5681 PU Communication Fault in ABB ACS180 Drive

Home/ABB/ABB ACS180 drive/5681 PU Communication Fault in ABB ACS180 Drive

The 5681 fault indicates that severe communication errors or packet corruptions have occurred across the internal data bus connecting the drive control unit and the power unit (PU). The drive trips immediately to prevent unsynchronized PWM gate firing and destructive shoot-through currents.

The ACS180 uses a high-speed internal communication link between the primary digital signal processor on the control board and the gate driver microprocessor on the power board. This bus continuously exchanges critical data including voltage references, phase current feedback, and gate timing pulses. When cyclic redundancy check (CRC) errors, frame corruption, or missing packet acknowledgments exceed noise immunity thresholds, the drive terminates modulation to prevent uncontrollable motor behavior and protect intermediate circuit components.

What Causes 5681 in ABB ACS180?

  1. High levels of radiated electromagnetic interference (EMI) originating from unshielded motor conductors.
  2. Loose, poorly mated, or oxidized internal board-to-board ribbon cable connectors or header pins.
  3. Improper grounding of the drive chassis or missing 360-degree high-frequency cable shield clamps.
  4. Transient electrical noise induced by switching unsuppressed contactor coils in the control cabinet.
  5. Degraded communication transceiver components or cracked solder joints on the internal circuit boards.

Step-by-Step Troubleshooting and Solutions

  1. Isolate power, wait 5 minutes for capacitor discharge, and verify that the motor cable shield is clamped securely with 360-degree bonding to the grounding plate.
  2. Check for inductive noise sources inside the enclosure, ensuring that all 24V DC and 230V AC relay coils have varistor or diode surge suppression.
  3. Inspect internal board interconnections; open the drive casing if authorized and verify that internal multi-pin headers are fully seated.
  4. Verify control cabinet grounding using an earth continuity tester, ensuring impedance to main plant ground is less than 1 Ω.
  5. Perform a control unit restart via parameter 96.08 Control board boot; if communication errors persist under zero-load conditions, replace the drive.

Preventative Maintenance to Avoid 5681 Faults

Maintain strict physical segregation between high-voltage motor output cables and low-voltage control circuits. Ensure all control cabinet doors and backplates have low-impedance bonding straps to shield internal drive electronics from industrial electromagnetic noise.

Frequently Asked Questions (FAQs)

What is the meaning of 5681 fault in ABB ACS180 drive?

The 5681 fault indicates that communication packet errors have disrupted data transmission between the drive control board and the internal power unit.

What are the primary causes of 5681 fault?

The primary root causes include industrial electromagnetic interference, loose internal ribbon connectors, improper motor cable shielding, or degraded transceiver components.

How do I troubleshoot and correct 5681 fault?

Verify motor cable shielding clamps, install surge suppression on cabinet relay coils, inspect internal board headers, and ensure clean low-impedance grounding.