The A5014 alarm occurs when local panel control is disabled on the ABB ACS355 drive due to an unacknowledged active drive fault trip. The control panel prevents switching to local operation until the root fault condition is reset.
During an active drive trip, the internal control logic inhibits inverter pulse-width modulation and blocks gate pulses to the output IGBTs. While the intermediate DC link remains charged, firmware security protocols disallow manual start, stop, or reference changes via the keypad, protecting downstream mechanical equipment from uncontrolled restarting before system diagnostics are completed.
What Causes A5014 in ABB ACS355?
- An active, unreset hard fault condition (such as overcurrent or overvoltage) locking the drive core.
- Attempting to press the
LOC/REMbutton while an active trip is logged in the control panel. - Digital fault reset input configured in parameter
1604 FAULT RESET SELnot receiving a clear signal. - Loose or corroded communication ribbon cable connections between the drive base and control panel.
- Persistent external interlock trips active across programmable digital inputs
DI1throughDI5.
Step-by-Step Troubleshooting and Solutions
- Identify the primary active trip code by accessing parameter Group
04 FAULT HISTORYvia the keypad. - Clear the primary trip condition and press the keypad
RESETkey or cycle power to clear active lockouts. - Check the wiring of reset circuits on terminal block
X1Aand verify digital input status in parameter0110 DI 5-1 STATUS. - Perform a
500V DCinsulation megger test across motor terminalsU2, V2, W2to rule out motor short circuits causing repeated trips. - Unseat and firmly reseat the keypad panel to verify proper physical contact with the drive interface cradle.
Preventative Maintenance to Avoid A5014 Faults
Perform routine checks on fault history records, maintain clean electrical connections on control terminal blocks, and ensure proper remote reset signal timing to avoid keypad lockout states.
Frequently Asked Questions (FAQs)
What is the meaning of A5014 fault in ABB ACS355 drive?
The A5014 alarm signifies that keypad control is temporarily locked out because the drive has an active, uncleared fault.
What are the primary causes of A5014 fault?
Primary causes include unresolved internal drive trips, attempts to enter local mode during active errors, and disconnected fault reset wiring.
How do I troubleshoot and correct A5014 fault?
Inspect parameter Group 04 to diagnose the primary fault, correct the physical problem, and execute a drive fault reset.