safety relays are energized.
- Review parameter
2109(EMERG STOP SEL) to confirm which digital input terminal is designated for emergency stop supervision. - Check parameters
1001(EXT1 COMMANDS) and1002(EXT2 COMMANDS) to confirm stop/start wiring logic matches hardware signals. - If utilizing 3-wire macros, pulse or cycle the stop digital input (typically
DI2) to clear the memory latch before attempting a panel start. - Measure DC control voltages across terminals
+24Vand digital commons with a digital multimeter to confirm stable loop power.
Preventative Maintenance to Avoid A5013 Faults
Routinely audit safety interlock switches, e-stop circuits, and auxiliary relay contacts for contact oxidation. Verify that wiring diagrams reflect parameter assignments in Groups 10 and 21 to facilitate rapid field fault clearing.
Frequently Asked Questions (FAQs)
What is the meaning of A5013 fault in ABB ACS150 drive?
The A5013 alarm indicates that panel starting is blocked because an emergency stop or 3-wire stop command is currently active.
What are the primary causes of A5013 fault?
Primary causes include a latched emergency stop button, an open 3-wire stop circuit, and misconfigured stop input parameters.
How do I troubleshoot and correct A5013 fault?
Troubleshoot by releasing any active e-stop, resetting the 3-wire stop signal, and checking parameter 2109 and parameter 1001 settings.