AFE2 alarm in ABB ACS180 drive

Home/ABB/ABB ACS180 drive/AFE2 alarm in ABB ACS180 drive

The AFE2 alarm indicates that the ABB ACS180 drive has received an active emergency stop command configured for Off1 or Off3 deceleration mode. The drive brings the motor to a controlled stop and inhibits starting until safety circuits are restored.

When an emergency stop command initiates via fieldbus or hardwired digital inputs, internal logic bypasses standard speed reference profiles. Depending on configuration, the drive either ramps down along the active deceleration profile (Off1) or executes a fast emergency deceleration ramp via parameter 23.23 Emergency stop time (Off3). During this braking phase, dynamic energy regenerates into the intermediate DC bus capacitors. Once output frequency hits zero, gating pulses to the output IGBT inverter bridge are suppressed, keeping the drive in a safe holding state until the safety interlock re-closes.

What Causes AFE2 in ABB ACS180?

  1. Actuation of an external emergency stop pushbutton or tripped perimeter safety pull-cord.
  2. Open-circuit fault, loose terminal screw, or cut wire in the +24V safety interlock loop feeding digital inputs.
  3. Emergency stop command transmitted via industrial communication network through the fieldbus Control Word.
  4. Incorrect signal source logic or inverted contact configuration assigned in parameter 21.05 Emergency stop source.
  5. Tripped external safety relay unit removing permissive control voltage from control terminals.

Step-by-Step Troubleshooting and Solutions

  1. Confirm operating area safety, then inspect and reset all physical emergency stop pushbuttons in the machine circuit.
  2. Check parameter 21.05 Emergency stop source to verify which digital input terminal or communication word triggers the event.
  3. Measure DC voltage across the assigned digital input terminal (e.g., DI1 or DI2) and DGND using a multimeter; confirm steady 24V DC presence.
  4. If commanded via fieldbus, verify bit 0 and bit 2 states in the active PLC control word profile.
  5. Check motor leads on terminals U2, V2, W2 with a 500V megohmmeter if the emergency stop was triggered by unexpected mechanical jamming.

Preventative Maintenance to Avoid AFE2 Faults

Conduct monthly functional safety tests on all emergency stop pushbuttons and safety relay interlocks. Inspect auxiliary control terminal tension and replace aging electromechanical contact blocks before high contact resistance provokes nuisance tripping.

Frequently Asked Questions (FAQs)

What is the meaning of AFE2 fault in ABB ACS180 drive?

It indicates that the drive has executed an emergency stop ramp according to configured Off1 or Off3 deceleration commands.

What are the primary causes of AFE2 fault?

Primary causes include depressed emergency stop pushbuttons, loose digital input wiring, tripped safety relays, or emergency stop bits sent via fieldbus.

How do I troubleshoot and correct AFE2 fault?

Verify safe mechanical status, pull out the actuated emergency stop button, measure 24V DC on the assigned terminal, and review parameter 21.05.