F0022 fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F0022 fault in ABB ACS355 drive

The F0022 fault indicates that the intermediate DC circuit voltage is oscillating excessively due to a missing input line phase or blown line fuse. The drive trips when DC bus voltage ripple exceeds 14% of nominal DC voltage to protect input rectifiers and DC capacitors.

When one incoming AC phase is lost on terminals U1, V1, W1, the three-phase bridge rectifier collapses into single-phase rectification. Under motor load, the intermediate DC reservoir capacitors must discharge far more deeply between charging peaks, causing severe 100 Hz / 120 Hz voltage ripple. When ripple exceeds the 14% threshold, the ACS355 trips immediately. This protective shutdown preserves electrolytic capacitor lifespan, prevents input diode bridge thermal destruction, and prevents motor torque pulsations.

What Causes F0022 in ABB ACS355?

  1. Blown input line fuse or open branch circuit breaker pole on one incoming AC phase.
  2. Loose, corroded, or disconnected conductor on line input terminals U1, V1, or W1.
  3. Severe utility mains voltage unbalance (greater than 3% phase-to-phase voltage imbalance).
  4. Pitted, oxidized, or defective main contactor contacts failing to pass current on all three poles under load.
  5. Failed internal input rectifier diode or degraded DC link filter capacitor bank.

Step-by-Step Troubleshooting and Solutions

  1. Measure incoming three-phase AC voltages line-to-line across terminals U1-V1, V1-W1, and U1-W1 with a multimeter; verify balance within 2%.
  2. Inspect all upstream line fuses using an ohmmeter with power isolated; replace any open or high-resistance semiconductor fuses.
  3. Check input terminal screw torque on U1, V1, W1 to rule out loose electrical connections causing phase drops under load.
  4. Monitor parameter 0107 DC BUS VOLTAGE under load; verify DC potential remains stable at approximately 1.35 × VAC_in (e.g., 540 VDC for 400 VAC supply).
  5. Check parameter 3016 SUPPLY PHASE; verify that the phase loss supervision function is enabled and configured correctly for the facility power network.

Preventative Maintenance to Avoid F0022 Faults

Perform annual thermographic infrared surveys on input disconnect switches and contactors to identify high-resistance terminations, verify power line balance, and maintain clean, securely torqued terminal connections on incoming mains cables.

Frequently Asked Questions (FAQs)

What is the meaning of F0022 fault in ABB ACS355 drive?

It is a power supply protection fault indicating that excessive DC bus voltage ripple was detected due to a missing incoming AC power phase.

What are the primary causes of F0022 fault?

Common causes include a blown input line fuse, an open circuit breaker pole, severe utility supply imbalance, or a loose incoming wire on terminal U1, V1, or W1.

How do I troubleshoot and correct F0022 fault?

Measure input line-to-line voltages across terminals U1, V1, and W1, inspect all upstream fuses for continuity, and verify terminal screw tightness.