F0035 fault in ABB ACS310 drive

Home/ABB/ABB ACS310 drive/F0035 fault in ABB ACS310 drive

The F0035 fault on an ABB ACS310 indicates an incorrect wiring configuration where incoming AC mains power has been connected to the drive’s output terminals. The drive triggers an emergency lockout to protect internal power semiconductors from destruction.

Connecting utility AC line power directly to motor output terminals U2, V2, W2 poses an extreme electrical hazard. The incoming grid potential bypasses the diode rectifier and directly energizes the freewheeling diodes across the output IGBT bridge. The resulting back-feed generates immediate DC link overvoltage and threatens destructive semiconductor short-circuits. Additionally, this fault can be falsely declared if the drive is operated on an ungrounded delta system with excessive motor cable ground capacitance, triggering false internal diagnostic leakage currents.

What Causes F0035 in ABB ACS310?

  1. Mains input lines incorrectly wired to motor output terminals U2, V2, W2 instead of L1, L2, L3.
  2. Motor cables mistakenly landed on line input power terminals L1, L2, L3.
  3. High parasitic cable-to-ground capacitance on exceptionally long, unshielded output motor cable runs.
  4. Operation on an ungrounded (IT) or corner-grounded delta power supply without removing the internal EMC filter screw.
  5. Internal power board failure or damaged IGBT bridge output current sensing circuit.

Step-by-Step Troubleshooting and Solutions

  1. Isolate all power and physically trace the incoming line feed to ensure it connects strictly to terminals L1, L2, L3.
  2. Verify that the three-phase motor leads terminate exclusively at drive output terminals U2, V2, W2.
  3. If operating on an ungrounded IT or corner-grounded network, verify that internal EMC filter screws (EMC and VAR) are disconnected.
  4. For long motor cable runs exceeding 30 m (shielded) or 50 m (unshielded), install an output du/dt reactor to reduce capacitive leakage.
  5. Perform a diode check across the IGBT power terminals using a digital multimeter to verify the output bridge is intact.

Preventative Maintenance to Avoid F0035 Faults

Clearly label power line and motor output cables during installation, double-check electrical schematics before initial power-up, and disconnect drive output terminals before conducting any high-voltage electrical insulation tests.

Frequently Asked Questions (FAQs)

What is the meaning of F0035 fault in ABB ACS310 drive?

The F0035 fault indicates that the drive detected mains input power landed on output terminals or excessive ground leakage capacitance.

What are the primary causes of F0035 fault?

It is mainly caused by swapped input and output power wiring, long motor cables on delta systems, or failed output semiconductors.

How do I troubleshoot and correct F0035 fault?

Verify line connections at terminals L1, L2, L3 and motor leads at U2, V2, W2, and verify EMC filter grounding screws.