2310 fault in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/2310 fault in ABB ACS380 drive

Fault 2310 in the ABB ACS380 drive indicates that the inverter output current has exceeded the hardware or software instantaneous overcurrent trip limit. The drive immediately cuts pulse-width modulation to the power semiconductors to protect the internal IGBT bridge from irreversible electrical destruction.

During normal switching modulation, internal current transducers measure instantaneous phase current across terminals T1/U, T2/V, and T3/W. When current surges past the maximum threshold—typically exceeding 200% to 350% of nominal rated drive current—the hardware comparator initiates a high-speed gate driver shutdown within microseconds. This protective response isolates the intermediate DC circuit and prevents thermal silicon runaway. The trip can stem from steep acceleration rates, sudden mechanical load shocks, motor insulation degradation, or improper V/Hz magnetization settings.

What Causes 2310 in ABB ACS380?

  1. Excessively aggressive ramp rates programmed in parameter group 23 Speed reference ramp or group 28 Frequency reference chain.
  2. Mechanical machine jamming, seized bearings, or sudden process shock loads on the motor shaft.
  3. Mismatched motor nameplate parameters entered in parameter group 99 Motor data.
  4. Downstream contactors opening or closing on the load side while the inverter is actively modulating.
  5. Ground fault leakage, phase-to-phase insulation breakdown, or presence of power factor correction capacitors on output cables.

Step-by-Step Troubleshooting and Solutions

  1. Increase acceleration time in parameter 23.12 Acceleration time 1 or frequency ramp parameter 28.72 Freq acceleration time 1 to reduce peak starting current.
  2. Disconnect motor leads from terminals T1/U, T2/V, T3/W and perform a 1000V DC megger insulation test; values must exceed 10 MΩ to ground.
  3. Cross-reference parameter group 99 Motor data (specifically 99.06 Motor nominal current and 99.09 Motor nominal speed) against the physical motor nameplate.
  4. Ensure no power factor correction capacitors, surge suppressors, or mechanical switches operate downstream of the drive output.
  5. Inspect speed and frequency scaling parameters 46.01 Speed scaling and 46.02 Frequency scaling to confirm feedback loop calculation accuracy.

Preventative Maintenance to Avoid 2310 Faults

Perform semi-annual insulation resistance testing on output cabling and motor windings. Regularly verify motor terminal torque tightness, audit mechanical drive belts and gearboxes for wear, and ensure auxiliary contacts on output maintenance disconnects interlock directly with the drive run permissive circuit.

Frequently Asked Questions (FAQs)

What is the meaning of 2310 fault in ABB ACS380 drive?

The 2310 fault indicates that output motor current has exceeded the internal peak trip threshold, triggering an immediate shutdown to protect inverter IGBTs.

What are the primary causes of 2310 fault?

Primary causes include rapid acceleration ramp settings, mechanical machine jams, motor winding insulation failure, incorrect motor nameplate parameters, and output switching contactors.

How do I troubleshoot and correct 2310 fault?

Extend ramp acceleration times, perform an insulation megger check on motor cabling, verify parameter group 99 settings, and inspect driven machinery for mechanical binding.