The A5087 alarm indicates that a parameter download from a source drive to a destination drive has failed due to incompatible parameter sets. The ABB ACS310 issues this warning to prevent mismatched drive configurations, motor ratings, or software builds from creating operational hazards.
During a parameter transfer from the Assistant Control Panel or commissioning software, the target ACS310 evaluates the incoming parameter header block against its own hardware architecture. The drive cross-references internal rating tables, application macros, and firmware revisions recorded in parameter group 33 INFORMATION. If the source backup was generated on a drive with a different kilowatt rating, current class, or firmware revision, the destination drive aborts the write operation, keeping its motor modulation logic and intermediate DC circuit protections completely uncompromised.
What Causes A5087 in ABB ACS310?
- Attempting to clone parameters between drives with differing firmware versions stored in parameter
3301 FIRMWARE VERSION. - Downloading a configuration created on a drive of a different power rating or frame size (e.g., Frame R1 to Frame R3).
- Transferring a parameter archive originating from a different ABB drive series, such as an ACS355, ACS550, or ACH550.
- Differences in factory installed macro variants or regional market software packages shown in parameter
3302 FIRMWARE PACKAGE. - Attempting to write an incomplete or partially corrupted parameter backup set from a shared control panel.
Step-by-Step Troubleshooting and Solutions
- Navigate to parameter group
33 INFORMATIONon both source and destination drives and compare parameter3301 FIRMWARE VERSION, parameter3302 FIRMWARE PACKAGE, and parameter3304 DRIVE RATING. - Verify that the physical model codes on the drive rating labels match in input voltage, ampere rating, and frame dimensions.
- If cloning between different firmware releases, use ABB DriveWindow Light on a PC to perform a selective parameter download rather than a full monolithic image restore.
- Ensure parameter
1602 PARAMETER LOCKis set to1 (OPEN)on the target drive to permit parameter updates. - If hardware ratings differ, program the destination drive manually using the motor nameplate ratings entered under parameter group
99 START-UP DATA.
Preventative Maintenance to Avoid A5087 Faults
Maintain an accurate drive fleet register detailing firmware builds and kilowatt ratings, standardize firmware across equipment upgrades, and clearly label backup panels with their matching drive series and power rating.
Frequently Asked Questions (FAQs)
What is the meaning of A5087 alarm in ABB ACS310 drive?
It is a parameter cloning warning indicating that the configuration file being downloaded is incompatible with the destination drive hardware or firmware.
What are the primary causes of A5087 alarm?
The primary causes are firmware version discrepancies, mismatched motor power ratings, differing drive frame sizes, and cross-model cloning attempts.
How do I troubleshoot and correct A5087 alarm?
Compare group 33 information parameters across both drives, ensure model ratings match identically, or configure parameters manually using commissioning software.