The F1013 fault on the ABB ACS310 indicates a mismatch between the total number of PFC motors configured and the relays allocated for motor staging and autochange. The drive blocks execution to protect multi-pump hydraulic networks from erratic staging commands.
In advanced PFC configurations, parameter 8127 MOTORS defines the complete cluster of motors (both the speed-regulated lead pump and direct-on-line lag pumps). When autochange is activated in parameter 8118 AUTOCHNG INTERV, the drive rotates the VFD connection among all pumps in the cluster, requiring two contactors and dedicated relay control for each motor. If the total motor count in parameter 8127 does not precisely match the relay outputs assigned in parameter group 14 RELAY OUTPUTS and autochange logic, the firmware encounters an unresolvable routing matrix. The ACS310 issues fault F1013, suppressing inverter gate pulses to prevent electrical short-circuits between contactors.
What Causes F1013 in ABB ACS310?
- Value in parameter
8127 MOTORSdoes not match the count of PFC-assigned relays in group14. - Autochange enabled in parameter
8118with fewer physical relays configured than required for full motor alternation. - Parameter
8127set to an invalid number of motors relative to available physical hardware outputs. - Mismatched parameter migration from a larger multi-pump panel to a drive with fewer relay channels.
- Inadvertently modifying parameter
1401,1402,1403, or1410away fromPFCto a general status function.
Step-by-Step Troubleshooting and Solutions
- Review parameter
8127 MOTORSand confirm the exact number of pumps present in the physical multi-pump manifold. - Examine parameters
1401,1402,1403, and1410to verify that each staged motor corresponds to a relay configured as31 (PFC). - If parameter
8118 AUTOCHNG INTERVis active, ensure the relay configuration supports the full autochange matrix. - Confirm that an MREL-01 module is installed and recognized if the system controls more than one auxiliary motor.
- Reset parameter
8127 MOTORSto match the actual available PFC relay outputs and cycle power to clear the fault.
Preventative Maintenance to Avoid F1013 Faults
Verify multi-pump control logic during routine station audits, check interposing contactor coils for transient surge suppressors, and document pump staging matrices in electrical maintenance records.
Frequently Asked Questions (FAQs)
What is the meaning of F1013 fault in ABB ACS310 drive?
The F1013 fault indicates that the total number of PFC motors set in parameter 8127 does not match the relay outputs configured in group 14.
What are the primary causes of F1013 fault?
It is caused by a mathematical discrepancy between parameter 8127 MOTORS, group 14 PFC relay allocations, and autochange settings in parameter 8118.
How do I troubleshoot and correct F1013 fault?
Adjust parameter 8127 to match the actual number of assigned PFC relays in group 14, or configure additional relays for PFC.