F1017 PAR SETUP 1 fault in ABB ACS355 drive

Home/ABB/ABB ACS355 drive/F1017 PAR SETUP 1 fault in ABB ACS355 drive

The F1017 fault warns of a digital hardware resource conflict caused by attempting to use high-speed pulse frequency input and pulse frequency output functions simultaneously on the ABB ACS355 drive. The microprocessor halts inverter gating until the shared internal timer channel is reconfigured.

The ACS355 control card features a dedicated hardware timer/counter peripheral that manages high-frequency pulse operations. This silicon resource is shared between digital input terminal 10 (DI3) when configured as a pulse train speed reference (up to 16 kHz) and transistor output terminal 16 (DO) when parameter 1804 (TO MODE) is set to FREQUENCY. Because the internal microcontroller timer cannot decode high-speed incoming reference edges while generating modulated outgoing frequency trains simultaneously, the operating system raises F1017 and prevents motor start.

What Causes F1017 in ABB ACS355?

  1. Parameter 1804 (TO MODE) is set to FREQUENCY while digital input DI3 is selected as a pulse frequency reference in parameter 1103 (REF1 SELECT).
  2. Transistor output frequency mode is enabled while process PID setpoint groups 40 (PROCESS PID SET 1) or 41 (PROCESS PID SET 2) select pulse frequency input.
  3. Parameter 4210 (TRIM SOURCE) or external PID trim parameters in group 42 designate frequency input while 1804 remains in frequency output mode.
  4. Loading a custom macro that inadvertently maps both pulse reference input on DI3 and pulse feedback output on the open-collector transistor terminal.
  5. A restored parameter backup file containing overlapping digital frequency function allocations.

Step-by-Step Troubleshooting and Solutions

  1. Decide whether the application requires a frequency pulse output (e.g., speed feedback to a PLC) or a frequency pulse input (e.g., speed command from a flowmeter).
  2. If frequency output is not needed, navigate to parameter 1804 (TO MODE) and change the value from FREQUENCY to 0 (DIGITAL).
  3. If frequency output is required, inspect parameter 1103 (REF1 SELECT) and parameter 1106 (REF2 SELECT); change any selection from PULSE INPUT (value 6) to an analog input (AI1, AI2) or keypad reference.
  4. Check PID parameter groups: ensure parameter 4010 (SET POINT SEL) and parameter 4110 are not set to PULSE INPUT.
  5. Check group 42 (EXT / TRIM PID); verify parameter 4210 does not reference frequency pulse input, and reset the drive fault via the control panel.

Preventative Maintenance to Avoid F1017 Faults

Standardize application I/O maps during system design to avoid assigning high-speed frequency functions to both input terminal 10 and output terminal 16. If both high-speed pulse feedback and pulse command are required, install an external signal converter or use Modbus RTU communication over RS-485 to transmit speed references.

Frequently Asked Questions (FAQs)

What is the meaning of F1017 fault in ABB ACS355 drive?

The F1017 fault indicates an internal resource conflict caused by configuring high-speed frequency pulse input and frequency pulse output at the same time.

What are the primary causes of F1017 fault?

Primary causes are selecting parameter 1804 as frequency mode while simultaneously setting speed reference or PID inputs to frequency pulse mode on DI3.

How do I troubleshoot and correct F1017 fault?

Change parameter 1804 transistor output mode to digital, or reassign reference inputs in parameter groups 11, 40, 41, or 42 away from pulse mode.