The A5018 alarm indicates that the ABB ACS355 drive cannot locate default parameter tables in its internal non-volatile memory. This critical warning flags corrupted firmware sectors or defective memory blocks inside the main control board.
Without access to default parameter maps, the drive microprocessor cannot safely determine hardware current limits, base PWM switching frequencies, or IGBT dead-time compensation. The inverter modulation remains strictly disabled or restricted to safe states to protect internal electronics and avoid uncontrolled power delivery to connected AC induction motors.
What Causes A5018 in ABB ACS355?
- Corrupted EEPROM or internal flash memory holding factory default tables.
- Interrupted power supply during a firmware upgrade or factory parameter restoration.
- Firmware version mismatch following a control panel replacement or memory module swap.
- Severe electrical fast transients (EFT) corrupting digital memory registers on the control board.
- Physical hardware degradation of internal memory chips caused by prolonged excessive heat.
Step-by-Step Troubleshooting and Solutions
- Cycle main input power across supply terminals
U1, V1, W1and allow the DC bus capacitors to discharge fully before restarting. - Attempt a complete factory macro reset by navigating to parameter
9902 APPLIC MACROand reloading the default macro. - Verify control board voltage levels using a multimeter across terminal block
X1A(terminals+24VandGND). - If memory corruption persists, reflash the drive firmware using ABB DriveWindow Light or the appropriate flash tool.
- Replace the control board or the complete ACS355 drive assembly if the flash memory hardware has failed permanently.
Preventative Maintenance to Avoid A5018 Faults
Maintain consistent operating temperatures inside electrical enclosures, protect drives with input line surge suppressors, and avoid interrupting control power during parameter transfers or firmware writes.
Frequently Asked Questions (FAQs)
What is the meaning of A5018 fault in ABB ACS355 drive?
The A5018 alarm indicates that the drive’s processor cannot locate or load the factory default parameter table from internal memory.
What are the primary causes of A5018 fault?
This fault is caused by corrupted flash memory sectors, interrupted firmware flash procedures, or physical control board component failure.
How do I troubleshoot and correct A5018 fault?
Perform a full power cycle, reload factory defaults via parameter 9902, and replace the control unit if memory corruption remains.