The F1017 PAR SETUP 1 fault on the ABB ACS310 drive indicates an illegal input/output configuration where both the frequency input signal and the frequency output signal have been activated simultaneously. The drive trips to prevent internal hardware timer resource collisions.
In the ACS310 control architecture, digital input DI5 can be configured as a high-speed pulse train frequency input, while the transistor output on terminals 16 (TRANSISTOR OUTPUT) and 17 (TRANSISTOR OUTPUT GND) can be operated as a high-speed pulse train frequency output. Because both functions share internal hardware timers and interrupt lines on the control microcontroller, the drive firmware strictly prohibits their concurrent use. If both are enabled, the drive immediately aborts operation and blocks IGBT gate pulses, protecting the intermediate DC circuit and motor from erratic reference calculations.
What Causes F1017 in ABB ACS310?
- Configuring transistor output parameter
1804 TO MODEto frequency mode while an external reference in Group11 REFERENCE SELECTis assigned to frequency input (DI5). - Enabling frequency input on
DI5for process PID feedback in Group40,41, or42while parameter1804 TO MODEis set to frequency. - Attempting to output an actual speed pulse train on terminal
16while receiving a pulse reference from a flowmeter on terminalDI5. - Downloading an application macro or cloned configuration from another drive that contained conflicting timer assignments.
- Serial fieldbus write commands over embedded Modbus RTU at terminal
X1Csetting mutually exclusive pulse modes.
Step-by-Step Troubleshooting and Solutions
- Determine whether frequency input on terminal
DI5or pulse output on terminal16is the essential function for the system. - If frequency output is not mandatory, open parameter
1804 TO MODEand change the setting to0 (DIGITAL). - If frequency output is required, reassign reference inputs in parameter
1103 REF1 SELECTor1106 REF2 SELECTfrom frequency input to analog inputAI1orAI2. - Inspect Group
40 PROCESS PID SET 1, Group41 PROCESS PID SET 2, and Group42 EXT / TRIM PID; reassign any setpoint or feedback mapped to frequency input. - Once the hardware timer conflict is removed, press the RESET key on the control panel or power cycle the drive to clear the trip.
Preventative Maintenance to Avoid F1017 Faults
Standardize I/O wiring and parameter allocation schematics during panel design. When flowmeters or supervisory PLCs require pulse communication, utilize analog outputs (terminals AO) for telemetry if digital input DI5 must be dedicated to pulse frequency inputs.
Frequently Asked Questions (FAQs)
What is the meaning of F1017 fault in ABB ACS310 drive?
It indicates that the drive has been configured to use the pulsed frequency input and pulsed frequency output simultaneously, which is prohibited by hardware constraints.
What are the primary causes of F1017 fault?
The primary causes are setting parameter 1804 to frequency output mode while digital input DI5 is simultaneously assigned as a frequency reference or PID feedback source.
How do I troubleshoot and correct F1017 fault?
Change parameter 1804 to digital mode to disable the frequency output, or reassign the speed reference and PID feedback away from the frequency input to analog channels.