6685 EFB Fault 2 in ABB ACS180 Drive

Home/ABB/ABB ACS180 drive/6685 EFB Fault 2 in ABB ACS180 Drive

The 6685 fault is a protocol-specific application trip indicating that an exceptional transmission error, framing breakdown, or illegal function code was processed by the embedded fieldbus interface. The drive trips to prevent executing unverified or erroneous automation commands.

In Modbus RTU communication topologies, the ACS180 serial transceiver decodes telegram frames on EIA-485 terminals +, -, and DGND. If the supervisory PLC transmits unsupported Modbus function codes, attempts out-of-bounds register reads, or if electrical noise introduces continuous CRC checksum errors, the protocol stack flags an application exception. When parameter 58.14 Communication loss action is configured for fault response, the drive halts motor modulation to safeguard downstream machinery.

What Causes 6685 in ABB ACS180?

  1. PLC master transmitting unsupported or reserved Modbus function codes to the drive.
  2. Reversed polarity or broken communication wiring across serial differential terminals + and -.
  3. Missing, damaged, or improperly switched 120 Ω bus termination resistors causing signal reflection.
  4. Severe common-mode voltage or ground loops between the PLC and drive EIA-485 interface.
  5. Communication frame collision caused by multiple slave drives sharing duplicate node IDs.

Step-by-Step Troubleshooting and Solutions

  1. Inspect fieldbus cable terminations on the drive control strip; verify that differential lines + and - are not reversed and the shield is properly grounded.
  2. Verify bus termination; ensure a 120 Ω termination resistor is activated only at both physical endpoints of the RS-485 trunk line.
  3. Use a communication packet analyzer or oscilloscope to monitor Modbus telegrams, checking for CRC errors, framing overruns, or illegal function codes.
  4. Check parameter 58.07 Communication diagnostics on the drive keypad to review the count of received good vs. bad message packets.
  5. Review PLC transmission routines to ensure polling intervals allow sufficient response turnaround time (minimum 10 ms to 20 ms).

Preventative Maintenance to Avoid 6685 Faults

Use shielded twisted-pair cables intended for EIA-485 industrial fieldbus networks. Avoid running communication lines in parallel with motor output wiring, and ensure galvanic isolation or common reference bonding between all networked devices.

Frequently Asked Questions (FAQs)

What is the meaning of 6685 fault in ABB ACS180 drive?

The 6685 fault indicates an application-level embedded fieldbus exception, typically triggered by corrupted protocol telegrams, illegal function codes, or wiring noise.

What are the primary causes of 6685 fault?

The primary root causes include unsupported Modbus function codes, line noise inducing CRC errors, missing bus termination, or reversed RS-485 differential wiring.

How do I troubleshoot and correct 6685 fault?

Inspect physical communication wiring, verify end-of-line 120-ohm termination, analyze Modbus telegrams in parameter 58.07, and adjust PLC polling intervals.