F1007 fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F1007 fault in ABB ACS355 drive

The F1007 fault indicates that fieldbus control has not been activated in the ABB ACS355 drive. The drive trips because operational control words or reference speeds have been assigned to fieldbus sources while the communication protocol remains disabled.

When start/stop or reference parameters are pointed to fieldbus commands (COMM), the drive’s internal supervisory controller requires an active fieldbus protocol handler. If parameter 9802 COMM PROT SEL is set to 0 (NOT SEL), the drive detects an orphaned control loop. Inverter pulse-width modulation remains strictly inhibited, preventing IGBT firing across terminals U2, V2, W2 to avoid uncontrolled or uncommanded motor motion.

What Causes F1007 in ABB ACS355?

  1. Parameter 1001 EXT1 COMMANDS or 1002 EXT2 COMMANDS assigned to COMM while fieldbus is deactivated.
  2. Parameter 1103 REF1 SELECT or 1106 REF2 SELECT set to COMM with protocol disabled in parameter 9802 COMM PROT SEL.
  3. Run enable parameter 1601 RUN ENABLE configured to fieldbus control without active communications.
  4. Keypad parameter download from a networked drive onto a standalone hardwired unit.
  5. Fieldbus adapter module removed from expansion slot X3 without reconfiguring control command parameters.

Step-by-Step Troubleshooting and Solutions

  1. Navigate to parameter Group 98 OPTIONS and check parameter 9802 COMM PROT SEL.
  2. Set parameter 9802 COMM PROT SEL to 1 (STD MODBUS) for built-in RS-485 or 4 (EXT FBUS) for an external plug-in adapter.
  3. If operating the drive using hardwired digital and analog terminals, change parameter 1001 EXT1 COMMANDS to 1 (DI1,2) or 2 (DI1P,2P).
  4. Reassign parameter 1103 REF1 SELECT to 1 (AI1) or 2 (AI2) for analog potentiometer control.
  5. Inspect RS-485 serial wiring on terminal block X1C (terminals 29 B+, 30 A-, 31 AGND) to ensure proper connection.

Preventative Maintenance to Avoid F1007 Faults

Maintain separate parameter template files for fieldbus-controlled and hardwired standalone drives, and review command source configurations whenever altering machine control wiring.

Frequently Asked Questions (FAQs)

What is the meaning of F1007 fault in ABB ACS355 drive?

The F1007 fault indicates that the drive has commands assigned to fieldbus control but the fieldbus protocol itself has not been activated.

What are the primary causes of F1007 fault?

Primary causes are selecting COMM for start/speed commands while parameter 9802 is set to NOT SEL, or downloading network parameter backups onto standalone drives.

How do I troubleshoot and correct F1007 fault?

Enable the required protocol in parameter 9802 or reassign parameters 1001 and 1103 to physical digital and analog input terminals.