A2018 alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A2018 alarm in ABB ACS310 drive

The A2018 alarm indicates that the ABB ACS310 drive process PID controller has activated sleep mode due to low process demand. The drive suppresses motor output modulation while remaining armed and ready to restart automatically when system demand returns.

When sleep criteria are met, the drive processor stops pulse-width modulation (PWM) switching across the output IGBT stage, reducing motor current to zero amperes. The intermediate DC bus remains charged at nominal potential (approximately 540V DC on 400V AC units). This control prevents centrifugal pumps and ventilation fans from running at deadhead pressures or inefficient minimum speeds, mitigating mechanical wear and wasted electrical energy.

What Causes A2018 in ABB ACS310?

  1. Process feedback exceeding the sleep threshold set in parameter 4022 SLEEP SELECTION.
  2. Motor operating below the frequency configured in parameter 4023 PID SLEEP LEVEL for longer than parameter 4024 PID SLEEP DELAY.
  3. Miscalibrated or drifting analog input signal on control terminals AI1 or AI2.
  4. Closed downstream discharge valves or zero fluid consumption creating artificially high process pressure.

Step-by-Step Troubleshooting and Solutions

  1. Review parameter group 40 PROCESS PID SET 1 or 41 PROCESS PID SET 2, checking parameters 4023 PID SLEEP LEVEL, 4024 PID SLEEP DELAY, and 4025 WAKE-UP DEV against process requirements.
  2. Measure the analog transducer voltage or current feedback signal across analog inputs AI1 or AI2 with a calibrated multimeter to confirm accurate pressure readings.
  3. Inspect field valves, piping restrictions, and mechanical flow demands to ensure process flow conditions match current control setpoints.
  4. Test motor stator insulation resistance with a 500V DC megger tester across motor terminals U2, V2, W2 to frame ground to rule out motor winding insulation degradation.

Preventative Maintenance to Avoid A2018 Faults

Regularly calibrate pressure and flow transmitters, verify analog wiring shielding at control terminal SCR to avoid electrical noise, and adjust sleep delay timers to eliminate nuisance cycling during periodic operational shifts.

Frequently Asked Questions (FAQs)

What is the meaning of A2018 alarm in ABB ACS310 drive?

Alarm A2018 confirms that the drive entered an intentional energy-saving sleep state because process feedback reached the programmed PID setpoint limit.

What are the primary causes of A2018 alarm?

The alarm is triggered by low mechanical demand causing output frequency to stay below parameter 4023 for the duration specified in parameter 4024.

How do I troubleshoot and correct A2018 alarm?

Verify sensor calibration on analog terminals AI1 and AI2, inspect hydraulic valve positions, and tune sleep and wake-up threshold parameters in group 40.