A2035 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A2035 alarm in ABB ACS355 drive

The A2035 alarm indicates that the integrated Safe Torque Off (STO) safety circuit has been triggered and is operating normally. The ABB ACS355 activates this status alarm when an external safety device opens the dual-channel STO circuit while parameter 3025 is programmed to react with an alarm.

The ACS355 STO circuit operates via hardware-level interlocks that remove control gate power from the inverter output IGBTs. This direct hardware action guarantees that the drive output cannot generate rotational torque, achieving an electrically safe stop without opening main line power contactors. If the safety circuit opens while the drive is running, modulation ceases immediately, causing the motor shaft to coast to a stop.

What Causes A2035 in ABB ACS355?

  1. Actuation of an emergency stop pushbutton, safety gate interlock, or optical light curtain.
  2. Loss of 24V DC excitation on safety input terminals IN1 or IN2 on terminal block X1C.
  3. Tripped safety relay or auxiliary contact disconnection in the external machine safety circuit.
  4. Parameter 3025 STO OPERATION programmed to react with 1 (ONLY ALARM) or 2 (ALARM&FAULT).
  5. Channel discrepancy or timing delay exceeding 200 ms between dual safety channels IN1 and IN2.

Step-by-Step Troubleshooting and Solutions

  1. Verify that physical emergency stop buttons and safety barrier switches are closed and reset.
  2. Measure DC voltage across terminal OUT and terminals IN1 and IN2 on safety terminal block X1C (must read 24V DC).
  3. Toggle the external start signal to low (transition from 1 to 0) to reset the drive run interlock.
  4. Inspect safety circuit jumper links on terminal block X1C if the application does not deploy external safety hardware.
  5. Configure parameter 3025 STO OPERATION to match application safety specifications for alarm or fault messaging.

Preventative Maintenance to Avoid A2035 Faults

Conduct proof testing on safety switches and terminal block X1C wiring every six to twelve months, verify dual-channel synchronization, and ensure control cables are shielded against stray electromagnetic interference.

Frequently Asked Questions (FAQs)

What is the meaning of A2035 fault in ABB ACS355 drive?

It indicates that the Safe Torque Off safety function has engaged and disabled inverter firing to safely eliminate motor torque.

What are the primary causes of A2035 fault?

This alarm is triggered by pressed emergency stops, tripped safety interlocks, open circuits on terminal X1C, or parameter 3025 settings.

How do I troubleshoot and correct A2035 fault?

Inspect safety devices, verify 24V DC on terminals IN1 and IN2, toggle the run signal low to high, and adjust parameter 3025 if needed.