The A2022 alarm warns that the ABB ACS355 drive has detected an active start command while the secondary hardware or software Start Enable 2 interlock signal is missing. This holds the motor modulation system in a safe disabled state, suppressing torque output until the input condition is satisfied.
Dual enable architectures are commonly deployed in automated work cells to guarantee redundant safety before current is applied to the stator windings. The internal microprocessor checks the status assigned in parameter 1609 (START ENABLE 2) against the specified physical terminal (such as DI2 through DI5) or communication word. Until this circuit delivers a stable +24V DC high logic state, PWM firing pulses to the output IGBT bridge remain blocked, preventing motor rotation while maintaining DC bus readiness.
What Causes A2022 in ABB ACS355?
- The digital input defined in parameter
1609(START ENABLE 2) is physically disconnected, loose, or broken. - A secondary process interlock, such as a lube oil pressure switch, cooling fan contactor, or guard switch, is open.
- Incorrect assignment of parameter
1609pointing to a digital input terminal that is not wired or energised. - Auxiliary
+24V DCcontrol power circuit fault, blown external fuse, or open return line at terminalDCOM. - Missing communication enable word or communication timeout over the embedded fieldbus (Modbus RTU) network.
Step-by-Step Troubleshooting and Solutions
- Check parameter
1609(START ENABLE 2) via the operator keypad to identify which input (e.g.,DI1–DI5orCOMM) is assigned. - Measure the voltage across the designated digital input terminal and terminal
DCOMwith a multimeter to confirm+24V DCpresence. - Trace the physical wiring back to secondary auxiliary interlocks (e.g., pressure sensors, mechanical limit switches, interposing relays).
- If fieldbus control is utilized, inspect parameter group
53and confirm PLC communication words are actively driving the enable bit. - Check diagnostic parameter
0118(DI 5-1 STATUS) on the drive display to verify real-time digital logic transitions when switching the input.
Preventative Maintenance to Avoid A2022 Faults
Include secondary interlock circuits in your standard preventative maintenance schedule. Inspect auxiliary terminal block screws on terminal header X1 for correct tightness, test auxiliary limit switches for mechanical wear or contact oxidation, and ensure PLC communication watchdog timers are configured to handle network hiccups without intermittent tripping.
Frequently Asked Questions (FAQs)
What is the meaning of A2022 fault in ABB ACS355 drive?
The A2022 alarm indicates that the secondary Start Enable 2 permissive circuit is missing or open, preventing the drive from energizing the motor.
What are the primary causes of A2022 fault?
The most common causes are open auxiliary interlock contacts, loose field wiring on terminal strip X1, or improper configuration of parameter 1609.
How do I troubleshoot and correct A2022 fault?
Check parameter 1609 settings, measure 24V DC across the assigned digital input terminal, and ensure external permissive switches are closed.