The 5691 fault indicates that the drive’s internal Analog-to-Digital Converter (ADC) measurement circuitry has failed its power-on self-test or reported out-of-range sensor calibration values. The drive trips immediately because reliable current, voltage, and thermal monitoring are essential for safe motor control.
During initial power-up and throughout runtime operation, the ACS180 samples critical signals using onboard high-speed ADCs, including output phase currents (via Hall-effect transducers or current shunts), intermediate DC link voltage, and heatsink thermistor feedback. Before releasing the inverter for motor modulation, the firmware validates current sensor zero-offset calibration. If an ADC channel is locked up, exhibits non-linear drift, or reads excessive zero-current bias, the drive blocks all gate firing to prevent undetected overcurrent events.
What Causes 5691 in ABB ACS180?
- Failure or hardware drift in the internal current transducer zero-offset calibration circuit.
- Damaged or malfunctioning high-speed Analog-to-Digital Converter IC on the power control board.
- Corrupted ADC factory reference voltage rail or degraded precision reference zener diodes.
- Severe electrostatic discharge (ESD) or line voltage surge penetrating internal analog measurement channels.
- Moisture condensation, conductive particulate contamination, or chemical corrosion across analog sensing traces.
Step-by-Step Troubleshooting and Solutions
- Disconnect incoming power, observe safety lockout, wait 5 minutes, and verify that motor cables are disconnected from terminals
T1/U,T2/V, andT3/Wto rule out external residual current leakage. - Re-energize the drive without the motor connected to determine whether the 5691 fault clears during a clean power-on self-test.
- Inspect the drive casing and ventilation grills for evidence of liquid contamination, condensation, or metallic dust ingress.
- Check parameter
01.11 DC voltageand motor current signals in parameter group01 Actual valuesto see if displayed values are plausible. - If the 5691 code persists with the motor disconnected, the internal measurement ADC circuitry has suffered permanent hardware failure, requiring drive replacement.
Preventative Maintenance to Avoid 5691 Faults
Ensure drive cabinets are sealed to NEMA/IP standards appropriate for the operating environment. Maintain operating environments within rated relative humidity specifications (below 95% non-condensing) and use anti-condensation heaters in panels exposed to fluctuating ambient temperatures.
Frequently Asked Questions (FAQs)
What is the meaning of 5691 fault in ABB ACS180 drive?
The 5691 fault indicates that the internal analog measurement ADC circuitry has experienced a hardware fault or failed its power-on calibration self-test.
What are the primary causes of 5691 fault?
The primary root causes include current sensor zero-offset drift, damaged ADC converter chips, unstable reference voltage rails, or internal board contamination.
How do I troubleshoot and correct 5691 fault?
Disconnect motor cables to isolate external leakage, reboot the drive, verify displayed actual current and DC voltage values, and replace the drive if the fault persists.