The F0035 fault indicates an output wiring error, specifically that input power supply cabling has been connected backwards to motor output terminals U2, V2, W2, or that severe capacitive leakage is present on ungrounded/corner-grounded delta networks. The ACS150 locks out operation to prevent catastrophic inverter failure.
The ACS150 incorporates pre-run diagnostic tests and internal current sensing to detect reverse power connections before full PWM modulation commences. If AC mains voltage is connected to motor terminals U2, V2, W2, current backfeeds into the free-wheeling diodes of the IGBT bridge, generating immediate trip conditions. Additionally, in ungrounded (IT) or corner-grounded delta power systems, excessive common-mode parasitic capacitance across long shielded motor cables can generate false leakage currents that trigger F0035. The drive trips to prevent inverter destruction and ground bus arc flash.
What Causes F0035 in ABB ACS150?
- Input mains power conductors incorrectly wired to drive output motor terminals
U2, V2, W2. - Motor cables connected backwards to input supply terminals
L1, L2, L3. - Operating on corner-grounded delta or ungrounded IT electrical systems with the internal EMC filter screw attached.
- Excessive motor cable length generating high capacitive leakage charging current to earth ground.
- Short circuit or damaged internal current measurement shunt on the drive inverter power stage.
Step-by-Step Troubleshooting and Solutions
- Immediately de-energize mains power and verify that incoming AC supply lines are wired strictly to terminals
L1, L2, L3. - Verify that motor leads are correctly landed on output terminals
U2, V2, W2and grounded at terminalPE. - If operating on an ungrounded (IT) or corner-grounded delta electrical network, disconnect the internal EMC filter screw as specified in the manual.
- Perform an insulation resistance megger test (at 500V DC) on the motor and motor cables disconnected from the drive to detect phase-to-ground leakage.
- For long cable runs exceeding manufacturer limits, install an output reactor or dv/dt filter to reduce high capacitive ground currents.
Preventative Maintenance to Avoid F0035 Faults
Always verify wire labeling and terminal assignments before initial drive energization. Review supply earthing topology (TN vs IT/delta) during engineering design to ensure proper EMC screw configuration and output reactor selection.
Frequently Asked Questions (FAQs)
What is the meaning of F0035 fault in ABB ACS150 drive?
The F0035 fault indicates that input power wiring is connected to motor terminals, or excessive capacitive ground leakage is detected.
What are the primary causes of F0035 fault?
Primary causes include crossed input and motor connections, ungrounded delta system leakage, long shielded motor cables, and internal inverter faults.
How do I troubleshoot and correct F0035 fault?
Troubleshoot by confirming power is connected to L1-L3 and motor to U2-W2, removing the EMC screw on delta grids, and megger testing motor cables.