The F0021 fault indicates an internal hardware failure where the drive output phase current measurement circuitry is reading out of permissible operational range. The drive trips instantly to prevent uncontrolled current surges from destroying the output inverter stage.
During start-up self-tests and continuous PWM modulation, the ACS355 samples phase currents across low-inductance shunt resistors or Hall-effect transducers connected to output terminals U2, V2, W2. Before firing the IGBT gates, the CPU performs an automatic zero-offset current calibration. If the detected offset exceeds tolerance limits or amplifier signals clip outside dynamic range, the central processor detects a sensor failure and locks all gate driver pulses, isolating intermediate DC bus energy from the motor.
What Causes F0021 in ABB ACS355?
- Defective internal current-sensing transducer, shunt resistor, or operational amplifier on the power output board.
- Failure of internal zero-offset calibration during the drive power-up initialization sequence.
- Severe phase-to-phase or phase-to-ground short circuit on motor cabling that damaged internal measurement circuits.
- Moisture, metallic dust, or corrosive chemical contamination bridging signal traces around the current sensing ASICs.
- Damaged gate driver circuitry or asymmetric IGBT leakage distorting phase current measurement channels.
Step-by-Step Troubleshooting and Solutions
- Disconnect all motor leads from output terminals
U2, V2, W2to rule out external load influences and reset the drive. - Perform a motor and cable insulation test using a
500 VDCmegohmmeter (with drive leads disconnected) to ensure winding insulation resistance exceeds1 MΩ. - Check if the drive trips on
F0021immediately upon power application with no run command active; an instant trip without run signals confirms an internal hardware defect. - Inspect the output terminal assembly for signs of mechanical overheating, carbon tracking, or loose hardware.
- If
F0021persists with the motor completely disconnected, the internal current-sensing hardware has failed, requiring professional drive repair or unit replacement.
Preventative Maintenance to Avoid F0021 Faults
Ensure motor lead cables are shielded and clamped properly to eliminate high di/dt capacitive spikes, test motor winding insulation annually, and install line reactors or dV/dt output filters on motor cable runs exceeding 30 meters.
Frequently Asked Questions (FAQs)
What is the meaning of F0021 fault in ABB ACS355 drive?
It represents an internal hardware trip indicating that the output phase current measurement channels are out of calibration or reading out of range.
What are the primary causes of F0021 fault?
Primary causes include damaged internal current-sensing components, failed power-on offset calibration, severe external motor short circuits, or PCB contamination.
How do I troubleshoot and correct F0021 fault?
Disconnect motor cables from U2, V2, and W2 to test if the fault clears; if the trip occurs with no motor connected, replace the drive hardware.