A2005 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2005 alarm in ABB ACS355 drive

The A2005 alarm indicates an active fieldbus communication break between the drive interface and the master controller. The internal protection mechanism triggers based on supervision timeout thresholds to alert operators before uncommanded speed loss or safety hazards occur.

When the ACS355 detects missing cyclic telegrams via embedded Modbus RTU or an optional fieldbus adapter module (such as FPBA-01 or FCAN-01), communication supervision timers elapse. If parameter 3018 COMM FAULT FUNC is configured to generate an alarm rather than an immediate inverter trip, the microprocessor maintains pulse-width modulation (PWM) while operating under predefined fallback conditions (such as maintaining last speed or applying preset speeds) instead of clamping the intermediate DC bus or locking the IGBT gate drivers.

What Causes A2005 in ABB ACS355?

  1. Physical disconnection, loose terminal screws, or cut RS-485 serial wiring on terminals 29 (B+), 30 (A-), or 31 (AGND).
  2. PLC or master network controller switched to stop mode, rebooting, or experiencing bus cycle execution faults.
  3. Incorrect baud rate, node address, or parity configuration in parameter group 53 EFB PROTOCOL or group 51 EXT COMM MODULE.
  4. High electromagnetic interference (EMI) corrupting communication packets due to unshielded fieldbus cabling routed adjacent to motor power lines.
  5. Missing or improperly engaged 120 Ω termination resistors at the end nodes of the serial link.

Step-by-Step Troubleshooting and Solutions

  1. Inspect fieldbus indicator LEDs on the drive control board or fieldbus module to verify physical layer link and network activity.
  2. Verify serial transmission parameters in group 53 (e.g., parameter 5302 EFB STATION ID and 5303 EFB BAUD RATE) against master PLC network settings.
  3. Measure DC resistance across communication terminals 29 and 30 with line power isolated; verify termination network equals approximately 60 Ω (two 120 Ω resistors in parallel).
  4. Check communication loss handling defined in parameter 3018 COMM FAULT FUNC and verify timeout delay setting in parameter 3019 COMM FAULT TIME.
  5. Confirm proper grounding and screening of serial communication cables, ensuring 360-degree clamp grounding at the drive gland plate to suppress noise coupling.

Preventative Maintenance to Avoid A2005 Faults

Routinely inspect network wiring for terminal tightness, ensure fieldbus cables remain segregated from high-voltage U1, V1, W1 input and U2, V2, W2 motor leads by at least 200 mm, and verify that PLC watchdog communication routines are tested during scheduled downtime.

Frequently Asked Questions (FAQs)

What is the meaning of A2005 fault in ABB ACS355 drive?

It represents an active communication timeout alarm indicating the drive has lost data transmission contact with the supervisory fieldbus controller.

What are the primary causes of A2005 fault?

Primary root causes include damaged fieldbus cabling, an offline master PLC, incorrect serial communication parameters, or severe EMI noise corruption.

How do I troubleshoot and correct A2005 fault?

Check the communication cable continuity, align parameter group 53 settings with your PLC, and ensure termination resistors are properly switched on.