2310 fault in ABB ACS180 drive

Home/ABB/ABB ACS180 drive/2310 fault in ABB ACS180 drive

The 2310 fault code in the ABB ACS180 drive represents a critical Overcurrent trip. It occurs when the instantaneous output phase current exceeds the drive internal hardware trip ceiling, initiating an immediate emergency shutdown of the inverter bridge.

To preserve semiconductor die integrity, the ACS180 monitors instantaneous motor currents using fast hardware comparator circuits. If mechanical jamming, severe load surges, or output shorts drive phase currents past the rated peak limit (typically 200% to 250% of nominal), the gate driver logic de-energizes all IGBTs within microseconds. This immediate shutdown prevents catastrophic thermal failure of the power bridge, suppresses severe intermediate DC bus ripple, and safeguards connected motor windings.

What Causes 2310 in ABB ACS180?

  1. Sudden mechanical jamming, binding, or heavy process shock loading applied to the motor shaft.
  2. Acceleration ramp configured too aggressively in parameter 23.12 Acceleration time 1 or parameter 28.72 Freq acceleration time 1.
  3. Mismatched motor nameplate parameters entered into parameter group 99 Motor data (parameters 99.06, 99.07, 99.08).
  4. Phase loss on incoming AC supply lines L1, L2, L3 or an earth fault on the motor power cabling.
  5. Power factor correction capacitors, output surge suppressors, or contactors opening and closing while the drive is modulating.

Step-by-Step Troubleshooting and Solutions

  1. Inspect the mechanical load, uncoupling the driven machine if required to verify free shaft rotation without bearing binding or lockup.
  2. Increase the acceleration time in parameter 23.12 Acceleration time 1 or frequency ramp parameter 28.72 Freq acceleration time 1.
  3. Verify that motor rating plate settings in group 99 Motor data match the motor nameplate exactly, confirming correct star or delta wiring links.
  4. Disconnect motor leads from terminals T1/U, T2/V, and T3/W and perform a 500V DC megger test to rule out ground faults (minimum 1 MΩ).
  5. Confirm that no electromechanical contactors switch downstream of the drive during operation, and remove any power factor correction capacitors.

Preventative Maintenance to Avoid 2310 Faults

Periodically clean drive heatsinks and cooling fan ducts to maintain optimal thermal margins. Conduct regular lubrication and vibration monitoring of motor bearings to prevent mechanical binding, and check electrical torque settings on supply terminals L1, L2, L3.

Frequently Asked Questions (FAQs)

What is the meaning of 2310 fault in ABB ACS180 drive?

The 2310 fault signifies that the drive instantaneous output current has exceeded the hardware safety threshold, causing an emergency inverter shutdown.

What are the primary causes of 2310 fault?

Primary causes include mechanical equipment jams, steep acceleration ramp times, incorrect motor nameplate parameters, earth faults, and incoming supply phase loss.

How do I troubleshoot and correct 2310 fault?

Extend acceleration times, check motor data in parameter group 99, test motor insulation with a megger, and verify mechanical load freedom.