A5087 alarm in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/A5087 alarm in ABB ACS355 drive

The A5087 alarm indicates that a parameter download from the source file to the destination drive has failed due to incompatible parameter sets. The drive halts the transfer process to protect against applying mismatched motor ratings or invalid hardware control logic.

During the parameter restoration routine, the ACS355 bootloader interrogates configuration headers against internal drive identification tables in group 33 INFORMATION. If the source file was archived from a drive with a different power rating, voltage class, or physical frame size (such as copying from an R1 frame to an R3 frame), the CPU detects incompatible voltage-to-frequency scaling and thermal model constraints. Pulse-width modulation (PWM) remains inhibited and IGBT gate drivers are locked out, leaving the DC bus in standby until a compatible configuration set is supplied.

What Causes A5087 in ABB ACS355?

  1. Cloning a parameter backup from a drive with a different nominal power rating or voltage class (e.g., parameter 3303 DRIVE RATING mismatch).
  2. Attempting to download parameter structures across differing physical frame sizes (e.g., parameter 3304 FRAME SIZE differs between source and target).
  3. Firmware package discrepancies between the original upload drive and the destination unit in parameter 3301 FIRMWARE VERSION.
  4. Incompatible application macro configurations or custom scalar/vector settings stored in parameter 9902 APPLIC MACRO.
  5. Attempting to apply an ACS550 or legacy ACS350 backup file directly to an ACS355 control board.

Step-by-Step Troubleshooting and Solutions

  1. Compare parameter group 33 INFORMATION on both the source and target drives; specifically inspect parameters 3301 FIRMWARE VERSION, 3303 DRIVE RATING, and 3304 FRAME SIZE.
  2. If the destination drive has a different frame size, perform a partial parameter restore via DriveWindow Light PC software, transferring only application groups (e.g., groups 10 through 50) while excluding motor start-up data.
  3. Confirm that the motor connected to terminals U2, V2, W2 matches the target drive power rating before entering nameplate values into group 99 START-UP DATA.
  4. Reset the destination drive to factory defaults by loading the standard macro through parameter 9902 APPLIC MACRO (setting to 1 = ABB STANDARD) before downloading.
  5. Execute a fresh upload from an identical reference drive sharing the exact same model designation and type code.

Preventative Maintenance to Avoid A5087 Faults

Standardize spare drive frame ratings across production lines, label backup control panels with the specific drive model code and firmware revision, and use DriveWindow Light software to maintain version-controlled parameter archives on an engineering server.

Frequently Asked Questions (FAQs)

What is the meaning of A5087 fault in ABB ACS355 drive?

It is a parameter download alarm indicating that the incoming configuration file was created for a drive with incompatible power, voltage, or frame specifications.

What are the primary causes of A5087 fault?

The main causes are frame size mismatches, differing drive power ratings, mismatched firmware versions in Group 33, or cross-platform parameter cloning.

How do I troubleshoot and correct A5087 fault?

Verify that parameters in Group 33 match between both drives, reload factory defaults via parameter 9902, or download only application parameters using PC software.