A2013 alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A2013 alarm in ABB ACS310 drive

The A2013 alarm indicates that the drive has initiated an automatic fault reset sequence in accordance with configured recovery rules. The ABB ACS310 broadcasts this warning to notify operators that an intermittent trip condition occurred and is actively being cleared by the controller.

When automatic reset functions are enabled, the ACS310 monitors minor trip events such as transient line undervoltage, overvoltage spikes, or momentary overcurrent surges. Instead of locking out into a hard trip, the internal logic pauses pulse-width modulation (PWM), awaits the delay interval configured in parameter 3103 DELAY TIME, and automatically restarts motor modulation. If recurring faults exceed the trial counter, the drive transitions into an unrecoverable hard fault.

What Causes A2013 in ABB ACS310?

  1. Normal execution of automated fault recovery routines programmed in parameter group 31 AUTOMATIC RESET.
  2. Intermittent power supply fluctuations, sags, or transient spikes on input terminals L1, L2, L3.
  3. Spurious analog or digital noise entering control wiring due to improper grounding or unshielded cables.
  4. Marginal motor overcurrent caused by erratic process flow or fluctuating pump backpressure.
  5. Exceeding the maximum allowed reset attempts defined in parameter 3101 NUMBER OF TRIES.

Step-by-Step Troubleshooting and Solutions

  1. Access parameter group 31 AUTOMATIC RESET and check parameter 3101 NUMBER OF TRIES and parameter 3102 TRIAL TIME to review reset behavior.
  2. Examine parameter 0401 LAST FAULT to determine the exact underlying fault that triggered the automatic reset cycle.
  3. Measure three-phase AC input voltages at terminals L1, L2, L3 with a calibrated multimeter to check for phase unbalance or voltage sags.
  4. Verify that all control signal cables on digital inputs DI1 through DI5 are twisted, shielded, and grounded at one end only.
  5. If auto-resetting is creating equipment safety hazards, disable the automated sequence by setting parameter 3101 NUMBER OF TRIES to 0.

Preventative Maintenance to Avoid A2013 Faults

Inspect incoming line power quality with a power analyzer, tighten input lugs to specified torque tolerances, and ensure auxiliary control cabinets maintain high electromagnetic compatibility (EMC) through clean ground planes.

Frequently Asked Questions (FAQs)

What is the meaning of A2013 alarm in ABB ACS310 drive?

It is an operational status alarm signaling that the drive has detected a minor fault and is currently executing an automated reset and restart routine.

What are the primary causes of A2013 alarm?

Primary causes include intermittent line voltage dips, brief overcurrent spikes, aggressive process fluctuations, and active auto-restart parameters in group 31.

How do I troubleshoot and correct A2013 alarm?

Review the fault history log in parameter 0401 to identify the underlying trip reason, check incoming mains stability, and tune parameter group 31 settings.