A2007 AI2 LOSS alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A2007 AI2 LOSS alarm in ABB ACS310 drive

The A2007 AI2 LOSS alarm on an ABB ACS310 drive indicates that the auxiliary analog input 2 signal has fallen below the safety limit configured in parameter 3022 AI2 FAULT LIMIT. This warning alerts personnel that secondary feedback or reference signals have dropped below valid operating ranges.

Analog channel 2 is primarily utilized for process PID feedback, such as differential pressure or water flow sensors in pump control macros. When signal levels fall below the threshold, the PID algorithm cannot compute control errors. The drive responds based on parameter 3001 AI, maintaining consistent IGBT modulation at a preset frequency to prevent hydraulic shock and rapid bus voltage swings.

What Causes A2007 in ABB ACS310?

  1. Broken, shorted, or loose signal conductors on analog input terminals 5 (AI2) and 6 (AGND).
  2. Defective process sensor or disconnected external 24 VDC transmitter power source.
  3. Misconfigured analog hardware selection jumper J2 on the control interface board.
  4. Excessively high trip threshold configured in parameter 3022 AI2 FAULT LIMIT relative to sensor output.
  5. Incorrect signal scaling in parameters 1304 MINIMUM AI2 and 1305 MAXIMUM AI2.

Step-by-Step Troubleshooting and Solutions

  1. Measure the incoming loop current across terminal 5 (AI2) and terminal 6 (AGND) using a calibrated digital multimeter.
  2. Check the position of hardware jumper J2 to confirm whether current loop mode (0/4–20 mA) or voltage mode is selected.
  3. Review parameter 3022 AI2 FAULT LIMIT and confirm it reflects the correct fault threshold (typically 20.0% for a 4–20 mA transmitter).
  4. Check auxiliary power output between terminal 9 (+24V) and terminal 11 (GND) to ensure proper transmitter excitation voltage.
  5. Simulate a 12 mA reference signal using a portable process calibrator to verify that actual signal parameter 0121 AI2 tracks correctly.

Preventative Maintenance to Avoid A2007 Faults

Maintain tight terminations at the X1A control strip and verify that signal cable shielding is properly tied to ground at terminal 1 (SCR). In wet pump rooms, inspect transducer junction boxes for moisture intrusion and replace deteriorated cable glands to avoid intermittent loop impedance changes.

Frequently Asked Questions (FAQs)

What is the meaning of A2007 AI2 LOSS fault in ABB ACS310 drive?

It indicates that the analog input 2 current or voltage level has fallen below the supervisory threshold set in parameter 3022.

What are the primary causes of A2007 fault?

The primary causes are disconnected sensor wiring on terminal 5, a failed pressure or flow transmitter, an incorrect J2 jumper setting, or misconfigured scaling parameters.

How do I troubleshoot and correct A2007 fault?

Check the loop current at terminal 5 with a multimeter, verify that jumper J2 matches your signal type, inspect 24V transmitter power, and calibrate parameter 3022.