The A2013 alarm indicates that the ABB ACS355 drive has initiated an automatic fault reset sequence. This informative alarm confirms that an active trip has occurred and the drive is attempting to restore normal operation autonomously without manual input.
During an autoreset interval, the drive suppresses standard persistent lockout routines and counts consecutive retry attempts within a predetermined timing window. The intermediate DC bus capacitors and gating logic remain prepared for re-energization while the motor coasts or prepares for flying start reconnection, ensuring unmonitored systems recover from transient supply or load dips.
What Causes A2013 in ABB ACS355?
- Transient AC line undervoltage or overvoltage spikes triggering auto-reset recovery.
- Momentary motor overcurrent trips occurring during heavy conveyor or compressor restarts.
- Loss of analog reference signals at control terminal
AI1orAI2with auto-reset enabled. - Active configuration of automatic restart parameters in Group
31 AUTOMATIC RESET. - External fault signals toggling intermittently across programmable digital inputs
DI1throughDI5.
Step-by-Step Troubleshooting and Solutions
- Review the fault history log in parameter Group
04 FAULT HISTORYto identify the underlying trip that triggered autoreset. - Review the allowed trial count in parameter
3101 NUMBER OF TRIALSand total trial duration in3102 TRIAL TIME. - Check delay interval in parameter
3103 DELAY TIMEto ensure sufficient motor demagnetization before restarting. - Verify specific enable parameters such as
3104 AR OVERCURRENTand3105 AR OVERVOLTAGEto isolate automated actions. - Inspect incoming three-phase supply lines on terminals
U1, V1, W1using a power quality logger to detect transient brownouts.
Preventative Maintenance to Avoid A2013 Faults
Audit electrical supply stability, install line reactors or surge suppression on fluctuating plant grids, and periodically clear drive historical logs to accurately monitor transient fault frequency.
Frequently Asked Questions (FAQs)
What is the meaning of A2013 fault in ABB ACS355 drive?
The A2013 alarm indicates that the drive has engaged its automatic reset function following a temporary trip condition.
What are the primary causes of A2013 fault?
It is caused by transient electrical disturbances like line sags, momentary overcurrent spikes, or intermittent analog reference dropouts.
How do I troubleshoot and correct A2013 fault?
Examine the fault log in Group 04 to identify the initial fault cause and evaluate retry parameters in Group 31.