The A2023 alarm indicates that the ABB ACS355 drive has received an active emergency stop command and is executing a controlled deceleration ramp to standstill. Inverter output frequency is actively forced to zero in accordance with parameter 2208 (EMERG DEC TIME) to ensure safe machine shutdown.
When the emergency stop input is triggered (configured in parameter 2109), the drive overrides active speed references and forces the IGBT switching pattern into a rapid deceleration profile. The kinetic energy generated by the stopping motor is transferred back into the intermediate DC circuit, causing the DC bus voltage to rise sharply. If the ramp time set in parameter 2208 is exceptionally aggressive, an optional dynamic braking resistor connected across terminals BRK+ and BRK- absorbs this regenerative energy to prevent a secondary F0002 DC overvoltage trip.
What Causes A2023 in ABB ACS355?
- An external Emergency Stop mushroom push button wired to a digital input terminal (such as
DI4orDI5) has been depressed. - An upstream safety relay, light curtain, or emergency interlock circuit has tripped or lost control power.
- Fieldbus command word bit
0or2was cleared by the supervisory PLC, triggering a network emergency stop command. - Parameter
2109(EMERG STOP SEL) is incorrectly assigned to an open or normally closed contact circuit. - Broken, loose, or severed control wiring between the e-stop push button and control terminal strip
X1.
Step-by-Step Troubleshooting and Solutions
- Verify that the physical machinery is safe, unjammed, and clear of personnel before taking any corrective operational action.
- Locate and reset the depressed emergency stop push button by twisting or pulling it back to its healthy, normally closed position.
- Inspect parameter
2109(EMERG STOP SEL) to verify whether the input logic expects an active-high or active-low (e.g.,DI4(INV)) signal. - Measure voltage at the designated digital input terminal with a multimeter to confirm that a solid
+24V DCsignal returns upon release. - If the drive trips on overvoltage during deceleration, increase parameter
2208(EMERG DEC TIME) or verify braking resistor continuity at terminalsBRK+andBRK-.
Preventative Maintenance to Avoid A2023 Faults
Regularly test all hardwired emergency stop push buttons and safety trip cords to guarantee contacts snap cleanly without excessive electrical resistance. Perform routine ohmic checks on external dynamic braking resistors and inspect terminal screws on X1 and safety relays to eliminate nuisance emergency stop interruptions caused by mechanical vibration.
Frequently Asked Questions (FAQs)
What is the meaning of A2023 fault in ABB ACS355 drive?
The A2023 alarm indicates that the drive has initiated an emergency stop ramp and is decelerating the motor to a complete standstill.
What are the primary causes of A2023 fault?
This alarm is caused by an activated emergency stop push button, open safety circuit contact, or an emergency command received over fieldbus.
How do I troubleshoot and correct A2023 fault?
Confirm operator safety, release and reset the emergency stop button, check 24V DC wiring at the assigned terminal, and resume operation.