F0044 SAFE TORQUE OFF fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F0044 SAFE TORQUE OFF fault in ABB ACS355 drive

The F0044 fault indicates that the integrated Safe Torque Off (STO) safety circuit has been tripped and that parameter 3025 (STO OPERATION) is configured to post a latching fault. The drive immediately removes power from the motor output terminals to achieve a SIL3 / PL e certified safety stop.

The ACS355 STO function relies on dual redundant safety input channels wired through terminal block X1C (terminals OUT, IN1, IN2, and GND). When an emergency stop switch or safety relay opens either IN1 or IN2, internal optocouplers disconnect the gate driver power supply from the IGBT inverter bridge. Even if the microcontroller attempts to generate switching signals, physical torque generation is impossible. When parameter 3025 is set to 1 (FAULT), the drive latches F0044, requiring a deliberate reset after safety interlocks are restored.

What Causes F0044 in ABB ACS355?

  1. An external emergency stop push button, safety gate interlock, or safety light curtain has tripped the dual-channel STO loop.
  2. Broken, disconnected, or high-resistance wiring on safety terminal block X1C (terminals IN1 or IN2).
  3. Discrepancy or timing skew between safety channels IN1 and IN2 exceeding the drive’s internal synchronism window.
  4. Parameter 3025 (STO OPERATION) is set to 1 (FAULT) or 2 (FAULT ALARM) instead of non-tripping alarm modes.
  5. Failure of the external +24V DC safety relay power supply driving terminals IN1 and IN2.

Step-by-Step Troubleshooting and Solutions

  1. Confirm that the machinery emergency stop buttons are released, safety gates are closed, and the emergency zone is safe.
  2. Measure DC voltage across terminal IN1 to GND and terminal IN2 to GND on header X1C; verify both read a steady +24V DC.
  3. Inspect terminal OUT (auxiliary +24V source on X1C) for continuity if using internal power with factory safety jumpers.
  4. Check parameter 3025 (STO OPERATION) setting; change from 1 (FAULT) to 3 (ALARM) or 4 (NO REACTION) if an automatic restart upon safety circuit closing is desired.
  5. After safety switches are closed and verified, press the RESET softkey on the control panel or pulse digital input DI1/DI2 to clear the latching trip.

Preventative Maintenance to Avoid F0044 Faults

Test the full functional safety chain—including all safety switches, light curtains, and safety relay contacts—at least once per year as mandated by functional safety standards IEC 61508 / ISO 13849. Ensure terminal X1C screw clamps remain firmly torqued, and protect safety control wires from pinch points and mechanical abrasion.

Frequently Asked Questions (FAQs)

What is the meaning of F0044 fault in ABB ACS355 drive?

The F0044 fault indicates that the Safe Torque Off (STO) circuit was activated and the drive is programmed to register a latching fault.

What are the primary causes of F0044 fault?

The most common causes are pressed emergency stop buttons, open safety gate contacts, loose wiring on terminal X1C, or 24V supply drops.

How do I troubleshoot and correct F0044 fault?

Close and verify all external safety devices, measure 24V DC across STO terminals IN1 and IN2, and issue a fault reset on the control panel.