AFEA alarm in ABB ACS180 drive

Home/ABB/ABB ACS180 drive/AFEA alarm in ABB ACS180 drive

The AFEA warning indicates that the start enable signal is missing in the ABB ACS180 drive. The drive holds motor modulation in standby because a required pre-start interlock has not been fulfilled.

The ACS180 control software incorporates a two-tier run authorization model separating basic start commands from permissive start enables. When parameter 20.19 Enable start command is assigned to a physical input or communication bit, the core microcontroller blocks PWM gate driver generation until this specific permissive verifies closed. While the intermediate DC link remains charged to nominal bus potential, switching output across IGBT phases U2, V2, W2 is strictly prohibited, generating warning AFEA on the local display.

What Causes AFEA in ABB ACS180?

  1. The external circuit wired to the digital input selected in parameter 20.19 is open.
  2. Auxiliary limit switches, process interlocks, or lube oil pressure switches remaining disengaged prior to machine start.
  3. Improper parameter assignment where parameter 20.19 Enable start command is routed to an unpowered terminal.
  4. Start enable bit within the PLC automation communication word remaining unasserted during startup.
  5. Defective +24V auxiliary control power supply or broken ground return connection at terminal DGND.

Step-by-Step Troubleshooting and Solutions

  1. Navigate to parameter 20.19 Enable start command and determine which digital input channel or communication bit is assigned.
  2. Inspect the physical terminal assigned (such as DI2 or DI3) and measure for 24V DC with respect to DGND.
  3. Trace external permissive loops, including enclosure door limit switches, lubrication permissive switches, or process interlocks.
  4. If start enable is managed over fieldbus communications, verify the PLC mapping logic against the ABB drive control profile.
  5. Temporarily reassign parameter 20.19 to Selected or verify internal logic using the diagnostic signal menu.

Preventative Maintenance to Avoid AFEA Faults

Routinely inspect external interlocking sensors and limit switch mechanical linkages. Clean auxiliary contact blocks and verify terminal screw tightness inside master control cabinets during annual plant turnarounds.

Frequently Asked Questions (FAQs)

What is the meaning of AFEA fault in ABB ACS180 drive?

It indicates that the drive has received an operational run command, but the prerequisite start enable permissive signal is not active.

What are the primary causes of AFEA fault?

Primary causes are open process safety switches, incorrect mapping in parameter 20.19, broken 24V control wiring, or missing PLC start bits.

How do I troubleshoot and correct AFEA fault?

Check parameter 20.19 to locate the assigned input, verify 24V DC presence on that terminal, and close external process interlocks.