A2029 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2029 alarm in ABB ACS355 drive

The A2029 alarm warns that a permanent magnet synchronous motor is spinning when a start command is issued using DC magnetization mode. The ABB ACS355 issues this alarm because a spinning permanent magnet rotor cannot be aligned using stationary DC current.

Permanent magnet motors generate back electromotive force (EMF) proportionally to rotational speed. When parameter 2101 START FUNCTION is set to DC magnetization, the inverter injects stationary direct current into the stator to establish rotor alignment. If the shaft is already freewheeling, this stationary magnetic field clashes against the spinning rotor magnets, creating current surges, erratic braking torque, and DC bus overvoltage regeneration.

What Causes A2029 in ABB ACS355?

  1. Permanent magnet motor freewheeling or windmilling due to duct draft or process flow during a start request.
  2. Parameter 2101 START FUNCTION configured to 2 (DC MAGN) instead of dynamic flying start mode.
  3. Rapid start cycling before the motor shaft has reached a full standstill after a coast-stop command.
  4. Unbalanced external process forces or back-driving gravity loads turning the motor shaft without an engaged mechanical brake.
  5. Inaccurate motor configuration under parameter 9903 MOTOR TYPE setting for permanent magnet machinery.

Step-by-Step Troubleshooting and Solutions

  1. Reconfigure parameter 2101 START FUNCTION to 1 (AUTO) to enable dynamic flying start capability on spinning rotors.
  2. Allow the motor to come to a complete mechanical standstill before reasserting the external start command.
  3. Install mechanical backstops or verify that the external electro-mechanical holding brake engages whenever the drive is disabled.
  4. Verify that parameter 9903 MOTOR TYPE is correctly defined as 2 (PMSM) with accurate back EMF data in group 99.
  5. Check parameter 2102 STOP FUNCTION to evaluate whether ramp-down braking rather than coasting prevents process windmilling.

Preventative Maintenance to Avoid A2029 Faults

Ensure fan damper controls prevent reverse mechanical windmilling, audit motor brake friction pads for wear, and review application parameter groups whenever drive firmware or process duty cycles are updated.

Frequently Asked Questions (FAQs)

What is the meaning of A2029 fault in ABB ACS355 drive?

It indicates that a permanent magnet motor is rotating while the drive is attempting to apply stationary DC magnetization at start.

What are the primary causes of A2029 fault?

This condition happens when a spinning motor receives a start command while parameter 2101 is configured for static DC magnetization.

How do I troubleshoot and correct A2029 fault?

Set start mode to auto in parameter 2101, ensure the motor has stopped spinning before starting, or install anti-windmilling dampers.