The A2003 alarm indicates that the ABB ACS355 DC undervoltage controller is active due to low intermediate circuit DC voltage. The drive automatically decreases motor torque and speed output to maintain DC bus voltage above the trip cutoff limit.
When the main AC supply sags or drops momentarily, the intermediate DC capacitor bank discharges rapidly. The ACS355 supervisory controller activates the undervoltage regulation routine by lowering output frequency and limiting inverter IGBT switching duty cycles. This dynamic reaction prevents immediate fault lockouts, giving the facility line supply time to recover before hardware shutdown occurs.
What Causes A2003 in ABB ACS355?
- Incoming AC supply phase missing, loose power feed, or blown upstream branch circuit fuse.
- Severe utility voltage sag, brownout conditions, or inadequate supply transformer kVA capacity.
- Degraded or worn DC link filter capacitors unable to retain intermediate circuit charge.
- Faulty input bridge rectifier diodes causing unbalanced half-wave DC ripple.
- Internal charging circuit or pre-charge relay contacts failing to close firmly during power application.
Step-by-Step Troubleshooting and Solutions
- Measure phase-to-phase and phase-to-neutral incoming AC voltage at input terminals
U1, V1, W1(orL, N) under run conditions. - Inspect all upstream line disconnect switches, circuit breakers, and main supply fuses for high contact resistance or loose clamping.
- Check parameter
2006 UNDERVOLT CTRLto ensure the undervoltage control function is enabled for transient ride-through capability. - Measure the DC bus voltage directly across terminals
BRK+andUDC-to confirm adequate rectified DC voltage levels. - Inspect incoming supply wiring sizing and line reactors to confirm voltage drop under full load does not drop below
-15%of rating.
Preventative Maintenance to Avoid A2003 Faults
Periodically clean and torque all input line feeder connections, conduct annual power quality audits to monitor harmonic distortion and voltage sags, and replace aged drives operating past their DC capacitor lifespan.
Frequently Asked Questions (FAQs)
What is the meaning of A2003 fault in ABB ACS355 drive?
It warns that the DC intermediate circuit voltage has fallen below operational parameters, forcing the drive to restrict motor power consumption.
What are the primary causes of A2003 fault?
Common causes include missing input phases, low mains line voltage, blown upstream branch fuses, or defective input rectifier components.
How do I troubleshoot and correct A2003 fault?
Verify incoming mains voltage across all phases, inspect disconnect contacts, check DC bus levels, and confirm parameter 2006 is activated.