F1005 fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F1005 fault in ABB ACS355 drive

The F1005 fault indicates an invalid motor nominal power calculation error in the ABB ACS355 drive. The drive trips to prevent operation because the programmed motor nameplate ratings violate basic electrical power and efficiency ratios.

The motor control algorithm calculates magnetic flux, rotor resistance, and thermal curves based on nominal nameplate data. If the ratio between apparent electrical power and mechanical output power falls outside the permissible physical window of 1.1 to 3.0, vector modulation routines cannot operate safely. The drive halts pulse-width modulation to protect the inverter IGBT bridge and prevent motor stator core saturation.

What Causes F1005 in ABB ACS355?

  1. Parameter 9909 MOTOR NOM POWER entered incorrectly relative to voltage or current ratings.
  2. Incorrect motor nominal current programmed in parameter 9906 MOTOR NOM CURR.
  3. Incorrect motor nominal voltage programmed in parameter 9905 MOTOR NOM VOLT.
  4. Unit selection error between kilowatts (kW) and horsepower (hp) in start-up settings.
  5. Extreme motor-to-drive size mismatch where the motor rating is far outside the drive frame capacity.

Step-by-Step Troubleshooting and Solutions

  1. Locate the motor physical rating plate and record nominal voltage, nominal current, and nominal mechanical power.
  2. Verify that the formula holds true: 1.1 < (9906 · 9905 · 1.73 / PN) < 3.0, where PN = 1000 · 9909 for kW (or PN = 746 · 9909 for hp).
  3. Correct the value in parameter 9909 MOTOR NOM POWER to ensure it matches the nameplate exactly.
  4. Verify that parameter 9905 MOTOR NOM VOLT and parameter 9906 MOTOR NOM CURR are entered accurately.
  5. Disconnect motor cables at terminals U2, V2, W2 and execute a 500V DC insulation megger test to ensure no phase grounding exists.

Preventative Maintenance to Avoid F1005 Faults

Always verify motor nameplate data during commissioning, maintain equipment record sheets for all replacement motors, and re-run motor identification routines whenever machinery motors are swapped.

Frequently Asked Questions (FAQs)

What is the meaning of F1005 fault in ABB ACS355 drive?

The F1005 fault indicates that the programmed motor power, voltage, and current values fail the drive's internal power balance formula.

What are the primary causes of F1005 fault?

Primary causes are incorrect values entered in parameter 9909, unit confusion between horsepower and kilowatts, or extreme motor-to-drive sizing mismatches.

How do I troubleshoot and correct F1005 fault?

Check the motor nameplate, recalculate the power formula using parameters 9905, 9906, and 9909, and correct the entries in Group 99.