The F0044 fault indicates that the integrated Safe Torque Off (STO) safety circuit has been tripped and that parameter 3025 (STO OPERATION) is configured to post a latching fault. The drive immediately removes power from the motor output terminals to achieve a SIL3 / PL e certified safety stop.
The ACS355 STO function relies on dual redundant safety input channels wired through terminal block X1C (terminals OUT, IN1, IN2, and GND). When an emergency stop switch or safety relay opens either IN1 or IN2, internal optocouplers disconnect the gate driver power supply from the IGBT inverter bridge. Even if the microcontroller attempts to generate switching signals, physical torque generation is impossible. When parameter 3025 is set to 1 (FAULT), the drive latches F0044, requiring a deliberate reset after safety interlocks are restored.
What Causes F0044 in ABB ACS355?
- An external emergency stop push button, safety gate interlock, or safety light curtain has tripped the dual-channel STO loop.
- Broken, disconnected, or high-resistance wiring on safety terminal block
X1C(terminalsIN1orIN2). - Discrepancy or timing skew between safety channels
IN1andIN2exceeding the drive’s internal synchronism window. - Parameter
3025(STO OPERATION) is set to1(FAULT) or2(FAULT ALARM) instead of non-tripping alarm modes. - Failure of the external
+24V DCsafety relay power supply driving terminalsIN1andIN2.
Step-by-Step Troubleshooting and Solutions
- Confirm that the machinery emergency stop buttons are released, safety gates are closed, and the emergency zone is safe.
- Measure DC voltage across terminal
IN1toGNDand terminalIN2toGNDon headerX1C; verify both read a steady+24V DC. - Inspect terminal
OUT(auxiliary+24Vsource onX1C) for continuity if using internal power with factory safety jumpers. - Check parameter
3025(STO OPERATION) setting; change from1(FAULT) to3(ALARM) or4(NO REACTION) if an automatic restart upon safety circuit closing is desired. - After safety switches are closed and verified, press the
RESETsoftkey on the control panel or pulse digital inputDI1/DI2to clear the latching trip.
Preventative Maintenance to Avoid F0044 Faults
Test the full functional safety chain—including all safety switches, light curtains, and safety relay contacts—at least once per year as mandated by functional safety standards IEC 61508 / ISO 13849. Ensure terminal X1C screw clamps remain firmly torqued, and protect safety control wires from pinch points and mechanical abrasion.
Frequently Asked Questions (FAQs)
What is the meaning of F0044 fault in ABB ACS355 drive?
The F0044 fault indicates that the Safe Torque Off (STO) circuit was activated and the drive is programmed to register a latching fault.
What are the primary causes of F0044 fault?
The most common causes are pressed emergency stop buttons, open safety gate contacts, loose wiring on terminal X1C, or 24V supply drops.
How do I troubleshoot and correct F0044 fault?
Close and verify all external safety devices, measure 24V DC across STO terminals IN1 and IN2, and issue a fault reset on the control panel.