3385 fault in ABB ACS180 drive

Home/ABB/ABB ACS180 drive/3385 fault in ABB ACS180 drive

The 3385 fault indicates that the autophasing routine has failed in the ABB ACS180 drive. The drive shuts down PWM output to prevent uncontrolled torque production or electrical instability when synchronizing magnetic field angles.

Autophasing is an essential startup routine applied when operating permanent magnet synchronous motors (PMSM) or synchronous reluctance motors without absolute rotor position feedback. The ACS180 injects small test current pulses across the stator windings via the output IGBT bridge to detect magnetic saturation and establish rotor magnetic pole alignment. If the motor shaft moves due to an external load, or if internal motor parameter models do not correlate with physical inductance curves, the algorithm aborts. Gating pulses are inhibited to prevent severe current surges and intermediate DC bus overvoltage.

What Causes 3385 in ABB ACS180?

  1. Motor shaft was already rotating, windmilling, or vibrating during autophasing sequence initiation.
  2. The motor identification run requested in parameter 99.13 ID run requested was bypassed, failed, or incomplete.
  3. Incorrect motor selection configured under parameter 99.03 Motor type (e.g., standard induction instead of PMSM).
  4. Mechanical backlash, excessive counter-torque, or load friction preventing accurate magnetic field alignment.
  5. High-resistance terminations or loose terminal connections on motor output leads U2, V2, W2.

Step-by-Step Troubleshooting and Solutions

  1. Ensure the motor shaft is completely stationary and mechanically locked against backspin before starting the autophasing routine.
  2. Verify parameter 99.03 Motor type correctly matches the physical motor nameplate design (such as permanent magnet motor).
  3. Re-run the full motor identification sequence by selecting an appropriate ID run mode in parameter 99.13 ID run requested.
  4. Check parameter 21.13 Autophasing mode to select between turning and standstill autophasing routines depending on load constraints.
  5. Perform an insulation resistance test with a 500V megohmmeter across motor cables and terminals U2, V2, W2 to ensure no phase grounds exist.

Preventative Maintenance to Avoid 3385 Faults

Always re-execute motor identification and autophasing routines whenever a motor, mechanical gearbox, or power lead is replaced. Ensure mechanical holding brakes fully engage during standstill periods to eliminate rotor back-rotation prior to drive acceleration.

Frequently Asked Questions (FAQs)

What is the meaning of 3385 fault in ABB ACS180 drive?

It indicates that the drive’s automatic rotor magnetic pole alignment routine for synchronous motors was unable to complete successfully.

What are the primary causes of 3385 fault?

Primary causes are pre-existing motor shaft rotation at start, incomplete motor ID runs, incorrect motor type settings in parameter 99.03, or excessive load torque.

How do I troubleshoot and correct 3385 fault?

Ensure the motor shaft is motionless, confirm the correct motor type in parameter 99.03, and complete a valid motor identification run via parameter 99.13.