A5080 alarm in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/A5080 alarm in ABB ACS310 drive

The A5080 alarm on an ABB ACS310 indicates that an attempted control operation—such as a start, stop, or reference change—was rejected because the drive is in Remote (REM) control mode. The drive restricts keypad control to maintain process safety.

The ACS310 operates under two distinct control locations: Local (LOC) and Remote (REM). In Remote mode, output frequency modulation and motor run/stop states are governed exclusively by input terminals (such as DI1-DI5 and AI1-AI2) or Modbus fieldbus communications. When an operator attempts to alter speed references or start the motor using keypad pushbuttons without taking local control ownership, the drive firmware asserts warning A5080. This interlock prevents contradictory speed commands from interfering with automated building management or industrial process networks.

What Causes A5080 in ABB ACS310?

  1. Pressing the keypad Start, Stop, or Reference direction keys while the drive is operating in Remote (REM) mode.
  2. Parameter 1606 LOCAL LOCK configured to lock out operators from switching the drive to Local mode.
  3. Supervisory PLC or SCADA systems maintaining automated remote control during inspection routines.
  4. Confusion regarding the active control location between plant automation networks and the local panel.
  5. Digital input selections in parameter group 10 START/STOP/DIR actively enforcing external command priority.

Step-by-Step Troubleshooting and Solutions

  1. Press the LOC/REM button on the control panel to switch the active control mode from Remote (REM) to Local (LOC).
  2. Confirm that the upper-left status header on the panel display toggles from REM to LOC before entering commands.
  3. Check parameter 1606 LOCAL LOCK and set it to 0 (NOT SEL) if the keypad mode switch is locked.
  4. Review parameter 1102 EXT1/EXT2 SEL to verify the active external reference source controlling the drive.
  5. Inspect active digital input status in parameter 0118 DI 1-5 STAT to verify remote run commands before taking local control.

Preventative Maintenance to Avoid A5080 Faults

Train operators on the distinction between Local and Remote control modes, document control room handover procedures, and use parameter 1606 LOCAL LOCK to restrict local keypad access on critical, automated production processes.

Frequently Asked Questions (FAQs)

What is the meaning of A5080 fault in ABB ACS310 drive?

The A5080 alarm indicates that the command entered on the keypad is blocked because the drive is set to Remote control mode.

What are the primary causes of A5080 fault?

It occurs when attempting to start, stop, or change speed references via the keypad while the drive is controlled by external inputs or fieldbus.

How do I troubleshoot and correct A5080 fault?

Press the LOC/REM key on the control panel to switch the drive to Local mode, and ensure parameter 1606 does not lock local mode.