A5050 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A5050 alarm in ABB ACS355 drive

The A5050 alarm indicates that a parameter upload sequence from the ABB ACS355 drive to the control panel was prematurely aborted. This event is triggered when communication between the drive processor and the keypad memory is interrupted.

While an upload abort occurs, active inverter pulse-width modulation and motor control routines remain unaffected if the drive is already running. However, the temporary memory buffer is discarded by the internal microprocessor, preventing incomplete or damaged parameter groups from being saved into the non-volatile memory partition of the control keypad.

What Causes A5050 in ABB ACS355?

  1. Manual user cancellation caused by pressing the BACK or EXIT key on the control panel during transfer.
  2. Physical movement or vibration dislodging the control panel from its mounting bezel.
  3. Transient electrical noise interfering with panel serial communication lines on terminal block X1.
  4. Momentary drop in the internal +24V DC auxiliary power supply during the data transfer.
  5. A concurrent start or stop command interrupting background serial communication tasks.

Step-by-Step Troubleshooting and Solutions

  1. Re-mount the control panel firmly into the front bezel of the ACS355 drive and ensure the retaining latch snaps into place.
  2. Restart the parameter upload sequence via the control panel utility menu and refrain from pressing keypad buttons during transfer.
  3. Clean serial contact pins on the drive interface cradle with electrical contact cleaner to remove dust or oxidation.
  4. Measure auxiliary DC control voltage across terminals +24V and GND to confirm a steady 24V DC (±10%) level.
  5. If uploading over a PC connection, verify that the OPCA-02 serial cable is securely screwed down and grounded.

Preventative Maintenance to Avoid A5050 Faults

Ensure drive panels installed on high-vibration equipment are secured using remote mounting kits, maintain clean enclosure environments, and instruct operators not to press keypad buttons during memory transfer procedures.

Frequently Asked Questions (FAQs)

What is the meaning of A5050 fault in ABB ACS355 drive?

The A5050 alarm indicates that an ongoing parameter upload from the drive to the control panel was canceled or unexpectedly aborted.

What are the primary causes of A5050 fault?

Primary causes are pressing the cancel key during transfer, loose keypad mechanical seating, or momentary serial communication loss.

How do I troubleshoot and correct A5050 fault?

Firmly reseat the control panel, ensure auxiliary voltage is stable, and initiate the parameter upload procedure again without interruption.